FIELDPOINT OPERATING INST RUCTIONS AND SPECIFICATIONS cFP-2200/2210/2220 Intelligent Real-Time Contro llers for Compact FieldPoint Figure 1. cFP-22 xx , Front and Bottom Views 1 RS-232 Serial Port 2 R.
cFP-2200/2210/2220 2 ni.com This document describes how to mount the cFP-2200/2210/2220 controllers, how to connect the controllers to networks, and how to use the feature s of the control lers. This document also contains specif ications for the controllers.
© National Instruments Corporatio n 3 cFP-2200/2210/2220 has the following symbol stamped besi de it: . Connect the backplane PE ground terminal to safety ground usin g 14 A WG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead scre w sh ipped with the backplane to secure the ring lug to the backplane PE ground termin al.
cFP-2200/2210/2220 4 ni.com Figure 3. cFP-22 xx Installed on cFP-BP- x , Bottom View with Dimensions Figure 4. cFP-22 xx Installed on cFP-BP-4, Front View with Dimensions C ab ling Cle a r a nce 4 s lot s = 246 mm (9.6 8 in.) 8 s lot s = 441 mm (17.4 in.
© National Instruments Corporatio n 5 cFP-2200/2210/2220 Figure 5. cFP-BP-8, Back View with Dimensions Figure 6. cFP-BP-4, Back View with Dimensions Caution Make sure that no I/O modules are in the backplane before m ounting it. 104.78 mm (4.1 in.) 63.
cFP-2200/2210/2220 6 ni.com Mounting the Backplane on a DIN Rail The DIN rail mounting kit is NI part nu mber 778614-01. You need one kit to mount the cFP-BP-4 on a standard 35 mm DIN rail. Complete the following step s to mount th e backplane on a DIN rail.
© National Instruments Corporatio n 7 cFP-2200/2210/2220 3. Press do wn firmly on the backplane to compress the spring u ntil the clip locks in place on the DIN rail.
cFP-2200/2210/2220 8 ni.com Figure 10. cFP-BP-4 with Horizontal Panel Mount Kit Installed, Front View with Dimensions Figure 11. cFP-BP-8 with Horizontal Panel-Mount Ki t Installed, Front View with Dimensions Figure 12. Installing th e Vertica l Pa nel-Mount Kit on the cFP-BP-4 260 mm (10.
© National Instruments Corporatio n 9 cFP-2200/2210/2220 Figure 13. cFP- BP-4 with Vertical Pa nel-Mount Kit Installed, Front View with Dimensions Figure 14. cFP- BP-8 with Vertical Pa nel-Mount Kit Installed, Front View with Dimensions 2. Bolt or screw the plates to a panel.
cFP-2200/2210/2220 1 0 ni.com Mounting the Backplane in a Standard 19 in. Rack The rack-mount kit for Compact FieldPoint is NI part number 778 615-01. The following figure shows the dimensions of the rack -mount kit. Figure 15. Dimensions of Rack-Mount Kit Complete the following steps to mount the system in a rack.
© National Instruments Corporatio n 11 cFP-2200/2210/2220 Figure 16. Installing the Rack-Mount Bracket on the cFP-BP-4 Figure 17. Installing the Rack-Mount Bracket on the cFP-BP-8 N AT ION AL INST R .
cFP-2200/2210/2220 1 2 ni.com 2. Bolt the rack-mount bracket to a standard 19 in. rack. 3. Connect the PE ground terminal on the cFP-BP- x to safety ground. Caution Disconnect power and mak e sure that no I/O modules are in the backplane before remov ing it from the rack.
© National Instruments Corporatio n 13 cFP-2200/2210/2220 Installing the cFP-22 xx on the Backplane 1. Make sure that no po wer is connected to the controller . 2. Make sure that the controller is rig ht side up with the NI logo at the top, and align the capti ve scre ws on the controller with the holes on the backplane.
cFP-2200/2210/2220 1 4 ni.com Installing I/O Modules on the Backplane 1. Align the captive scre w s on the I/O modu le with the holes on the backplane. 2. Press firmly to seat the I/O module on the backplane. 3. Using a number 2 P hillips scr ewdri ver with a shank of at least 64 mm (2.
© National Instruments Corporatio n 15 cFP-2200/2210/2220 Installing Connector Blocks on the Backplane In order to connect I/ O modules to input si gnals or loads, you need to install a cFP-CB- x connector block or other conn ectibility accessory for each I/O module on the backplane.
cFP-2200/2210/2220 1 6 ni.com Figure 21. Installing a Connector Block on the Backplane 4. Using a number 2 P hillips scr ewdri ver with a shank of at least 64 mm (2.5 in.) length, tighten the captive scre ws to 1.1 N · m (10 lb · in.) of torque. 5. Repeat this procedure to install additional connector blocks on the backplane.
© National Instruments Corporatio n 17 cFP-2200/2210/2220 Connecting the cFP-22 xx to a Network Connect the cFP-22 xx to an Ethern et network using RJ-4 5 Ethernet port 1 on the controller front panel.
cFP-2200/2210/2220 1 8 ni.com Wiring Power to the cFP-22 xx The cFP-22 xx requires an external power supply that meets the specifications in the Power Requirements section. The cFP-22 xx filters and regulates the supplied power an d provides power for all of the I/O mo dules.
© National Instruments Corporatio n 19 cFP-2200/2210/2220 2. Install a tie wrap or o ther device on the po wer wires to secure the ferrite in place near the controller po wer connector , as shown in Figure 24. Figur e 24. Ferrite Installed with Tie Wrap 3.
cFP-2200/2210/2220 2 0 ni.com Note The controller indicates which terminal it is using on the channel called Power Source in software. A value of 0 indicates V2, and a value of 1 indicates V1. This beh avior is dif ferent from that of older Compact Fiel dPoint contr ollers.
© National Instruments Corporatio n 21 cFP-2200/2210/2220 COM 1 COM 1 is an RS-232 DTE serial port with a standard DB-9 connector. The Serial VIs access COM 1 as port 0. The following fi gure shows the locations of the DB-9 connector pins and Table 1 lists the signals on the pins.
cFP-2200/2210/2220 2 2 ni.com COM 4 (cFP-2220 Only) COM 4 is an RS-485 serial port with a 10-position modular jack. The Serial VIs access COM 4 as port 3. COM 4 has 100 V rms of operational isolat ion. Use an external RS-485 isol ator if your applicat ion requires more isolatio n.
© National Instruments Corporatio n 23 cFP-2200/2210/2220 Figure 27 sho ws how to wire se veral FP-1001 banks in an RS-485 net work controlled by the cFP-2220. Only tw o FP-1001 banks are shown, b ut the cFP-2220 can control up to 24 FP-1001 banks. Inst all 120 Ω termination resistors at each end of the network as s hown in Figure 27.
cFP-2200/2210/2220 2 4 ni.com Y ou can use the two digital input s to control the cFP system from LabVIEW . For example, one input could be a ST AR T/STOP switch, and the other could determine which of two VIs should run at startup.
© National Instruments Corporatio n 25 cFP-2200/2210/2220 Configuring DIP Switches Figure 29. DI P Switches All of the DIP switches are in the OFF position when the controller is shipped from National Instruments. IP RESET Switch Push the IP RESET switch to the ON position and reb oot the controller to reset the IP address to 0.
cFP-2200/2210/2220 2 6 ni.com NO APP Switch Push the NO APP switch to the ON position to pr event a LabVIEW RT startup application from running at startup . If you want to permanently disable a LabVIEW RT app lication from running at startup, you m ust disable it in LabVIEW.
© National Instruments Corporatio n 27 cFP-2200/2210/2220 Using the Reset Button Pressing the Reset button resets the processor in the same m anner as cycling power. Understanding LED Indications Figure 30. LEDs ST A TUS LED The STATUS LED is off during normal operation.
cFP-2200/2210/2220 2 8 ni.com POWER LED The POWER LED is lit while the cFP-22 xx is powered on. This LED indicates that the power supply con nected to the controller is adequate. The POWER LED lights green when the co ntroller i s using the primary p ower supply and amber when the controller is u sing the secondary power supply.
© National Instruments Corporatio n 29 cFP-2200/2210/2220 Remote Front Panels You may need to monitor and cont rol an embedded VI remotely. The cFP-22 xx supports multiple rem ote front panels for embedded VIs. Users can view the remote front panel using either LabVIEW or a Web browser.
cFP-2200/2210/2220 3 0 ni.com T roubleshooting This section contains troubleshoo ting instructions for the cFP-2 2 xx and FieldPoint software. For mo re troubleshooting in formation, refer to the Measurement & Automation Explorer Help for FieldPoint and the Measurement & Automation Explorer Remote Systems Help .
© National Instruments Corporatio n 31 cFP-2200/2210/2220 Specifications The following specifications are typi cal for the – 40 to 70 °C operating temperature range unless otherwi se noted. Network Network interface ....................... .......
cFP-2200/2210/2220 3 2 ni.com RS-232 (DTE) serial ports Maximum baud rate ................ .........115,200 bps Data bits ........... .............. ................. .5, 6, 7, 8 Stop bits ....................... ................ ....1, 1.5, 2 Parity.
© National Instruments Corporatio n 33 cFP-2200/2210/2220 Physical Characteristics If you need to clean the controller, wipe it with a dry towel. Screw-terminal wiring ..... .............. ......... Use copper conductor wire with 10 mm (0.39 in.) of insulation from the ends.
cFP-2200/2210/2220 3 4 ni.com Electromagnetic Compatibility This product is designed to meet the requirements of the follow ing standards of EMC for el ectrical equipment for m easurement, control, an.
© National Instruments Corporatio n 35 cFP-2200/2210/2220 Environmental The cFP-22 xx is intended for indoor use only, but it m ay be used outdoors if mounted in a suitably r ated enclosure. Operating temperature (IEC 60068-2-1, IEC 60068-2-2) ......
cFP-2200/2210/2220 3 6 ni.com Cabling Table 4 shows the standard Ethernet cable wiring connection s for both normal and crossover cables. Figure 31. Ethernet Connector Pinout Table 4.
© National Instruments Corporatio n 37 cFP-2200/2210/2220 Where to Go for Support The National Instrum ents W eb site is your complete resource for t echnical support.
National Instruments, NI, ni.com, and LabVIEW are tradem arks of National Instruments Corporation. Refer to t he Terms of Use section on ni.com/legal for m ore informat ion about Natio nal Instruments trademarks. Other product and compan y names mentioned herein are trademarks or trade names of their respective companie s.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il National Instruments CFP-2220 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del National Instruments CFP-2220 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso National Instruments CFP-2220 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul National Instruments CFP-2220 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il National Instruments CFP-2220, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del National Instruments CFP-2220.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il National Instruments CFP-2220. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo National Instruments CFP-2220 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.