Manuale d’uso / di manutenzione del prodotto 20 - 200 KVA del fabbricante APC
Vai alla pagina of 40
E-51028230XT/BG - 1 User manual MGE™ Galaxy™ PW 20 - 200 kV A.
2 - E-51028230XT/BG.
E-51028230XT/BG - 3 Contents Introduction General characteristics of MGE™ Galaxy™ PW UPSs ......................................... 5 System description ..............................................................................................
4 - E-51028230XT/BG All products in the MGE™ Galaxy™ PW range are protected by patents. They implement original technology not available to competitors of APC by Schneider Electric. To take into account evolving standards and technology, equipment may be modified without notice.
E-51028230XT/BG - 5 Introduction General characteristics of MGE™ Galaxy™ PW UPSs UPS power rating in kVA 20 30 40 50 60 80 100 120 160 200 Normal AC input number of conductors 3 phases rated volta.
6 - E-51028230XT/BG System description (see figure 1) ◗ a rectifier/charger module (A) converts 3-phase AC power from the normal AC source supply (1) into DC power for the normal inverter input and .
E-51028230XT/BG - 7 Different types of MGE™ Galaxy™ PW systems Frequency converter without battery backup power Parallel UPS system Fig. 2 Single-UPS unit Fig. 3 Frequency converter with battery backup power Fig. 4 See figure 5 showing two parallel- connected (redundant) UPS units.
8 - E-51028230XT/BG Introduction (cont.) Operation in on-line mode Normal operation Normal AC source power is available (see figure 7). ◗ lights 1 , 4 and 5 shine green on the control panel; ◗ the.
E-51028230XT/BG - 9 Operation with the normal AC source restored See figure 9. When normal AC source power (1) is restored or its voltage returns to within specified tolerances, the system automatically returns to its normal operating mode described above (on the condition it did not reach the end of battery power).
10 - E-51028230XT/BG Introduction (cont.) Operation with bypass AC source restored ◗ no battery discharge (see figure 11). When bypass AC source power supply (2) is restored or returns to within specified tolerances, the load is transferred back to the static bypass (C) , without an interruption in the supply of power.
E-51028230XT/BG - 11 Parallel UPSs with redundancy ◗ the shutdown of one UPS unit is of no consequence for the load. The others each take up an equal amount of load power and the load continues to b.
12 - E-51028230XT/BG Operation with an engine generator set See figure 15 below. If a stand-by generator is included in the installation, it is generally started automatically in the event of a normal AC source failure and connected to the main low voltage switchboard.
E-51028230XT/BG - 13 UPS cubicle The rated outputs for MGE™ Galaxy™ PW UPSs (or frequency converters) are 20, 30, 40, 50, 60, 80, 100, 120 , 160 and 200kVA.
14 - E-51028230XT/BG Control panel Battery cubicle Figure 17 shows an example of component layout in a battery cubicle or a battery circuit-breaker enclosure. Legend for figure 17: 1 - battery isolation and protection circuit breaker QF1, 2 - battery cells.
E-51028230XT/BG - 15 "Inverter" light 4 ◗ light off: inverter OFF; ◗ light flashing green: inverter starting, inverter ON but not connected to the load; ◗ light shines green: normal in.
16 - E-51028230XT/BG Keys 1 0 and 1 1 These keys are used to select commands in the main menu and access the secondary messages. Key 1 2 This key is used to validate the user’s choice.
E-51028230XT/BG - 17 Parallel UPS unit for increased output See figure 21. Proceed in the following order: ◗ check that all load devices are off or that the load is disconnected; ◗ close the upstream switch supplying normal AC source power (on the LV switchboard); ◗ close the normal AC input switches Q1 on the UPS units.
18 - E-51028230XT/BG Start-up of a module Start-up of a rectifier/ charger ◗ rectifier/charger start-up is automatic when the normal AC input switch Q1 is closed: ◗ ◗ the green "rectifier/charger" light 1 on the control panel goes on; ◗ close battery circuit breaker QF1.
E-51028230XT/BG - 19 Shutdown of a rectifier/ charger Except in frequency converters without a battery, it is recommended not to stop the rectifier/charger because the battery will no longer be charged.
20 - E-51028230XT/BG Display of messages In addition to keypad operations, the graphical display brings up a window giving the overall device status. The message displayed is then said to be primary (see list in the paragraph below).
E-51028230XT/BG - 21 LOAD PROTECTED BATTERY DISCHARGING Remaining battery time (min) = XX % kW used = XXX The load is supplied by the inverter, but the normal AC source is down or outside tolerances and power is supplied by the battery. This message indicates the remaining battery time in minutes prior to inverter shutdown and the percent load.
22 - E-51028230XT/BG MAINS 1 OUTSIDE TOLERANCES, CHECK MAINS 1 The normal AC source (M1) frequency or voltage is outside specified tolerances and the rectifier/charger has shut down. The inverter is on battery power. MAINS 1 INPUT SWITCH Q1 IS OPEN The normal AC input (M1) switch Q1 is open.
E-51028230XT/BG - 23 THE NUMBER OF UPS READY IS INSUFFICIENT, LOAD TRANSFER IN STAND BY This message may be displayed in non- redundant, parallel UPS systems, when the number of ready inverters in not sufficient to supply the load.
24 - E-51028230XT/BG ◗ bypass AC source 2 ◗ ◗ phase-to-neutral voltage, ◗ ◗ phase-to-phase voltages, ◗ ◗ frequency, ◗ ◗ currents of the three phases; ◗ battery 3 ◗ ◗ voltage; .
E-51028230XT/BG - 25 Selections and settings These selections and settings may be accessed by pressing the "contrast" key 1 3 . The following menu is displayed. Battery measurements These measurements may be accessed by pressing the "battery" key 1 9 .
26 - E-51028230XT/BG Control-panel display (cont.) ◗ Inverse video: When this function is selected, the text and background colours are reversed (white text on black or black text on white). ◗ Past events: See section "logging and time- stamping".
E-51028230XT/BG - 27 TEST INTERRUPTED CHECK PRESENCE OF THE BATTERY CHECK ALARMS ◗ ◗ the screen opposite is displayed when the battery test cannot be completed.
28 - E-51028230XT/BG General The autodiagnostic system considers any system status other than normal as a problem. Before taking any action , note down the messages displayed on the control panel. Certain problems may prevent the control panel from functioning.
E-51028230XT/BG - 29 ◗ signal to open battery circuit breaker(s) QF1 in the event the "emergency off" button is pressed or to avoid an excessive battery discharge (lasting more than three .
30 - E-51028230XT/BG Logging and time-stamping Presentation of event time-stamping by MGE™ Galaxy™ PW Time-stamping of events by MGE™ Galaxy™ PW makes it possible to: ◗ log the events; ◗ c.
E-51028230XT/BG - 31 DATE AND TIME SETUP > YEAR 1997 MONTH 9 DAY 8 HOURS 8 MINUTES 11 SECONDS 42 02/09/1997 07:25:03 Appearance: MAINS 1 INPUT SWITCH Q1 IS OPEN Example: Note: numerical values are never indicated in screens for time-stamped events.
32 - E-51028230XT/BG Logging and time-stamping (cont.) ◗ total time with Tbatt > 25° C (h): this is the total time of operation with the battery temperature greater than 25° C since initial startup of the UPS.
E-51028230XT/BG - 33 BACKUP (min) T=30 days last read: 05/09/1997 1 2 0 |0 |0 |0 |0 1 1 5 |0 |0 |0 |0 1 1 0 |0 |0 |0 |0 1 0 5 |0 |0 |0 |0 0| 0| 0| 0| 0 0| 0| 0| 0| 0 OUTPUT LOAD LEVEL(%) T=30 days las.
34 - E-51028230XT/BG Maintenance Maintenance configuration Single-UPS unit or UPS in "ECO" mode See figure 24. During maintenance, the UPS must be isolated from the normal and bypass AC source, the battery and the load.
E-51028230XT/BG - 35 Redundant, parallel UPS See figures 27 and 28 in the Appendix. During maintenance, a UPS unit must be isolated from the normal AC source, its battery and the output circuits of the other UPS units.
36 - E-51028230XT/BG 1 0 1 0 0 1 1 0 1 1 0 1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 2 3 4 5 1 0 1 0 1 0 Q5N Q4S Q3BP Q5N Q4S Q3BP Q5N Q1 Q4S QF1 0 I bypass 600 kV A bypass 150, 360 kV A 7 2 3 4 5 5 6 1 MGE Ga.
E-51028230XT/BG - 37 Battery maintenance Consult the instructions supplied by the battery manufacturer. Below are a few general indications: ◗ sealed lead-acid batteries: these batteries require no .
38 - E-51028230XT/BG Maintenance (cont.) T raining center Training centers Schneider Critical Power & cooling services 50 Hz : France Training Centre 140, Avenue Jean Kuntzmann Innovallée 38334 -.
E-51028230XT/BG - 39 Harmonics filter and power factor improvement This option, placed on the normal AC input upstream of the UPS in the 1.9 meter high UPS cubicle for UPSs up to 120 kVA and in an auxiliary cubicle for higher ratings, reduces the reinjection of harmonic currents into the normal AC source.
40 - E-51028230XT/BG Empty cubicles Cubicles may be supplied empty, thus enabling users to make up their own auxiliary cubicles (battery cubicles or other) or panels and meet the particular demands of each installation. In this way, the entire electrical installation will have a uniform appearance.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il APC 20 - 200 KVA è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del APC 20 - 200 KVA - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso APC 20 - 200 KVA imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul APC 20 - 200 KVA ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il APC 20 - 200 KVA, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del APC 20 - 200 KVA.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il APC 20 - 200 KVA. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo APC 20 - 200 KVA insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.