Heat Controller , Inc. • 1900 Wellworth A ve. • Jackson, MI 49203 • (517)787-2100 • www .heatcontroller .com ENGINEERING DESIGN GUIDE Commercial Horizontal & V ertical Packaged W ater-Sour.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T able of Contents Unit Features ........................................................................................................................................ 2 Selection Procedure .
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide HB Series The HBH/V Series exceeds ASHRAE 90.1 efciencies, and uses R-410A zero ozone depletion refrigerant, making it an extremely environmentally-friendly option.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T o conver t Inch-Pound (English) to SI (Metric) Air Flow Correction T able 400 CFM per ton of cooling capacity is nominal rated airflow f.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. 7 May , 2009 Page 10 HEA T CONTROLLER OEM PRICE LIST HBH & HBV Model Structure HBH & HBV COMP ACT Horizontal & V ertical HFC-4.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data ARI/ASHRAE/ISO 13256-1 ASHRAE/ARI/ISO 13256-1. English (IP) Units ASHRAE/ARI/ISO 13256-1.
20 7.0 4.5 10.3 0 0 0 0 0 0 0 710 1 1.6 1.05 8.2 85.1 3.25 20 7.0 4.5 10.3 0 0 0 0 0 0 0 825 11.7 1.02 8.4 83.2 3.38 30 3.5 1.2 2.8 620 22.2 14.0 0.63 0.58 24.1 38.3 710 13.6 1.09 10.1 87.8 3.66 30 3.5 1.2 2.8 725 22.5 14.7 0.65 0.59 24.4 38.3 825 13.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance capacities shown in thousands of Btuh 220 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance capacities shown in thousands of Btuh 325 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 012 Performance capacities shown in thousands of Btuh 400 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 015 Performance capacities shown in thousands of Btuh 525 CFM Nominal (Rated) Airow Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 018 Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certied conditions are 80.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 024 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 030 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 036 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 042 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Performance Data HBH/V 048 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Performance Data HBH/V 060 Performance capacities shown in thousands of Btuh Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Air Flow Correction T able Air Flow Correction T able Cooling Corrections Ent Air WB º F T otal Clg Cap Sens Clg Cap Multipliers - Entering DB º F Power Heat of Rej 65 70 75 80 80.6 85 90 95 50 0.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Antifreeze Correction T able Antifreeze T ype Antifreeze % Cooling Heating WPD Corr . Fct. EWT 30°F EWT 90°F EWT 30°F T otal Cap Sens Cap Power Htg Cap Power W ater 0 1.000 1.000 1.000 1.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Blower Performance Data Standard Unit Airow in CFM with wet coil and clean air lter Model Fan Speed Rated Airow Min CFM Airow (cfm) at External Static Pressure (in. wg) 0.00 0.05 0.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Model Fan Speed Rated Airow Min CFM Airow (cfm) at External Static Pressure (in. wg) 0.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Physical Data HB Series 006 009 012 015 018 024 030 036 042 048 060 Compressor (1 Each) Rotary Scroll Factory Charge R410A (oz) 17 18.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide HB - Horizontal Dimensional Data Horizontal Model Overall Cabinet A Width B Length C Height 006 - 012 in cm 19.1 48.5 34.1 86.6 1 1.1 28.2 015 - 018 in cm 20.1 51.1 43.1 109.5 17.0 43.2 024 - 030 in cm 20.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. HB - Horizontal Dimensional Data F Right Return Straight Discharge Front L N O M Right Return Front Straight Discharge CSP Back Discharge Condensate 3 / 4" IPT 3.3" [83.8mm] 0.7" [17.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide HB - V ertical Upow Dimensional Data Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future eld service.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. HB - V ertical Upow Dimensional Data Access Panels T op View-Left Return U R S Isometric View Left Return Left View - Air Coil Opening T C Power Supply 3/4" [19.1 mm] HV Knockout Low V oltage 1/2" [12.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Corner Weights for HBH Series Units Model T otal Left-Front* Right-Front* Left-Back* Right-Back* HBH006 Lbs 103 37 24 23 19 kg 46.72 16.78 10.89 10.43 8.62 HBH009 Lbs 105 38 24 23 20 kg 47.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. Electrical Data - Standard Unit HB Model V oltage Code Rated V oltage V oltage Min/ Max Compressor Fan Motor FLA T otal Unit FLA Min Circuit Amp Max Fuse/ HACR QTY RLA LRA 006 1 208-230/60/1 197/254 1 3.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide Electrical Data High Static Blower HB Model V oltage Code Rated V oltage V oltage Min/ Max Compressor Fan Motor FLA T otal Unit FLA Min Circuit Amp Max Fuse/ HACR QTY RLA LRA 015 1 208-230/60/1 197/254 1 6.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T ypical Wiring Diagram Single Phase HB Units With CXM Controller 31.
Heat Contr oller , Inc. HBH/V SERIES Engineering Design Guide T ypical Wiring Diagram Three Phase 208/230V HB Units With CXM Controller 32.
Engineering Design Guide HBH/V SERIES Heat Contr oller , Inc. T ypical Wiring Diagram Three Phase 460/575V HB Units With CXM Controller 33.
04/2009 1 1/2010.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Heat Controller HBH/V è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Heat Controller HBH/V - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Heat Controller HBH/V imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Heat Controller HBH/V ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Heat Controller HBH/V, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Heat Controller HBH/V.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Heat Controller HBH/V. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Heat Controller HBH/V insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.