Thank Y ou! Thank y ou for selectin g the American Power Conversion SmartSlot Series Measure-UPS II . It has been desi g ned for man y y ears of reliable, mainte- nance-free service. Please read this manual! It provides installation and operatin g instructions that will help y ou g et the most from y our accessor y .
Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Operation Check . . . . . . . . . . . . .
1. Introduction The SmartSlot Measure-UPS II performs temperature and humidit y sensin g , as well as contact monitorin g . Measure-UPS II supports up to four zones of contact monitorin g , each of which supports both normall y open and normall y closed contacts.
Safety Notice The SmartSlot Measure-UPS II UPS accessor y is intended solel y for use in supplementar y surveillance of equipment. APC does not recom- mend this product for life or propert y protection. APC will not know- in g l y sell Measure-UPS II for use in such applications.
2. Installation Use the followin g procedure to install SmartSlot Measure-UPS II : 1. Install and configure an y software or hardware that will be used with Measure-UPS II for data reporting (see software and hard- ware compatibility abov e). 2. Using figure 2 as a guide, install Measure-UPS II in the host SmartSlot.
Do not: • Cov er any of the ventilation holes on the probe • Immerse the probe or place it where de w can be expected to form • Use the probe in an en vironment with chlorine gas or insecti- cides. 5. The contact monitoring connection is a two piece design.
3. Operation Check 1. Confirm the basic operation of Measure-UPS II . Use the data reporting system (see hardware and software compatibility in sec- tion 1) to confirm that Measure-UPS II is w orking.
4. Sensor Zone Connections Connection Information Measure-UPS II supports normall y open and normall y closed loop s y stems, and allows mixin g of normall y open and normall y closed sensors on an y zone. See the fi g ures below for more information on usin g multiple sensors in one zone and for s y stem hookup.
In order to avoid receivin g alarm indications on unused zones, install a j umper wire between the COM and NC connectors for each unused zone. T o use more than one sensor on a zone, follow the dia g ram below . Connect normall y open sensors in parallel and normall y open sensors in series.
See below for a t y pical hookup. Note that in this example s y stem zone 1 is a normall y closed motion zone with power for the passive infrared detector supplied b y Measure-UPS II . Zone 2 is a normall y open zone. Zone 3 is a combination normall y open and normall y closed zone.
5. Sensor Selection Measure-UPS II ma y be used with an y dr y contact closure t y pe sen- sors. The Measure-UPS II sensor inputs are desi g ned to monitor cir- cuits that have no volta g e potential of their own.
6. Maintenance Measure-UPS II requires periodic maintenance. Confirm contact sens- in g usin g the sensor manufacturers recommended intervals and meth- ods. Use the data reportin g s y stem to verif y that each sensor operates as planned. Clean the temperature (or temperature and humidit y ) probe whenever there is a visible buildup of dust.
7. T roubleshooting Problem Possible Cause Solution Constant Alarm on one or more unused zones. Unused zones not jumpered. Connect a wire between the COM and NC terminals of all unused zones (see section 4). Constant low tem- perature and humid- ity readings.
8. Service If the SmartSlot Measure-UPS II requires service: 1. Check Measure-UPS II using the troubleshooting chart in section 7 before calling for service. 2. Note the model number of the Measure-UPS II , the serial number , and the date purchased. See the back cov er of this manual for the correct telephone number and call customer service.
9. Specifications Electrical SmartSlot specification compatible Operatin g volta g e: 16 - 27 Vdc Operatin g current draw: 30 mAdc (exclusive of an y attached sensors) T emperature accurac y : ±2° C (± 3.
10. Declaration of Conformity Application of Council Directives: 89/336/EEC Standards to Which Conformit y is Declared: EN55022, EN50082-1 Manufacturers Name: American Power Conversion 132 Fair g roun.
Limited W arranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obli- gation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il APC SmartSlot Series è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del APC SmartSlot Series - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso APC SmartSlot Series imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul APC SmartSlot Series ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il APC SmartSlot Series, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del APC SmartSlot Series.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il APC SmartSlot Series. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo APC SmartSlot Series insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.