Manuale d’uso / di manutenzione del prodotto UPS del fabbricante APC
Vai alla pagina of 18
990-1074B 01/2006 User Manual English APC Smart-UPS ® 1000/1500 VA 100/120/230 V A C 750/1000XL VA 120/230 VA C Tower Uninterr uptible Pow er Supply.
.
1 Introduction American Po w er Con version Corporation (APC) is the leading national and in ternational manufac- turer of state-of-the- art uninterrupt ible power su pplies, redundant switches, powe r man agement soft- ware, an d related equipment.
2 Connecting Equipment and Power to the UPS S MART -UPS R EAR P ANEL 230V M OD ELS 120V/100V M ODELS 1. Plug in the b attery conn ector n . 2. Connect equ ip ment to the UPS. Note: Do not connect a la ser printer to the UPS. A laser printer d raws significantl y more power than other type s of equipm ent and may overload the UPS.
3 B ASIC C ONNE CTORS Serial Port USB Port Power management s oft ware an d interface kits can be used wi th the UPS. Use only interface kits supplied or appro ved by APC. Use the APC supplied cable to connect to the Serial Port. DO NOT use a standard serial interface cable since it is incompatible with the UPS connector.
4 2: O PERA TION S MART -UPS F RONT P ANEL Power On Power Off Load Battery Charge Online The online LED illuminates when the UPS is supplying utilit y power to the con- nected equipment. If the LED is not lit, the UPS is eit her not turned ON, or is sup- plying battery power.
5 AVR Boost This LED illuminates to indicate the UPS is compensating for a low utility voltage. On Battery When the on batter y power LED is lit the UPS is supplying battery power to the con nected equipment. When on batter y, the UPS sounds an alarm—four beeps ev er y 30 s econds.
6 3: U SER C ONFIGU RAB LE I TEM S N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HU TE SOFTW ARE OR OPTION AL S MA RT S LOT ACCESSORY CARDS . F UNCTION F ACTORY D EFAULT U SER S EL EC TABLE C H.
7 N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HU TE SOFTW ARE OR OPTION AL S MA RT S LOT ACCESSORY CARDS . F UNCTION F ACTORY D EFAULT U SER S EL EC TABLE C HOICES D ESCRIPTION Low B attery Warning .
8 4: S TO R AG E , M A INTENA NCE , A ND T R ANSPORTING Storage Store the UPS covered and positioned as for proper functioning, in a cool, dry location, with the bat- teries fully charged. At -15 t o +30 ° C (+5 to +86 ° F), charge the UPS battery every six months.
9 1500VA Model Step 3 Pull the battery module out of the compartment until t he back of the modu le is flush with th e outer edg es of the UPS. Disconn ect the battery connector. 1000VA Model Step 3 Disconnect the batter y cable termin a ls before re moving t he batt er y module fr om the UP S.
10 R EPL ACING THE B ATTERY M ODULE To replace the battery module, rev erse the directions above for Removin g the Front Bezel and Bat- tery M odule . Disconnecting the Battery for Transport Alway s DISCONNECT THE B ATTERY before shippin g in compliance with U.
11 5: T ROUBLESHOOTI NG Use the chart belo w to so lve minor Smart-UPS installatio n and operatio n problems. Refer to the APC web site, www.apc.com , for assistance with com ple x UPS problems. P ROBLEM AND P OSSI B LE C AUSE S OLUTION UPS WILL NOT TURN ON Batter y not conn ected prop- erly.
12 P ROBLEM AND P OSSI B LE C AUSE S OLUTION T HE OVERLOAD LED IS LIT AND TH E UPS EMITS A SUSTAINED A LARM TONE The UPS is overloaded. The conn ected equi pment exceed s the speci fied “maximu m load” as de- fine d in Specificati ons at the A PC web site , www.
13 P ROBLEM AND P OSSIBLE C AUSE S OLUTION UTILITY CIRCUIT BREAKER T RIPS Utility c ircuit breaker trips dur ing norma l operation. 100V mo dels: In orde r to operate a t the full VA rating of the 1 500VA produ ct, the sup plied 15A pl ug must be replaced with a 20 A plug.
14 Service If the UPS requires s er vice do not return it to the dealer. Instead, follow these steps: 1. Revi e w th e problems discuss e d in th e Troubleshooti ng section of th i s manual to eliminate com- mon probl ems. 2. If the problem persists, contact APC Customer Service through the APC web s ite, www.
15 6: R EGULA TOR Y A ND W ARR AN TY I NF ORMA T I ON Regulatory Agenc y Approvals a nd Radio F reque ncy Warnings 230V MODE LS This is a Class A product. I n a dome stic enviro nment this product m ay cause ra dio int erferenc e, in which cas e the u ser ma y be requi red t o take co rrect ive ac - tions .
16 Declaration of Conformity Limited Warranty America n Power Conversi on (APC) warrant s its produ cts to be free from d efects i n materia ls and workmans hip for a period of two years from th e date of pu rchase.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il APC UPS è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del APC UPS - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso APC UPS imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul APC UPS ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il APC UPS, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del APC UPS.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il APC UPS. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo APC UPS insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.