INST ALLA TION, OPERA TION & MAINTENANCE INSTRUCTIONS 9013-0001 (3/08) WELL-X-TROL ® WELL-X1 ™ INST ALLER: LEA VE THIS MANUAL WITH THE OWNER IMPORT ANT GENERAL SAFETY INFORMA TION - ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
1. T ABLE OF CONTENTS GENERAL SAFETY INFORMA TION ........................................................... 2 COMPONENTS ........................................................................................... 3 INST ALLA TION AND SIZING CONSIDERA TIONS .
3 3. COMPONENTS The W ell-X1 ™ combines all the standard well tank components in a single, easy to install package. The pressur e tank, control and tank fittings are factory-installed. After removing from the carton, inspect the W ell-X1 ™ for damage and ensure all components ar e present.
4 4. INST ALLA TION AND SIZING CONSIDERA TIONS The W ell-X1 ™ functions like a traditional pressure switch by cycling the pump on and off. The factory pressure settings are 40 psi cut-in and 60 psi cut-out. The controller allows these settings to be adjusted to best suit the application.
5 5. INST ALLA TION CONSIDERA TIONS LOCA TION The W ell-X1 ™ is designed for indoor and outdoor installations. The NEMA 3R enclosure can be installed in direct weather . If installed outdoors, be sure the following conditions are met: • Do not install where ambient temperatures can drop below freezing or exceed 120° F .
6 6. PLUMBING 1. Plumbing connections are similar to a traditional "tank cross" or "tank tee". Provisions are made for popular line sizes via a 1-1/4" NPT male outer thread and a 1" NPT female inner thr ead. The plumbing connections are not directional and allow flow from either side.
7 4. Connect the water line fr om the well pump to the inlet of the W ell-X1 ™ . 5. Plumb the outgoing supply to the building's water supply system or into the water treatment equipment (if present). 6. Install a blow down tube from the relief valve to a drain or to within 6" of the floor as requir ed by local codes.
8 7. WIRING LINE LINE MOTOR MOTOR BLACK WHITE/STRIPE BLUE WHITE TA B TA B SCREW 1. Shut off the circuit br eaker for the well system. Loosen the top screw housing cover . Flip the cover forward and remove to expose the contr ol wires. Electrocution hazard.
9 8. ST AR TUP & ADJUSTMENT 1. After plumbing and wiring are complete, close the service valve to allow startup without pr essurizing the entire plumbing system. If a service valve was not installed, close all fixtures in the home. Ensure the bottom drain is closed.
10 8. ST AR TUP & ADJUSTMENT (con't) 5. The factory cut-out (pump off) setting is 60 psig. When the pump reaches 60 psig, the W ell-X1 ™ will shut the pump off.
11 1. T o enter the programming mode, press and hold the MODE button until LO appears. This is the cut-in setting. Factory default will be 40 psi. 2. Use the s and t arrows to raise or lower the cut- in setting. Adjustment can be made within 10 psig or as wide as 55 psig of the cut-out setting to 60 psig.
12 3. T o adjust the cut-out, depress MODE once and the display will read HI . Again, press the t or s buttons to raise or lower the setting. The same 10-55 psig differ ential range applies. Maximum setting is 80 psig. 4. After adjusting the cut-in and cut-out, r elease the buttons.
13 9. PUMP PROTECTION AND DIAGNOSTICS The W ell-X1 ™ continually monitors pr essure, cycle time and voltage to protect the well pump. The following error codes alert the user to a potential problem, pr ompting service.
14 10. TROUBLESHOOTING PROBLEM POSSIBLE CAUSE SOLUTION Alarm sounds 1. Error encounter ed 1. See Error Code section for possible causes. No water at fixtures 1. Error encounter ed 2. No power 3. W ater line obstructed 4. Faulty pump 5. Drain or relief valve open 6.
15 11. REPLACEMENT P AR TS DESCRIPTION POSITION WX1-202 WX1-203 WX1-250 WX1-251 WX1-302 Replacement tank: Blue 1 144R273 146R825 145R379 145R380 150R92 Replacement tank: T uf Kote™ 1 144R274 146R826.
16 AMTROL INC. LIMITED PRODUCT WARRANTY Products cover ed: all Products manufactured by AMTROL Inc. (“AMTROL”). This warranty cannot be transferred – it is extended only to the original Purchaser or First User of the Product.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Amtrol WELL-X-TROL è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Amtrol WELL-X-TROL - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Amtrol WELL-X-TROL imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Amtrol WELL-X-TROL ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Amtrol WELL-X-TROL, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Amtrol WELL-X-TROL.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Amtrol WELL-X-TROL. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Amtrol WELL-X-TROL insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.