7/2012 506945-01 *2P72012* *P506945-01* Page 1 E 2013 Lennox Industries Inc. Dallas, T exas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE W ARNING The State of California has determined that this product may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death.
Page 2 A B SIDE VIEW UNIT DIMENSIONS - INCHES (MM) FIGURE 2 T ABLE 1 UNIT DIMENSIONS Model Numbers A B 13ACX-018-230 24-1/4 (616) 25-1/4 (641) 13ACX-024-230 24-1/4 (616) 25-1/4 (641) 13ACX-030-230 24-.
Page 3 13ACX SERIES ANCHORED HEA VY NYLON WIRE TIE OR AUT OMOTIVE MUFFLER‐TYPE HANGER STRAP LIQUID LINE TO V APOR LINE W ALL STUD LIQUID LINE NON-CORROSIVE MET AL SLEEVE V APOR LINE - WRAPPED IN ARM.
Page 4 STEP 2 -- REFRIGERANT PIPING -- Flushing Existing Line Set and Indoor Coil Flush the existing line set per the following instructions. For more information, refer to the Installation and Service Procedures manual available on DaveNet.
Page 5 13ACX SERIES STEP 2 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device SENSING LINE TEFLON ® RING FIXED ORIFICE BRASS NUT LIQUID LINE ASSEMBL Y (INCLUDES STRAINER) LIQUID LINE O.
Page 6 STEP 2 -- REFRIGERANT PIPING -- Brazing Procedures A TT ACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / V APOR LINE SERVICE V AL VES OUTDOOR UNIT LIQUID LINE V APOR LINE LIQUID LINE.
Page 7 13ACX SERIES WHEN BRAZING LINE SET TO SER VICE V AL VES, POINT FLAME A WA Y FROM SER VICE V AL V E. LIQUID LINE SERVICE V AL VE LIQUID LINE BRAZE LINE SET Wra p both service valves with water -saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set.
Page 8 STEP 2 -- REFRIGERANT PIPING -- Installing Indoor Expansion V alve This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or expansion valve metering device (purchased separately) at the indoor coil.
Page 9 13ACX SERIES STEP 3 -- LEAK TEST AND EV ACUA TION A With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only). B Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit.
Page 10 STEP 3 -- LEAK TEST AND EV ACUA TION (CONTINUED) A Open both manifold valves and start the vacuum pum p. B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury). NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once.
Page 1 1 13ACX SERIES STEP 4 -- ELECTRICAL -- Circuit Sizing and Wire Routing In t he U .S .A., w iring must conform with current local codes a nd the current National Electric Code (NEC). In Canada, wiring must conform with cur rent local codes and the current Canadian Elec trical Code (CEC ).
Page 12 STEP 4 -- ELECTRICAL (CONTINUED) -- High V oltage and Field Control Wiring The following illustration provide an example of control wiring connections when using standard thermostat. Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring.
Page 13 13ACX SERIES T ABL E 3 . T O RQUE REQUIREM ENTS Parts Recommended Torque Service valve cap 8 ft.- lb. 1 1 NM Sheet metal screws 16 in.- lb. 2 NM Machine screws #10 28 in.- lb. 3 NM Compressor bolts 90 in.- lb. 10 NM Gauge port seal cap 8 ft.- lb.
Page 14 CHECKING AND ADDING SYSTEM REFRIGERANT The 13ACX unit is factory-charged with enough HFC-410A refrigerant to accommodate a 15-foot length of refrigerant piping. Charge should be checked and adjusted using the tables provided on the charging procedure sticker located o n th e unit access panel.
Page 15 13ACX SERIES 13ACX Start-Up and Performance Checklist Customer Address Indoor Unit Model Serial Outdoor Unit Model Serial Notes: ST ART UP CHECKS Refrigerant T ype: Rated Load Amps: Actual Amp.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Lennox International Inc. 506945-01 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Lennox International Inc. 506945-01 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Lennox International Inc. 506945-01 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Lennox International Inc. 506945-01 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Lennox International Inc. 506945-01, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Lennox International Inc. 506945-01.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Lennox International Inc. 506945-01. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Lennox International Inc. 506945-01 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.