Manuale d’uso / di manutenzione del prodotto EKTC09-1G del fabbricante Heat Controller
Vai alla pagina of 28
Heat Controller • 1900 Wellworth A ve. • Jackson, MI 49203 • (517)787-2100 • www .heatcontroller .com Ser vice Manu al Packaged T erminal Air Conditioners & Heat Pumps 7,000-15,000 BTUH Co.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 1 EKT C 0 7 - 1 G UNIT NOMENCLA TURE EKTC —Cooling only with Electric Heat EKTH —Heat Pump with Electric Heat BTU/H 07 K 09K 12K 15K VOL T A.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 2 UNIT COMPONENTS.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 3 Model EKTC07-1G EKTH0 7-1G F unction Cooling Heating Cooling Heating Rated V oltage 230/208V 230/208V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 4 Model EKTC07-2G EKTH0 7-2G F unction Cooling Heating Cooling Heating Rated V oltage 265V 265V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 5 Model EKTC09-1G EKTH09-1G F unction Cooling Heating Cooling Heating Rated V oltage 230/208V 230/208V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 6 Model EKTC09-2G EKTH09-2G F unction Cooling Heating Cooling Heating Rated V oltage 265V 265V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 7 Model EKTC12-1G EKTH1 2-1G F unction Cooling Heating Cooling Heating Rated V oltage 230/208V 230/208V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 8 Model EKTC12-2G EKTH1 2-2G F unction Cooling Heating Cooling Heating Rated V oltage 265V 265V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 9 Model EKTC15-1G EKTH15-1G F unction Cooling Heating Cooling Heating Rated V oltage 230/208V 230/208V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 10 Model EKTC15-2G EKTH15-2G F unction Cooling Heating Cooling Heating Rated V oltage 265V 265V Rated F requency 60Hz 60Hz Indoor Side F an T ype-Piece Cross Flo w Fan - 1 Cross Flo w Fan - 1 Diameter-Length in.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 11 EXTENDED PERFORMANCE D A T A EXTENDED COOLING PERFORMANCE OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 12 EXTENDED PERFORMANCE D A T A CONTINUED EXTENDED HEATING PERFORMANCE OUTDOOR DRY BULB TEMP. (DEGREES F) 37 42 47 52 57 EKTH07 BTUh 5250 5540 6300 6899 7620 WATTS 509 518 540 549 580 AMPS 2.4 2.5 2.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 13 Controller F unctions and Operating Methods The relationship between Centigrade and F ahrenheit is: T centigrade=Tfahrenheit*1.8+3.2 A . T emperature P arameter n Indoor setting tem perature (Tpeset) n Indoor ambient tem perature (T amb) B.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 14 Controller F unction and Operating Method continued 7 . Open circuit and short circuit of temperature sensor If the t emperature sensor has an open circuit, it will send an err or signal. The error signal is display ed (see table below).
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 15 D. Special F unctions and Features The PT AC unit is designed t o be operated b y the unit’s main control panel, ho wev er , factory installed connections are included to allow the PT A C to operat e via remote thermostat or energy management in put (front desk contr ol).
Heat Controller SERVICE MANU AL Packaged T erminal A/C 16 SUGGESTIONS: 1. T o size transf ormer , use the f ollowing equation: Quantity of PT AC units x 12 v a=T ransformer Size (va) Example: 1 10 PT A C units x 12 va = 1320 vaT ransf ormer 2. Follo wing are American Wire Gauge recommended sizes: AW G WIRE SIZE NO.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 17 W all Thermostat Connections A standard lo w voltage wall thermostat can be w ed with the PT AC unit’s fact or y installed t erminal. Multiple PT ACs can e ven be connected t ogether on a single wall thermostat.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 18 T ypical Wiring Diagram.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 19 1 . TEMP CONTROL T emp Control is used t o maintain room t emperature. Compressor will cy cle on and of f t o keep r oom at the request ed lev el of comfort. COOLER— Low ers temperature. (Minimum t emperature setting is 6 1°F/1 6°C) W ARMER— Raises temperature.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 20 KEYP AD CONFIGURA TION Allows further conguration of system to desired application such as whe ther th unit displays in °F or °C, whether the displa y shows the set point or r oom air tem perature, and to set contr ols for sensor biasing.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 21 DIP SWITCHES Auxiliary dip switch controls are locat ed behind front panel, through an opening belo w the control panel. Dip switches are accessible without opening the control bo x. Unit must be pow ered OFF to effectiv ely change their status.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 22 F . Protectiv e Features 1 . F rost Protection Mode (heat pump): When the compressor is running under wired contr oller’s heating signal. If T outer tube ≤ 28°F (-2°C) is det ected f or 1 min - ute successiv ely , the compressor and outdoor fan will st op running.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 23 Electric Circuit Diagram Packaged T erminal Air Conditioner Packaged T erminal Air Conditioner 55 55 5 If the above electri c circuit diagram has changed, please refer to it provided on the body Electric Circuit Diagram This electrical diagram is subject to change.
Heat Controller SERVICE MANU AL Packaged T erminal A/C 24 POWER CONNECTION OPTIONS Appropriat e power cor d accessory kit is determined by the v oltage, and amperage of the branch circuit. The unit does not come with a power cord (or hard wire kit) . An accessory power cor d kit must be ordered t o connect the unit to the outlet.
P A CKAGED TERMINAL A/C SERVICE MANU AL Heat Controller 25 Prev entative maint enance is essential to pr oper unit operation, efciency and longevity . T o ensure equipment operat es properly , it must be properlymaintained. Equipment operation should be check ed and veried sev eral times during each year .
Heat Controller SERVICE MANU AL Packaged T erminal A/C 26 Window T ype Series Window T ype Series C OOL IN G H E A TIN G 11200/ 11600 10 000/ 10300 1180/ 1220 1 130/ 1160 1484 1669 6. 93 8. 19 F an T y pe- P iec e Diam et er -L engt h in. (m m ) φ7 .
9/2013 Design, specications, performance data and materials subject to change without notice. :HOOZRUWK $ YH-DFNVRQ0,3K.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Heat Controller EKTC09-1G è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Heat Controller EKTC09-1G - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Heat Controller EKTC09-1G imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Heat Controller EKTC09-1G ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Heat Controller EKTC09-1G, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Heat Controller EKTC09-1G.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Heat Controller EKTC09-1G. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Heat Controller EKTC09-1G insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.