DRA-DCC-8 DIGIT AL TO 8 CURRENT LOOP CONVERTER User’s Guide http://www .omega.com e-mail: info@omega.com.
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGASM Customer Service: 1-800-622-2378 / 1-800-622-BESTSM Engineering Service: 1-800-872-9436 / 1-800-USA-WHENS M TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA Mexico and Latin America: T el: (95) 800-TC-OMEGASM F AX: (95) 203-359-7807 En Espanol: (95) 203 359-7803 e-mail: espanol@omega.
C o n t e n t s 1. MOUNTING INSTRUCTIONS 2. REPLACING FUSES 3. ASSEMBL Y 4. SUPPL Y VOL T AGE 5. MODES OF OPERA TION 5.1 0-20 or 4-20mA output current selection 5.2 Switch Settings 6. P ARALLEL CONTROL MODE 6.1 PLC Inter face 6.2 The "E" (ENABLE) T erminal 7.
1. MOUNTING INSTRUCTIONS 2 The DRA-DCC-8 is designed for standard DIN rail mounting. Place the unit on the upper par t of the mounting rail with the fastening tab facing down. Using a suitable flat screwdriver loosen the tab slightly and attach the unit to the rail.
3 The DRA-DCC-8 is powered by a DC power supply at a range of 15-32Vdc. In order to determine the minimum supply voltage, use the following equation: Vmin = 8 + Rload( Ω ) * 0.02 where: Vmin is the minimum required supply voltage. Rload( Ω ) is the maximum output load including the leads resistance.
4 Figure 2. SW5 MSB Self T est Mode * according to para #5.2 6. P ARALLEL CONTROL MODE * according to para #5.2 In the parallel control mode, the DRA-DCC-8 unit is controlled via a 15 bit bus. Three Address bits (A0-A3) select the proper current output channel and 12 Data bits (D0-D11) determine its value (A0 and D0 are MSB).
5 6.2 THE "E" (ENABLE) TERMINAL For E="1" the unit is enabled, which means that all input vectors are received and the output is updated. When E="0" the unit ignores any new input vector . The E terminal is recommended to be used as a strobe for parallel data which has a long setup time.
6 7.4.1 BAUD RA TE SELECT SW1 and SW2 select one out of four available baud rates. 300 BPS 4800 BPS 9600 BPS 19200 BPS OFF SW1 SW2 OFF ON OFF OFF ON ON ON 7.4.2 ID CODE Up to eight DRA-DCC-8s can be connected in a multidrop configuration. Switches SW3, SW4, and SW5 (MSB) set the ID code.
7 Note: If the value is omitted it will be treated as zero. Separators such as blanks or commas are not allowed. Example: Channel 4 in DRA-DCC-8 no. 7 has to receive the value of 981.
8 8.1 SELF TEST #1 (Communication Por ts T est) In order to test the serial communication por ts, this test mode converts the unit to a transponder for ASCII characters. Any transmitted character will be echoed to the host terminal. The host parameters should be set to: Baud rate : 4800, W ord length: 8 bits, Parity: even, Stop bit: 1 8.
9 11. DRA-DCC-8 CALIBRA TION Generally there is no need to calibrate the DRA-DCC-8 unit. However if calibration is required, the following steps should be carried out: T wo potentiometer trimmers, one for "Zero" and the other for "Span" are located on printed card 7040.
10 INPUTS: P ARALLEL INPUTS LOGIC LEVELS: DA T A HOLD TIME: MAXIMUM P ARALLEL INPUT RA TE: SERIAL COMMUNICA TION BAUD RA TES: P ARITY : STOP BIT : ST A TUS REPORT : MUL TIDROP CAP ABILITY : OUTPUTS: O.
RETURN REQUESTS / INQUIRIES Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBT AIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SER VICE DEP ARTMENT (IN ORDER TO A VOID PROCESSING DELA YS).
Where Do I Find Ever ything I Need for Pr ocess Measurement and Control? OMEGA…Of Course! TEMPERA TURE ⻬ Thermocouple, R TD & Thermistor Probes, Connectors, Panels & Assemblies ⻬ W ire: .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Omega DRA-DCC-8 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Omega DRA-DCC-8 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Omega DRA-DCC-8 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Omega DRA-DCC-8 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Omega DRA-DCC-8, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Omega DRA-DCC-8.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Omega DRA-DCC-8. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Omega DRA-DCC-8 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.