Industrial Automation and Control, 110 Virginia Drive, Fort Washington, PA 19034 Printed in U.S.A. ■ Copyright 1997 Honeywell Inc. UDC3000 Versa-Pro Universal Digital Controller 51-52-03-07 2/97.
51-52-03-07 Page 2 Features, continued CE Mark- Conformity with 73/23/EEC, Low Voltage Directive and 89/336/EEC, the EMC Directive Moisture Resistant Front Panel - Capable of meeting NEMA 3 and IEC529 IP65 (i.e. hosedown) requirements. Timer - This standard feature pro- vides a configurable time period of 0 to 99 hours, 59 minutes.
51-52-03-07 Page 3 Output Types The following output types are available per the model selection guide: • Current output • Electromechanical relays • Solid state relays • Open collector output.
51-52-03-07 Page 4 ALM RSP OUT % 1 2 1 2 1 2 F C MAN FUNCTION SET UP LOWER DISPLAY MANUAL AUTO SETPOINT SELECT RUN HOLD DI Indicator definition when lit ALM - Alarm conditions exist DI - Digital Input.
51-52-03-07 Page 5 Specifications Design CE Conformity (Europe) This product is in conformity with the protection requirements of the following European Council Directives: 73/23/EEC , the Low Voltage Directive, and 89/336/EEC , the EMC Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed.
51-52-03-07 Page 6 Specifications (continued) Design (continued) Controller Output Types Current Output (Isolated) Range can be set anywhere between 0 to 21 mA, and as direct or reverse action. Resolution: 11 bits for 0 to 21 mA Accuracy: 0.5% full scale Temperature Stability: 0.
51-52-03-07 Page 7 Specifications (continued) Design (continued) Auxiliary Linear Output (Optional) (Isolated) 21 mA dc maximum into a negative or positive grounded load or non-grounded load of 0 to 1000 ohms. Output range can be set anywhere between 0 to 21 mA, and as direct or reverse action.
51-52-03-07 Page 8 Specifications (continued) Environmental and Operating Conditions Parameter Reference Rated Operative Limits Transportation and storage Ambient Temperature 25 ± 3 ˚ C 77 ± 5 ˚ F.
51-52-03-07 Page 9 General Reference Data Data Isolation (Functional) AC Power : is electrically isolated from all other inputs and outputs to withstand a HIPOT potential of 1900Vdc for 2 seconds per Annex K of EN61010-1. Analog Inputs and Outputs: are isolated from each other and all other circuits at 850Vdc for 2 seconds.
51-52-03-07 Page 10 Dimensions Panel Cutout ALM RSP OUT % 1 2 1 2 F C MAN PV 1 2 3 4 96 3.780 AL M % 1 2 1 2 1 2 F C M A N DI ALM RSP OUT % 1 2 1 2 F C MAN DI FUNCTION LOWER DISPLAY MANUAL AUTO SETPOINT SELECT SET UP HOLD 1 2 24 .945 Max Panel Thickness 10 .
51-52-03-07 Page 11 Wiring Diagram 1 2 3 4 5 6 7 8 9 ALM 1 CTL 2 ALM 2 CTL 1 4-20 MA 10 11 12 13 14 15 16 17 DI 1 TX- or AUX- TX+ or AUX+ RX-/TX- RX+/TX+ SHIELD DI 2 UDC 3000 EXTERNAL WIRING L1/H L2/N.
51-52-03-07 Page 12 Ordering Information For the complete ordering information, request Model Selection Guide: 51-51-16-32 for UDC3000 Universal Digital Controller or . . Honeywell offers a full Iine of Sensors, Transmitters, and Final Control Devices for use with the UDC3000 Universal Digital Controller.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Honeywell DC300K-E è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Honeywell DC300K-E - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Honeywell DC300K-E imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Honeywell DC300K-E ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Honeywell DC300K-E, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Honeywell DC300K-E.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Honeywell DC300K-E. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Honeywell DC300K-E insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.