Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 1 Models: BE-41C BE-41LPC BE-41IPIC BE-41IPILPC • DO NOT store or use gasoline or other fl am- mable vapors and liquids in the vicinity of this or any other appliance. • What to do if you smell gas - DO NOT try to light any appliance.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 2 Listing Label Information/Location Model Name: ___________________________________________ Date purchased/installed: ___.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 3 Safety Alert Key: • DANGER! Indicates a hazardous situation which, if not avoided will result in death or serious injury . • W ARNING! Indicates a hazardous situation which, if not avoided could result in death or serious injury .
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 4 Î = Contains updated information. 13 Finishing A. Mantel and Wall Projections . . . . . . . . . . . . . . . . . . . . . . . 51 B. Facing Material . . . . . . . . . . . . .
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 5 B. Limited Lifetime W arranty Î.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 6 B. Limited Lifetime W arranty (continued) Î.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 7 B. T empered Glass Speci fi cations Hearth & Home T echnologies appliances manufactured with tempered glass may be installed in hazardous loca- tions such as bathtub enclosures as de fi ned by the Con- sumer Product Safety Commission (CPSC).
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 8 H. Requirements for the Commonwealth of Massachusetts For all side wall horizontally vented gas fueled equipment install.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 9 Figure 2.1 General Operating Parts B. Y our Fireplace W ARNING! DO NOT operate fi replace before read- ing and understanding operating instructions. Failure to operate fi replace according to operating instructions could cause fi re or injury .
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 10 D. Clear Space W ARNING! DO NOT place combustible objects in front of the fi replace or block louvers. High temperatures may start a fi re. See Figure 2.2. Avoid placing candles and other heat-sensitive objects on mantel or hearth.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 1 1 I. Lighting Instructions (IPI) The IPI system may be operated with two D-cell batteries. When using batteries, unplug the transformer . T o prolong battery life, remove them when using the transformer .
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 12 J. Lighting Instructions (Standing Pilot) 1. Turn of f all electric power to the appliance if ser- vice is to be performed. 2. Open control access panel. 3. Move switch to “OFF” position.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 13 Initial Break-in Procedure • The fireplace should be run three to four hours continuously on high. • T urn the fi replace off and allow it to completely cool. • Remove fi xed glass assembly .
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 14 Glass Cleaning Frequency: Seasonally By: Homeowner T ools Needed : Protective gloves, glass cleaner , drop cloth and a stable work surface. CAUTION! Handle fi xed glass assembly with care.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 15 V enting Frequency: Seasonally By: Homeowner T ools needed: Protective gloves and safety glasses. • Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow , debris, etc.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 16 (Either cobrahead or SIT) Figure 3.1 IPI Pilot Flame Patterns Figure 3.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 17 A. T ypical Appliance System NOTICE: Illustrations and photos re fl ect typical installations and are for design purposes only . Illustrations/diagrams are not drawn to scale.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 18 B. Design and Installation Considerations Heat & Glo direct vent gas appliances are designed to operate with all combustion air siphoned from outside of the building and all exhaust gases expelled to the outside.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 19 5 5 F raming and Clearances A. Selecting Appliance Location When selecting a location for the appliance it is important to consider the required clearances to walls (see Figure 5.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 20 B. Constructing the Appliance Chase A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should be enclosed inside the chase.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 21 D. Mantel and W all Projections W ARNING! Risk of Fire! Comply with all minimum clear- ances as speci fi ed. Framing or fi nishing material closer than the minimums listed must be constructed entirely of noncom- bustible materials (i.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 22 A. V ent T ermination Minimum Clearances Roof Pitch H (Min.) Ft. Flat to 6/12...........................................................1.0* Over 6/12 to 7/12 ...........
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 23 O N P R Q V = VENT TERMINAL X = AIR SUPPL Y INLET = AREA WHERE TERMINAL IS NOT PERMITTED Figure 6.3 Minimum Clearances for T ermination A = 12 inches................. clearances above grade, ver anda, porch, deck or balcony B = 12 inches.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 24 A. Approved Pipe This appliance is approved for use with Hearth & Home T echnologies DVP or SLP venting systems. Refer to Sec- tion 16B for vent component information.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 25 INST ALLED HORIZONT ALL Y H 1 H 2 V 1 H 1 V 1 Figure 7.3 Figure 7.4 T op V ent - Horizontal T ermination T op V ent - H.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 26 Figure 7.5 T op V ent - Horizontal T ermination - (continued) Three Elbows H 2 H 1 V 2 V 1 V 1 Min. H 1 Max. V 2 Min. H 2 Max. Elbow only 2 ft. 610 mm 0 in. 0 mm 1 ft. 305 mm 6 in.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 27 EXHAUST SHIELD FLUE RESTRICTOR T op V ent - V ertical T ermination No Elbow Figure 7.6 Note: If installing a vertical vent/ termination off the top of the ap- pliance, the fl ue restrictor should be used.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 28 H 1 V 1 V 2 T op V ent - V ertical T ermination (continued) Figure 7.1 1 T wo Elbows Figure 7.10 4. Center the Flue Restrictor on vent and secure in place by using two self-tapping screws (see Figure 7.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 29 Figure 7.12 T op V ent - V ertical T ermination - (continued) Three Elbows INST ALLED HORIZONT ALL Y H 1 H 2 V 1 V 2 V 1 H 1 + H 2 V 2 V 1 + V 2 Minimum H 1 + H 2 Maximum Elbow only 1 ft.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 30 Rear V ent - Horizontal T ermination Figure 7.13 Figure 7.14 No Elbow One 45º Elbow H 1 H 1 H 1 = 16 in. (406 mm) Maximum Do not use a 45º elbow in corner installations.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 31 INSTALLED HORIZONTALLY H 3 H 1 H 2 V 1 Rear V ent - Horizontal T ermination - (continued) T wo Elbows Figure 7.15 Figure 7.16 Three Elbows H 1 H 2 V 1 H 1 Maximum V 1 Minimum H 2 H 1 + H 2 Maximum 1 ft.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 32 Rear V ent - V ertical T ermination One Elbow Figure 7.17 T wo Elbows Figure 7.18 H 1 V 1 INST ALLED HORIZONT ALL Y H 1 H 2 V 2 V 1 Minimum H 1 Maximum 6 in. 152 mm 2 ft.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 33 Rear V ent - V ertical T ermination - (continued) Three Elbows Figure 7.19 Three Elbows Figure 7.20 INST ALLED HORIZONT ALL Y H 3 H 1 H 2 V 1 V 2 V 1 H 2 H 1 H 1 H 2 H 3 V 1 Minimum H 1 + H 2 + H 3 Maximum *** 8 ft.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 34 A* B* 10 in. 12 in. C D 10 in. 12 in. A. Pipe Clearances to Combustibles W ARNING! Risk of Fire! Maintain air space clearance to vent.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 35 C. Install the Ceiling Firestop A ceiling fi restop MUST be used between fl oors and attics. • DVP pipe only - Frame an opening 10 in. by 10 in. (254 mm by 254 mm) whenever the vent penetrates a ceiling/ fl oor (see Figure 8.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 36 D. Install Attic Insulation Shield W ARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home T echnologies Inc. requires the use of an attic shield.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 37 CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp. NOTICE: Once appliance is set up for top or rear venting, it CANNOT be changed at a later time.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 38 B. Rear V ent CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and safety glasses during instal- lation. Sheet metal edges are sharp. NOTICE: Once appliance is set up for top or rear venting, it CANNOT be changed at a later time.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 39 Figure 9.12 Non-combustible Board C. Installing the Non-combustible Board The factory supplied non-combustible board spans the distance from the top of the fi replace to the center of the framing header .
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 40 1 0 10 Inst all ing V ent Pipe (D VP and SLP P ipe ) A. Assemble V ent Sections (DVP Pipe Only) Attach V ent to the Firebox Assembly Note: Th e end of the pipe sec tions with t he lanced ta bs will face toward the applianc e.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 41 B. Assemble V ent Sections (SLP Pipe Only) T o attach the fi rst vent component to the starting collars of the appliance: • Attach a DVP-2SL or DVP-SLP24 adapter to the starting collar of the appliance.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 42 120º Figure 10.8 Securing V ertical Pipe Sections 120º Figure 10.9 Securing Horizontal Pipe Sections E. Disassemble V ent Sections • Rotate either section (see Figure 10.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 43 F . Install Decorative Ceiling Components (SLP only) A decorative ceiling thimble can be installed on a fl at ceil- ing through which the vent passes. The decorative ceiling thimble is used to cover the fi restop.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 44 G. Install Metal Roof Flashing • See minimum vent heights for various pitched roofs (Figure 10.14) to determine the length of pipe to extend through the roof. • Slide the roof fl ashing over the pipe sections extending through the roof as shown in Figure 10.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 45 SCREWS CAULK STORM COLLAR (1 of 3) Figure 10.18 Figure 10.18 TERMINA TION CAP I.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 46 Figure 10.20 Venting through the wall INTERIOR HEA T SHIELD OR EXTENDED HEA T SHIELD W ALL SHIELD FIRESTOP HEA T SHIELD 1-1/2 IN.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 47 A. Fuel Conversion • Make sure the appliance is compatible with available gas types. • Conversions must be made by a qualified service technician using Hearth & Home T echnologies speci fi ed and approved parts.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 48 Figure 12.1 Ignitor Button C. Standing Pilot Ignition System Wiring • The standing pilot ignition system wiring does not require a 1 10 V AC supply to operate. See Figure 12.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 49 E. Electrical Service and Repair W ARNING! Risk of Shock! Label all wires prior to dis- connection when servicing controls. Wiring errors can cause improper and dangerous operation.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 50 G. W all Switch Installation for Fan (Optional) If the box is being wired to a wall mounted switch for use with a fan (See Figure 12.5): • The power supply for the appliance must be brought into a switch box.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 51 1 3 13 Fi nishing A. Mantel and W all Projections W ARNING! Risk of Fire! Comply with all minimum clear- ances as speci fi ed. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materials (i.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 52 C. Doors Only doors certi fi ed for use with this appliance model may be used.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 53 A. Remove Fixed Glass Assembly See Section 14.G. B. Remove the Shipping Materials Remove shipping materials from inside or underneath the fi rebox.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 54 F . Install the Log Assembly LOG ASSEMBL Y : LOGS-6000BE 1. Release four glass clips and set the glass assembly aside. NOTE: See Step 9 when replacing the log set in an existing fi replace.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 55 5. The grate is located in the lower cavity . Remove the screw holding the grate in place and discard the screw . 6. Position the grate into the cutout in the refractory .
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 56 Figure 14.2 Fixed Glass Assembly G. Fixed Glass Assembly W ARNING! Risk of Asphyxiation! Handle fi xed glass assembly with care. Inspect the gasket to ensure it is undamaged and inspect the glass for cracks, chips or scratches.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 57 A. Standing Pilot Ignition System 1 5 15 T roubleshooting With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 58 T roubleshooting (continued) Symptom Possible Cause Corrective Action 3. (Continued) C. V alve. T urn the valve knob to the ON position. Place the ON/ OFF switch in the ON position.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 59 B. IntelliFire Ignition System Symptom Possible Cause Corrective Action 1.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 60 IntelliFire Ignition System - (continued) Symptom Possible Cause Corrective Action 4.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 61 1 6 16 Reference Materials A. Appliance Dimension Diagram Dimensions are actual appliance dimensions. Use for reference only . For framing dimensions and clearances refer to Section 5.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 62 B. V ent Components Diagrams Figure 16.2 DVP vent components 10-1/2 in. (267 mm) 10-7/8 in. (276 mm) 45 ° 7-3/8 in. (187 mm) 11-3/8 in. (289 mm) 1-1/4 in. (32 mm) 9-1/4 in.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 63 DVP-HPC1 DVP-HPC2 DVP-TRAP1 DVP-TRAP2 DVP-TRAPK2 DVP-TRAPK1 DVP-TRAP Horizontal T ermination Cap 15-1/8 in. (384 mm) 12 in. (305 mm) 8 in. (203 mm) Max Effective Length Note: Heat shields MUST overlap by a minimum of 1-1/2 in.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 64 13-1/4 in. (367 mm) 24-5/8 in. (625 mm) 27-1/2 in. (127 mm) RF6M Roof Flashing Multi-pak 31 in. (787 mm) 24-5/8 in. (625 mm) 13-1/4 in. (367 mm) RF12M Roof Flashing Multi-pak BEK Trap Ca p Brick Extension 13-3/4 in.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 65 DVP-TB1 BasementVent Cap 12 in. (305 mm) 1-1/2 in. (38 mm) 7-3/8 in. (187 mm) 14 in. (356 mm) 17-3/4 in. (451 mm) 7-1/4 in. 12 in. 305 mm (184 mm) 5-1/4 in. (133 mm) 12-1/2 in.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 66 B. V ent Components Diagrams (continued) DVP-HRC-SS DVP-HRC-ZC-SS HORIZONT AL TERMINA TION CAP 13 in. (330 mm) 15 in. (381 mm) 8-1/8 in. (206 mm) 10-7/8 in. 276 mm 10-1/2 in.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 67 B. V ent Components Diagrams (continued) Figure 16.7 SLP Series V ent Components Effective Height/Length Pipe inches mm SLP4 4 102 SLP6 6 152 SLP12 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 - 6 51 - 152 SLP12A 2 - 12 51 - 305 8-3/4 in.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 68 B. V ent Components Diagrams (continued) Figure 16.8 SLP Series V ent Components SLP-SNKD Snorkel T ermination Cap SLP-.
Heat & Glo • BE-41C / LP , BE-41IPIC / LP • 2105-900 Rev . P • 6/09 73 Heat & Glo, a brand of Hearth & Home T echnologies Inc. 7571 215 th Street West, Lakeville, MN 55044 www .heatnglo.com D. Contact Information Please contact your Heat & Glo dealer with any questions or concerns.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Heat & Glo LifeStyle BE-41IPIC è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Heat & Glo LifeStyle BE-41IPIC - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Heat & Glo LifeStyle BE-41IPIC imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Heat & Glo LifeStyle BE-41IPIC ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Heat & Glo LifeStyle BE-41IPIC, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Heat & Glo LifeStyle BE-41IPIC.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Heat & Glo LifeStyle BE-41IPIC. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Heat & Glo LifeStyle BE-41IPIC insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.