Manuale d’uso / di manutenzione del prodotto CR del fabbricante Hubbell Electric Heater Company
Vai alla pagina of 25
OPERATING AND MAINTENANCE MANUAL FOR INSTANTANEOUS ELECTRIC CIRCULATION HEATER ELECTRIC HEATER COMPANY BASE MODEL “ CR ”.
2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: http://www.hubbellheaters.com/ -- IMPORTANT -- Always reference the f ull model num ber and serial number when calling the factory. WARNING / CAUTION 1.
3 TABLE OF CONTENTS SECTION TITLE PAG E # I GENERAL DESCRI P TI ON AND CONSTRUCTION 5 II INSTAL LATI ON 12 III S C H E D U LE D M A IN TE NANC E AND OPERATION 14 I V TROUBL ES HOOTI NG 15 V S E R V I .
4.
5 SECTION I - GENERAL DESCRIPTION AND CONST RUCTION GENERAL DESCRIPTION This book describes a packaged electric heater that is a stationary , self-contained unit.
6 OUTER SHELL, INSULATION, AND SUPP ORTS The pressure vessel is encapsulated in 2-inches of high-density fiberg lass insulation. The protective shell is constructed of galvaneel and is coated with a durable silver hammertone finish. The horizontal configuration is supported on heavy -duty steel I-beam supports.
7 CONTROL THERMOS TAT The control pane l is supplied standard with a single- stage immersion thermosta tic switch. As an optional any of the following may be supplied; a four- stage immersion thermosta tic switch, a solid-state staging controller with thermistor, or a digital 1/16 DI N temperature controller with thermocouple.
8 TEMPERATURE HIGH LIMIT SWIT CH As a safety device, an immersion high temper ature cut-off switch with manua l reset, adjustable throug h a range of 100° - 240° F, is provided. The high limit must be manually reset thereafter to restart the heater.
9 INDIVID UALLY FUSED ELEM ENTS To prevent the possibility of damage to c ontrol circuits a nd other eleme nts in case of electrica l overloads, fuses may be suppl ied for each element. Two types of fuses may be used; a ty pe NON for voltages less than 250-volt or ty pe JJ S for voltage less than 600-volt.
10 On / Off Control Switc h A built-in non-fused On/Off disconnect switch may be supplied with the control panel to decrease the risk of injury when working with the c ontrol panel. Buil t-In Circui t Breaker A built-in circuit breaker may be provided with or without shunt trip protection for protection from circuit overload.
11 Silicon Control Re ctifier An SCR “zero fired” power controller for 0-100% proportional control of heaters may be supplied. Dial Temperature an d Pressure Gauge A combination temperature (70° .
12 SECTION II – INSTALLATION WARNING / CAUTION DO NOT TURN ON THE ELECTRI C POWER SUPPL Y to this equipment until heate r is completely filled with water and all air has been re leased. If the heater is NOT fille d with water when the power is turned on, the heating elements will burn out.
13 Outlet to floor drain I nstall into provided tapping Manual Release Lev e r Temperature and Pressure Relief Valve 4. I nstall a relief valve overflow pipe to a nearby floor drain. CAUTION: No valve of any ty pe should be installed between the relief valve and tank or in the drain line.
14 SECTION III - SCHEDULED MAINTE NANCE AND OPERATION WARNING / CAUTION Before performing any maintenance procedure, make certain power supply is OF F and cannot accidentally be turned on. MAINTENANCE AND OPERATION The heater is automatic in its operation.
15 SECTION IV – TROUBLESHOOTING Symptom Probable Cause Corrective Action / Remedy Circuit breaker tripped at source. Reset circ uit breaker. On/Off switch in ‘OF F’ position, if installed. Turn switch to ‘ON’ position. Circuit breaker at control cabinet trippe d, if installed.
16 Faulty thermostat. Chec k thermostat adjustment. Monitor thermostat as described in S e ct i o n III, Q u a rt e r l y In s p e c t i on. Replace if necessary.
17 SECTION V - SERVICING & REPLACEMENT OF PARTS WARNING / CAUTION Before servicing or replacing any part make sure to turn the power supply switch to the OF F position. MAGNETIC CONTACTOR 1. Disconnect power from unit. 2. Disconnect line and load wires to contactor.
18 IMMERSION TEMPERATURE HIGH L IMIT CUT-OFF 1. Disconnect power from unit. 2. Remove access cover. 3. Remove high limit c over screw and cover. Cover Cover Screw Reset Switch 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell 6.
19 IMMERSION THE RMOSTAT 1. Disconnect power from unit. 2. Remove access cover and locate t hermostat. 3. Remove high limit c over screw and cover. Cover Cover Screw 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell.
20 HEATING ELEM ENT 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Attach hose to drain connection. 4. Lift manual release lever on relief valve to let air into sy stem or break union on outgoing water line. 5. Drain water from tank.
21 RELIEF VALVE 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Lift test lever on relief valve to relieve pressure in tank. 4. Disconnect overflow piping. 5. Unscrew relief valve, remove assemb ly and repl ace with new one. 6. Connect overflow piping.
22 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS NEMA ENCLOSURE S.
23 ELECTRICAL D ATA.
24 FORMULAS.
25 TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI LI CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.6 5.4 6.1 3.6 6.9 6.7 5-40 7.7 6.3 7.1 4.2 8.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Hubbell Electric Heater Company CR è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Hubbell Electric Heater Company CR - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Hubbell Electric Heater Company CR imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Hubbell Electric Heater Company CR ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Hubbell Electric Heater Company CR, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Hubbell Electric Heater Company CR.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Hubbell Electric Heater Company CR. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Hubbell Electric Heater Company CR insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.