Inst allation PDPM150G6F PDPM150L6F PDPM175G6H 150/175kW Modular PDU.
.
Content s 150/175kW Modular PDU Installation i Overview ....................................... ................................... 1 Important Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Disclaimer . . . . . .
150/175kW Modular PDU Installation ii Power Distribution Modules (PDM s) . . . . . . . . . . . . . . . . . . . . . . . . . 14 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Remove power distribu tion modules (PDMs) .
1 150/175kw Modular PDU Installa tion Overview Import ant Safety Information Read the instructions caref ully and l ook at the equipment to be come familiar with the device before trying to install, operate, service or maintain it.
150/175kw Mod ular PDU In stallation 2 Disclaimer The information presented in this manual is not warranted by Schn eider Electric to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan.
3 150/175kw Modular PDU Installa tion Additional Safety Information Before you begin V erify that the system is free from all short circ uits and gr ounds, except those gro unds installed according to local regulations (according to the Na tional Electrical Code in the U.
150/175kw Mod ular PDU In stallation 4 About This Manual This manual is intend ed for users of the specified APC equipmen t. It contains important safety warnings and instructions, gives an introduc tion to the display interface and pr ovides detailed information for proper use of the equipmen t.
5 150/175kw Modular PDU Installa tion Inst allation Electrical Safety SA VE THESE INSTRUCTIONS! This document contains important instructions that should be follo wed during installation of the 150/ 175kW Modular Power Distribution Unit (PDU). Inrow Inst allation Maintain 36” hot aisle spacing.
150/175kw Mod ular PDU In stallation 6 Perform Equipotential Bonding Proper bonding is essential to create an equipotential plane between service grounds and eq uipment du ring fault and transient conditions. Connect the two equipotential bonding conductors between adjacent enclosures in the system.
7 150/175kw Modular PDU Installa tion Inst all Input Power Cables T op entry installation 1 Open the front door . Unlatch and swing the display interface and bracket out towards the front door . 2 Loosen the captive screws and remove the top safety pane l.
150/175kw Mod ular PDU In stallation 8 Bottom entry installation Note: The sidecar is required for undefloor wiring in to the PDU. The Sidecar does not contain a switch or circuit breaker so a readily acce ssib le disconne ct device shall be incorp orated external to the equipment.
9 150/175kw Modular PDU Installa tion 3 T ake the cables that are preinstalled in the Side Car and route them through the left side into the PDU. pdx0879a P ower In T o PDU.
150/175kw Mod ular PDU In stallation 10 Inst all Subfeed Cables 1 Open the rear doors. 2 Remove the subfeed safety panel. 3 Loosen the four captive screws on each of two rear dedicated cover plates. Drill holes in the plates for conduits and re-install the plate with the conduits installed.
11 150/175kw Modular PDU In stallation Inst all User Input/Output Cont act s Note: Contact wires from external sign aling, alarming, and sensing devices may be connected to the interface board to allow the contro ller to monitor these devices and to also control outside devices through the output con tacts.
150/175kw Mod ular PDU In stallation 12 5 Make connections to the labelled terminals on the interface board. Note: Input Contacts are Normally open or Normally closed. A vailable Output Contacts: DPDT , 1A@30VDC AST0, AST1, AST2, ASTEN, AC/DC, +24V , and EPO CONT ACT are reserved and not available.
13 150/175kw Modular PDU In stallation Inst all the Communication Cable 1 Connect the CA T -5 cable for StruxureW are Central or your local area network to the RJ45 conn ection coupling on top of the PDU. 2 Inside the PDU enclosure, a second CA T - 5 cable is conn ected to the other side of RJ45 coupling.
150/175kw Mod ular PDU In stallation 14 Power Distribution Modules (PDMs) Inst al lation Note: 1. Power distribution modules can be safely installed when the PDU is operational. 2. Install only APC-supplied PDMs with matching output voltage. 3. Install PDMs starting from the bottom of the panel to avoid cable congestion.
15 150/175kw Modular PDU In stallation 6 Slide the PDM into the panel using the top and bottom guide tracks for that position. Make sure you slide the PDM all the way into its position. 7 Close the latch. This will tighten electrical contacts in the PDM against the busbar .
150/175kw Mod ular PDU In stallation 16 Options Shielding T roughs 1 Snap an APC-provided trough into sl ots on the roof of the PDU. The tabs at the base of the trough must fit securely into the slots. Note: Properly align the PDU trough wit h troughs installed on to p of the enclosures locate d adjacent to the PDU.
17 150/175kw Modular PDU In stallation Seismic S t ability Kit Inst all rear anchoring brackets 1 Secure the floor anchoring bracket to the floor using floor anchoring bolts (no t supplied). Use M12 strength class 8.8 or 1/2 inch, grade 5 steel bolts.
150/175kw Mod ular PDU In stallation 18 Inst all front anchoring bracket 1 Secure the front anch oring bracket to the enclosure. 2 Secure the front anchorin g bracket to the floor using floor anchoring bolts (no t supplied). Use M12 strength class 8.8 or 1/2 inch, grade 5 steel bolts.
19 150/175kw Modular PDU In stallation S pecifications AC Input Model PDPM150G6F PDPM150L6F PDPM175G6H Nominal voltage 480V , 3W +G 600V , 3W +G 480V , 3W + G Frequency 60 Hz 60 Hz 60 Hz Maximum conti.
150/175kw Mod ular PDU In stallation 20 Note: Circuit breakers and conductor ampacity are derated in accordance with the National Electrical Code. Distribution T ransformer Model PDPM150G6F PDPM150L6F.
21 150/175kw Modular PDU In stallation Recommended conductor sizes Note: All wiring must comply wi th all applicab le national and or local electrical codes.
150/175kw Mod ular PDU In stallation 22 Regulatory Agency Approval This equipment has been tested and found to comp ly with the limits for a Class A digital device, pursuant to Part 15 of the FCC and ICES-003 Rul es.
Radio Frequency Interference Note: Changes or modifications to this unit not e xpressly approved by the party responsible for compliance could void the user ’ s authority to operate this equipment. USA — FC C This equipment has been tested and found to comp ly with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
5/2012 990-4384 APC W orldwide Customer Support Customer support for this or any other APC product is available at no char ge in any of the following ways: • V isit the APC W eb site to acce ss documents in the APC Knowledg e Base and to submit customer support requests.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il APC 175kW è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del APC 175kW - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso APC 175kW imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul APC 175kW ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il APC 175kW, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del APC 175kW.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il APC 175kW. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo APC 175kW insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.