R VS-DX Digit al Sof t S t arter Instruction Manual Power Control Systems April 1, 2004 Part Number: 188-10130 © Copyright 2004 Magnetek.
RVS-DX, Digital Soft Starter Instruction Manual— 04/01/ 04 Contents: Disclaimer of Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii-iii Chapter1: Introduction Overview . . . . . . .
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 Chapter 7: Start-Up Procedure Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3 Start-Up Procedure with Pump Control .
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 i ©2004 MAGNETEK All rights reserved. This notice applies to all co pyrighted materials includ ed with this product, including, but not limited to, this manual and software embodied within the pr oduct.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 ii Disclaimer of W arranty Magnetek, hereafter referred to as Company , assumes no responsibility for im proper programming of a soft starter by untrained personnel. A soft starter should only be pr ogrammed by a trained technician who has read and understands the conten ts of this manual.
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 iii A TTENTION 1. This product was design ed for complianc e with IEC 947-4-2 for class A equipment.
chapter 1 Intr oduction.
This page intentionally left blank..
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 1-3 Overview The R VS-DX is a digital electronic soft starter , incorporating six SC R’ s to start a three phase squirrel cage induction .
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 1-4 No control voltage required) Model Number Max. FLA Frame Size 230/460 V olts* 575 V olt 8 A1 R VS-DX-8-D R VS-DX-8-E 17 R VS-DX-17-D R V.
chapter 2 Installation.
This page intentionally left blank..
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 2-3 Physical Installation Location of the R VS-DX is import ant to achieve proper performance and normal operating life.
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 2-4 Built in Bypass After Acceleration The bypass after acceleration allows the R VS-DX to control the motor during starting and stopping for smooth, step-less acceleration and deceleration. Howe ver , o nce up to fu ll voltage the R VS-DX is bypassed to reduce the watt loss.
chapter 3 R VS-DX T erminals and W iring.
This page intentionally left blank..
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 3-3 Contr ol T erminals T erminal Function Description A1 Control Supply (Note 1) 120V control power must be connected at terminals A1 & A2. A2 B1 Sta rt /St op Input from a N.O. maintained contact.
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 3-4 T ypical W iring Diagram.
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 3-5 Operating “Inside the Delta” Using the R VS-DX soft starter “inside the delta” redu ces the required soft st arter rating by 1.73 ( √ 3) factor . For example, for a 150 amp, 460 volt mo tor , the R VS-DX-170-D is selected to operate in standard “line” mode.
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 3-6 T ypical W iring for Inside the Delta Operation:.
chapter 4 Contr ol Layout.
This page intentionally left blank..
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 4-3 Digital Operator Layout LED Arrangement: LED Description On Lights when control power is connect ed to R VS-DX Ramp Lights during start.
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 4-4 Keypad Arrangement Keypad Description Mode This button scrolls through the following modes: Display Only Main Parameters Sta rt Paramete.
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 4-5 LCD Display The LCD display consists of two lines of alphanum eric characters, displaying: system parameters starter settings, motor current, fau lt indication and statistical data. Th e LCD can be displayed in four different languages: English, French, German and Spanish.
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 4-6 Extended Parameter Setting The R VS-DX incorporates a parameter , “WIDER SETTINGS”, in the special Features Parameters.
chapter 5 Featur es.
This page intentionally left blank..
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 5-3 S tart/S top Featur es The R VS-DX incorporates many fe atures that assist in starting and /or stopping va rious applications. These features are described within this section. Pump Control (S tart Curves) Induction mot ors produce peak torq ue up to three times the rated to rque.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 5-4 Initial V oltage The initial voltage determines the motor ’ s initial torque setting (the to rque is di rectly proportional to the square of the voltage). The initial voltage can be set from 10 to 50%.
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 5-5 S top Curves For many applications, the load torque decreases in a squa re relation to the speed. In these applications, reducing the voltage will reduce the to rque and the motor will smoothly decelerate to a stop.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 5-6 Dual Adjustment The dual adjustment feature allows the R VS-DX to have two sets of startin g characteristics. This feature is very beneficial in ap plications where the motor may be starting loaded or unloaded.
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 5-7 Motor Pr otection Featur es The R VS-DX incorporates advanced microproc essor- based digital circuitry , which allows for sophisticated motor protection with digital accura cy . The motor protection features are covered in detail below .
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 5-8 Undervoltage The under voltage function becomes available only af ter the start signal. The starter will trip when the main voltage drops below the pr eset level for a time period longer than the under voltage delay .
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 5-9 Heatsink Over T emperatur e The starter has thermal sensors mounted on the he atsink, tripping the star ter when the heatsink temperature rises above 85°C. Wr ong Parameters This protection indicates when in correct parameters have been en tered into the EEPROM.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 5-10 Additional Protection A vailable: Short Circuit Pr otection Protects the starter against a short circ uit by SCR protection fuses.
chapter 6 Parameters.
This page intentionally left blank..
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 6-3 Mode Mode Mode Mode Mode Upon Initiation P arameter Display P age 1 P age 2 Page 3 P age 4 Select Select Select Select Select % Of Motor FLA Main P arameters Star t P arameters Stop P arameters Dual Adj.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 6-4 Mode Mode Mode Mode Mode P age 6 P age 7 P age 8 P age 9 Select Select Select Select Select Special F eatures P arameters F ault P arameters I/O Programming P arameters Comm. Parameters Statistical Data Press K eys T o Change P arameter V alue Slow Speed T orq.
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 6-5 * Requires an option card for thes e parameters to be displa yed. If there are no option cards, the display will read,“Option Card—Not Installed”. DISPLA Y MODE Parameter Description De fault V alue Range Access % of MOTOR FLA MOTO R INSULA TI ON* THERMIST OR RES.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 6-6 The User access level is always available. The maximized access is available when Dispaly Mode parameter is set to maximized (changing available param eters from minimized t o maximized lev el), but thes e parameters can only be changed when the R VS-DX is stop ped.
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 6-7 S TOP PARAMETERS Parameter Description/Functio n Default V alue Range Access SOFT STOP CUR VE STOP T ACHO GAIN DEC. TIME FINAL TORQUE STORE ENABLE STOP P ARAMETERS Determines the soft stop curve Allows tach.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 6-8 FAULT PARAMETERS (display mode set to maximized to access) Parameter Descrip tion/Function Default V alue Range Access PHASE SEQ. Y/N INSULA TION ALARM INSULA TI ON TRIP AUTO RESET THERMIST OR TYPE THERMISTOR TRIP UNDER CUR.
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 6-9 (1) The FLC of the R VS-DX is pre-dete rmined by the size of the power section. This setting can be adjusted lower , but not higher than the unit’ s rating. The Motor FLA setting is shown in amps.
chapter 7 S tart-Up Pr ocedur e.
This page intentionally left blank..
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 7-3 S tart-Up Pr ocedur e NOTE: If the motor is NOT connec ted to the load t erminals, the “WRONG CONNECTION” fault indication will appear on LCD display . S tart-Up Procedur e: 1. Connect an N.
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 7-4 High Inertia Loads-Fans, Centrifuges, etc. Initial V oltage (IV)-set 50% Current limit (CL)-set 400% Acceleration time (A T)-set 20 sec. V oltage and current increase until current reaches “ Current Limit”.
RVS-DX, Digital Soft Start er Instruction Manual— 04/01/04 7-5 S tart Up Pr ocedur e With Pump Contr ol St a r t i n g C u r v e 1. Adjust main parameters as necessary (FLA, FLC, etc). 2. Set Starting Curve, Acceleration T ime, Current Limit, and Initial V oltage to their default values (curve 0, 10 sec.
RVS-DX, Digital Soft Start er Instruction Manual—04/01/04 7-6 Final tor que during soft -stopping a pump motor 1. While decelerating, the check valve may close before Deceleration Time has elapsed, thus, allowing current to flow through sta tor winding causing unnecessary heat.
Chapter 8 T r oubleshooting.
This page intentionally left blank..
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 8-3 T r oubleshooting Upon fault the motor stop s, “Fault” LED illuminates and fault relay operates. The LCD will display “T rip: fault description”. Check “Statist ical Data” for add itional fault-related information.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 8-4 WRONG P ARAMETERS Parameters were not transferre d from RAM to EEPROM. This may happen after replacing the EEPROM with a new version progra m.
appendix A T echnical Data/Specifications.
This page intentionally left blank..
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 A-3 R VS-DX T echnical Data/Specifications General Inform ation: Supply V oltage Line to Line 220-600V (to be specified) +10%, -15% Frequency.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 A-4 Control: Displays LCD in 4 (field sele ctable) languages and 4 LEDs Keypad 6 keys for easy setting Aux. Contact–immediate or end of accel 1 N.O., 8A, 250 V AC, 2000 V A Fault Contact 1 N.
appendix B Dimensional Drawings.
This page intentionally left blank..
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 B-3 Dimensional Drawings Protected Chassis RV S - D X 8 - 4 4 A R VS-DX 58-72.
RVS-DX, Digital Soft Start er Instruction Manual—4/01/04 B-4 Protected Chassis R VS-DX 85-105A R VS-DX 145-170A.
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 B-5 Protected Chassis R VS-DX 210-310A.
appendix C Fuse Selection T able.
This page intentionally left blank..
RVS-DX, Digital Soft Starter Instruction Manual— 4/01/04 C-3 Fuse Selection T able *Fuse Kit consists of fuses and fuse blocks. 230 V olt 460 V olt 575 V olt RV S - D X Max. SCR I 2 T Allowed Fuse Amp Rating 250V Fuse Kit* Part Number R V S-DX Max. SCR I 2 T Allowed Fuse Amp Rating 500V Fuse Kit* Part Number R VS-DX Max.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Magnetek 188-10130 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Magnetek 188-10130 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Magnetek 188-10130 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Magnetek 188-10130 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Magnetek 188-10130, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Magnetek 188-10130.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Magnetek 188-10130. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Magnetek 188-10130 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.