Manuale d’uso / di manutenzione del prodotto T3BN del fabbricante Nordyne
Vai alla pagina of 16
Outdoor Heat Pump User’ s Inf ormation and Installation Instructions T3BN Series High Effi ciency Commer cial Split System These instructions are pr imarily intended to assist qualifi ed individuals e xpe- rienced in the proper installation of heating and/or air conditioning appliances.
2 2. Set the ther mostat temper ature to the desired temperature le v el using the temperature selector . Please ref er to the separate detailed thermostat user’ s manual f or complete instructions regarding ther mostat prog ramming.
3 T O MAINT AIN Y OUR HEA T PUMP— CA UTION: Be certain the electrical power to the outdoor unit and the furnace/air handler is disconnected before doing the follo wing recommended maintenance.
4 Read Y our W arranty Please read the separate w arranty document completely . It contains v aluable inf ormation about your system. GENERAL INFORMA TION Read the f ollowing instructions completely before perf or ming the installation. Outdoor Unit Section — Each outdoor unit is shipped with a refrigerant holding charge.
5 The maximum recommended interconnecting refrigerant line length is 75 f eet, and the v er tical elev ation diff erence between the indoor and outdoor sections should not e xceed 20 f eet. Consult long line application guide for installations in e xcess of these limits.
6 Electrical P ower Wiring — Electr ical po wer wiring must comply with the current provisions of the “National Electrical Code” (ANSI/NFP A 70) and with applicable local codes ha ving jurisdiction.
7 GR W 2 CE O Y Thermostat R Air Handler Heat Pump OD Section T ypical Heat Pump with Standar d Air Handler O NO TE: Jumper between W2 and E is required when no OD T -Stat is used.
8 Indoor Blower — Set the thermostat function s witch to COOLING and the fan s witch to ON. V erify that the indoor blo wer is operating and that airfl ow is not restricted. Set the f an s witch back to A UT O . Low-Pressure Switc h — A low-pressure s witch is f actor y-installed (see attached).
9 2. Jumper the “T2”-”DFT” test pins. This will indicate to the board that the defrost T -stat is closed(if the compressor is running). Defrost T -stat is closed at 32° or below and is open at 68° or abov e. But it’ s state is unknown if the temper ature is between 32°F and 68°F .
10 Refrigerant Charging Charts 7.5 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature (F) Liquid Pressure (psig) Ad.
11 Refrigerant Charging Charts 10 Ton HP TXV Charging Chart 150 175 200 225 250 275 300 325 350 375 400 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Temperature (F) Liquid Pressure (psig) Add.
12 REFRIGERANT CHARGING CHAR T Heating Mode of Operation PR OCEDURE FOR CHARGING 10-T ON HEA T PUMP IN HEA TING MODE. 1. Ev acuate the refr igerant system. 2. Charge the system by w eighing in 30 lbs R-22 refrigerant. This is the recommended charge for 5/8 inch 15 f oot line set.
13 RELA Y 4 2 3 1 6 5 T1 T2 T3 CCH C S R T1 T2 C Y O W2 R DFT DF1 DF2 E DEFROST CONTROL BOARD CY O W 2 R E L3 L2 L1 GRD REV VA LVE DFT LOW PRESSURE SWITCH THREE PHASE FIELD SUPPL Y CAP ACITOR CONT ACT.
14 A CCESSORIES — Condensing Unit Low Ambient Kit 913549A- Maintains system pressures during low ambient conditions. PHYSICAL AND ELECTRICAL SPECIFICA TIONS / OUTDOOR UNITS 10.
15.
INST ALLER: PLEASE LEA VE THESE INST ALLA TION INSTRUCTIONS WITH THE HOMEO WNER ¢708538G¤ 708538A 708538A (replaces 7085380) Specifi cations and illustr ations subject to change without notice and without incurring obligations.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Nordyne T3BN è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Nordyne T3BN - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Nordyne T3BN imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Nordyne T3BN ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Nordyne T3BN, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Nordyne T3BN.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Nordyne T3BN. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Nordyne T3BN insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.