Solar Pump Station Installation and Operation Manual SPS0250, SPS0500 & SPS1000 This manual must only be used by a qualified heating installer/ service technician. Read all instructions, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
2 Hazard definitions The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
3 1 General Information Before starting work, the Installer must read, understand and note these installation and operating instructions. WARNING The solar pump station may only be installed and maintained by trained professionals. Trainees may only work on the product under the supervision of an experienced person.
4 Included Components Solar Station: ■ Grundfos solar circulation pump ■ VFS sensor (flow sensor) ■ 145 psi relief valve, with pressure gauge ■ Multi-function instruments (Flow Check, Thermome.
5 2 Installing the solar station Installing the solar station on a wall ■ Remove front insulation shell. ■ The solar pump station forms a single unit with the wall bracket and rear insulation shell.
6 3 Technology, installation and commissioning Clamp ring screw connections ■ Cut the copper pipe to length and deburr. ■ First, slide the clamp ring nut over the pipe, then slide the clamp ring. ■ Insert the prepared pipe into the screw connection until its stop is reached.
7 4 Commissioning the solar system General ■ Before commissioning, all piping, connections and saftey equipment should be checked to ensure that they are correctly installed. ■ All pre-fitted solar station screw connections are firmly tightened in the factory so that they do not usually need retightening.
Solar group with Grundfos UPS 25-58U pump (and GF sensor 0.5-3 GPM) residual delivery height 0 5 10 15 20 25 0,0 0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 V olumetric flow rate [GPM] Residual delivery height [Ft] Max. residual delivery height pressure drop of components Solar group with Grundfos UPS 25-99U pump (and GF-Sensor 0.
9 6 VFS flow sensor Figure 6-1 VFS 1-12 flow ouput signal VFS 1-12 output signal ow Assignment of m easurement range: 0.26-3.17 gpm i s eq ual to 0.5-3.5V Flow rate calculation: Q = 0.26gpm + [(U-0.5)V/3V]*2 .91gpm Figure 6-3 VFS 2-40 flow output signal VFS 2-40 output signal ow Assignment of m easurement range: 0.
10 7 Technical data for solar station Designation SPS0250 / SPS0500 SPS1000 PUMP SPS0250: Grundfos UPS 25 - 58 U SPS1000: Grundfos U P 2 5 - 120 U SPS0500: Grundfos UPS 25 - 99 U SOLAR AND TANK CONNEC.
11 7 Technical data for solar station (continued) Designation SPS0250 / SPS0500 SPS1000 GRAVITY BRAKES Installation location: forward flow and return ball valves Material: Brass Seal: O-ring 70 EPDM 2.
8 Component breakdown 20 3 2 4+5 12+15 25 8+9 22 14 11 23 16 13 26 30 27 24 4 6 17 19 1 10 18 7+9 21 SPS0250/ SPS0500 Item Name – SPS0250 - Pumpstation 250 sq-ft w/ flow sensor and CU – SPS0500 - Pumpstation 500 sq-ft w/ flow sensor and CU 1 Solar return ball valve USA 1 1/2" x M28 x 1.
2 27 4+5 3 19 30 31 11 6+7 9 13 21 4 12 29 17 20+22 10 24 1 18 23 32 8 25 16 26 28 33 34 35 Figure 9-2 SPS1000 8 Component breakdown (continued) 13 SPS1000 Item Name – Pumpstation 1000 sq-ft w/ flow sensor and CU 1 Solar return ball valve 1 1/2" Fl.
14 9 Service De-energize and lock the solar control and pump to prevent them from accidentally being switched back on again by mistake before any maintenance or repair work. Service is not permitted until components and solar liquid have cooled. WARNING ■ The solar station features an air separator.
15 10 Faults, causes and rectification Pump doesn’t run when power is switched on : ■ Check solar control unit for correct settings and tight wire connections. ■ Check fuses. ■ Check pump voltage, refer to the pump rating plate for requirements.
Revision Notes: Revision A (ECO C06520) initial release. Revision B (ECO C07610) reflects formatting adjustments. SL-PS-I-O Rev B 3/11.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Lochinvar SPS0500 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Lochinvar SPS0500 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Lochinvar SPS0500 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Lochinvar SPS0500 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Lochinvar SPS0500, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Lochinvar SPS0500.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Lochinvar SPS0500. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Lochinvar SPS0500 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.