OUTDOOR SPLIT SYSTEM HEA T PUMP INST ALLA TION INSTR UCTIONS DO NO T DESTRO Y . PLEASE READ CAREFULL Y AND KEEP IN A SAFE PLA CE FOR FUTURE REFERENCE. IMPOR T ANT A TTENTION INST ALLERS: It is your responsibility to kno w this product better than y our customer .
2 W ARNING: ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage. Improper servicing could result in dangerous operation, serious injur y , death or property damage. • Before servicing, disconnect all electrical power to the indoor blo wer .
3 HEA T PUMP INST ALLA TION General Information Split system heat pumps are designed only f or outdoor rooftop or ground le v el installations. This unit has been tested f or capacity and efficiency in accordance with AHRI Standards and will provide man y years of saf e and dependable comf or t, providing it is properly installed and maintained.
4 Connecting RefrigerantT ubing Between the Indoor & Outdoor Unit CA UTION: When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accum ulation of moisture and other contaminants.
5 the line-v oltage leads to the ter minals on the contactor inside the control compar tment. • Use only copper wire for the line voltage power supply to this unit as listed in T able 1. Use proper code agency listed conduit and a conduit connector f or connecting the supply wires to the unit.
6 • Do not add additional oil to motors unequipped with oil tubes. The compressor is her metically sealed at the f actor y and does not require lubrication. ST ART UP & ADJUSTMENTS Pre-Start Check List √ V er ify the unit is le vel and has sufficient clearances f or unobstructed airflow .
7 ther mostat. NO TE: The blo wer should also stop unless f an s witch is set to the ON position. System Heating (Optional) 1. If heating equipment (fur nace, air handler) is pro vided with the system, lower the thermostat setpoint temperature to the lo west temperature setting and change the ther mostat’ s system mode to HEA T .
8 • A high-pressure s witch is f actor y installed and located inter nally on the compressor discharge line of the outdoor unit. If the discharge pressure rises above 650 psig, theswitchwillopenand de-energizetheoutdoorunit.
9 2 . Measure the liquid refrigerant temperature (in F ahrenheit) at the ser vice valv e. 3. Deter mine the required liquid refrigerant pressure . Ref er to T ables 3-9 (pages 11-13) and Figures 5-11 (pages 13-16).
10 Figure 4. Charging Chart for 3 T on Units Liquid T emperature (° F) Liquid Pressure (psig) 250 275 300 325 350 375 400 425 450 475 500 70 75 80 85 90 95 100 10 51 10 115 120 12 5 Remo ve refr igerant when abo ve cur ve Add refrigerant when below cur ve Figure 5.
11 Figure 6. Charging Chart for 5 T on Units Liquid T emperature (° F) Liquid Pressure (psig) 250 275 300 325 350 375 400 425 450 475 500 70 75 80 85 90 95 100 105 110 11 51 20 125 Remo ve refr igerant when abo ve cur ve Add refrigerant when below cur ve Figure 7.
12 HPS W2 OU T LP S Y OU T Y2 OU T Y2 W2 IN L COI L C Y O R AMB DF 1D F2 RV OUTDOOR FA N MO TO R T1 T2 L1 L2 RIGHT COMPRESSOR HPS LPS RV COIL C R S CCH BLACK YELLOW RED C H C TO THERMOST AT AMB SENSOR.
13 AMB HP S W2 OU T LP S Y OU T Y2 OU T Y2 W2 IN L COIL C Y O R DF1 DF2 RV BLACK RED OUTDOOR F AN MO TO R T1 T2 L1 L2 COMPRESSOR HPS LPS RV COIL CCH BLACK RED BLUE ORANGE H F C R S TO THERMOST AT AMB .
14 HPS W2 OU T LP S Y OUT Y2 OUT Y2 W2 IN L COIL C Y O R AMB DF 1D F2 RV OUTDOOR F AN MO TO R COMPRESSOR HPS LPS RV COIL CCH WHITE YELLOW H C TO THERMOST AT AMB SENSOR OD SENSOR BR OW N BLACK CONT AC .
15.
INST ALLA TION / PERFORMANCE CHECK LIST REFRIGERA TION SYSTEM W as unit given 24 hr w arm up per iod for cr ankcase heaters? YES NO Stage-1 Liquid Pressure (high side) ________________________ Stage-1.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Heat Controller R-410A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Heat Controller R-410A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Heat Controller R-410A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Heat Controller R-410A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Heat Controller R-410A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Heat Controller R-410A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Heat Controller R-410A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Heat Controller R-410A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.