Manuale d’uso / di manutenzione del prodotto SETC del fabbricante Nortec Industries
Vai alla pagina of 20
Manual No. H-504 2008-02-15 RETROFIT INSTRUCTIONS FOR GSTC / SETC / NHTC / NHDI / NHSC Inst allation Manual TM.
Page ii 2008-02-15 PROPRIETARY NOTICE This document and the info rmation disclosed herei n are propriet ary data of W AL TER MEIER L TD. Neither this document nor the information cont ained herein shall be reproduced used, or disclosed to others without the written authoriza tion of W AL TER MEIER L TD.
2008-02-15 TABLE OF CONTENTS Subject Page 10-00 LINKS 2 - FIELD INSTALLATION OF A SE-50 1. FIELD INSTALLATION OF A SE-50 SERIES HUMIDIFI ER WITH A LINKS 2 REMOTE PACKAGE . . . . . . . 2 A. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . .
10-00 Page 1 2008-02-02 10-00 LINKS 2 - FIELD INSTALLATION OF A SE-50.
10-00 Page 2 2008-02-02 (1) FIELD INSTALLATION OF A SE- 50 SERIES NORTEC LINKS 2 REMO TE PACKAGE A. STEP 1 - INSTALLATION (1) Mount the LINKS 2 remote package in a convenient location. Note that the remote package does not need to be mounted in close proximity to the humidifier.
10-10 Page 1 2008-02-15 10-10 LINKS 2 - FIELD CONVERSION OF A GSTC/SETC.
10-10 Page 2 2008-02-15 (1) FIELD CONVERSION OF A GS TC/SETC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: A. WIRING THE NORTEC LINKS 2 MODUL E (1) Most of the wiring conn ec.
10-10 Page 3 2008-02-15 B. MOUNTING THE LI NKS 2 ASSE MBLY (1) Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the GS or SE unit. If pilot holes for the mounting screws are not already present on the humidifier frame follow steps 2 and 3.
10-10 Page 4 2008-02-15 C. CONFIGURING TH E HUMIDIFIERS (1) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can be determined by the presence of the Links module.
10-20 Page 1 2008-02-15 10-20 LINKS 2 - FIELD CONVERSION OF A NHTC.
10-20 Page 2 2008-02-15 (1) FIELD CONVERSION OF A NHTC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: Figure 1. Component Identification A. MOUNT THE LINKS 2 ASSEMBLY (1) The Nortec LINKS 2 assembly mounts on the top, right corner of the elect rical compartment.
10-20 Page 3 2008-02-15 Figure 2. Hook Position Figure 3. Assembly Mounting Location Hook Position Hook Position.
10-20 Page 4 2008-02-15 B. CONFIGURING THE H UMIDIFIERS (1) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can be determined by the presence of the Links module.
10-30 Page 1 2008-02-15 10-30 LINKS 2 - FIELD CONVERSION OF A NHDI/SC.
10-30 Page 2 2008-02-15 (1) FIELD CONVERSION OF A NHDI/SC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: Figure 1. Component Identification A. MOUNT THE LINKS 2 ASSEMBLY (1) Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the NHDI or NHSC unit.
10-30 Page 3 2008-02-15 Figure 2. LINKS 2 Bracket Placement B. WIRING THE NORTEC LINKS 2 MODUL E (1) Most of the wiring connections for the Nortec LINKS 2 module will have already been finished at the factory, however, there are a few connections that will need to be made to connect the module to the NHDI/SC series humidifier.
10-30 Page 4 2008-02-15 Figure 3. NHDI LINKS 2 Slave Installation (3) Installation of LINKS 2 Slave Option (a) The LINKS 2 module is capable of supporting up to 8 humidifiers when each unit is equipped with a TTL to RS-485 signal conv erter. The LINKS 2 slave option consists of a small bracket with the signal converter mounted on one side.
10-30 Page 5 2008-02-15 (4) Configuring the Humidifiers (a) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can b e determined by the presence of the LINKS module and should be set to modbus address 1.
WARRANTY (1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collective ly referred to as THE COMPANY), warrant for a period of two years afte r installation or 30 months from manufacturer’s.
Authorized Agent: INST ALLA TION DA TE (MM/DD/YYYY) MODEL # SERIAL # CYLINDER # U.S.A. W alter Meier (Climate USA) Inc. 826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: nortec@humidity .com WEBSITE: www .humidity .com CANADA W alter Meier (Cli mate Canada) Ltd.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Nortec Industries SETC è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Nortec Industries SETC - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Nortec Industries SETC imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Nortec Industries SETC ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Nortec Industries SETC, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Nortec Industries SETC.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Nortec Industries SETC. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Nortec Industries SETC insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.