® Power Distribu tion Unit (PDU ) AP7620 AP7621 AP7622 AP7626 User ’ s Man ual.
Thi s ma nual is a vai la ble in En gli sh on t he encl osed CD . ❖❖❖ Dieses Handbuch ist in De utsch auf der beiliege nden CD-ROM verfü gbar . ❖❖❖ Este manual está dispon ible en español en el CD-ROM adjunto . ❖❖❖ Ce manuel est disponi ble en français sur le CD-ROM ci-inclus.
PDU: User’s Manual Conte nts Product Descriptions an d Safety Information . . . . . 1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Configurati on .
.
PDU: User’s Manual 1 Pr oduct Descriptions a nd Safety Inform ation Featur es of single-branc h PDU models This manual ex plains ho w to inst all and use the fo llowing Rack-moun t PDUs: All the PDU.
2 PDU: User’s Manual Product Descriptio n s and Sa fety Inf ormat ion 120V PDU ! ! ! ! Rack-mount PDU ( AP76 20 ) " " " " Display interf ace # # # # NEMA 5-20R outlets ( 24) $ $ .
PDU: User’s Manual 3 Prod uct Des cripti ons an d Safety Infor mation 208V PDU ! ! ! ! Rack-mount PDU ( AP76 22 ) " " " " Display interf ace # # # # NEMA L6-2 0R outlets (6) $ $ .
4 PDU: User’s Manual Product Descriptio n s and Sa fety Inf ormat ion 230V PDU wi th IEC 32 0 C20 power cor d ! ! ! ! Rack-mount PDU ( AP7621 ) " " " " IEC C13 outlets (21) # # #.
PDU: User’s Manual 5 Prod uct Des cripti ons an d Safety Infor mation 230V PDU wi th NEMA L6-20 power cor d ! ! ! ! Rack-mount PDU ( AP7626 ) " " " " IEC C13 outlets (21) # # # #.
6 PDU: User’s Manual Installation Mounting options Y ou can install Rack-mount PDUs in one of two ways: using toolless mounting pegs or the m oun ting brackets . Y o u mount the Rack-mount P DUs in the rear of the enclosu re, in t he channel di rectly b ehind t he rear ver tical moun ting r ails.
PDU: User’s Manual 7 Installation T o olless mounting 1. Decide where to mount the PDU an d whether the power cord will be at the upper or lower end of the PDU.
8 PDU: User’s Manual Inst allat ion in the rear panel of the enclosure. 3. Pu sh the P D U do wnwa r d until it locks into pos i tion. ..
PDU: User’s Manual 9 Installation Bracket- mounting Y ou can ord er a rack-mount brack et kit from APC— AR81 16BLK. The brackets attach to the Rack-mo unt PDU in two di fferent direct ions, sho wn in the figu res in step 1. Consider the or ientation of the Rack- mount PDU in the enclosure before attaching the brackets.
10 PDU: User’s Manual Inst allat ion brackets alig n with the holes. T ighten to secure the Rack- mount PDU to the enclosu re. – Recessed Orientation – Raised Orientatio n.
PDU: User’s Manual 11 Operation Rack-moun t PDU display interfac e ! ! ! ! Control Button T o view the o rient at ion of the LED displa y , press an d hold the bu tton fo r 5 seco nds T o cha nge the ori enta tion, h old th e bu tton fo r an additi on al 5 seconds un til “ AA ” f la she s and t hen changes orientati on.
12 PDU: User’s Manual Config uration Using a seri al port connection 0 1. Connect an available serial port of your comp uter to the serial po rt on t he front panel o f the PDU , using the supplied serial cable. 2. Run a terminal emul atio n prog ram such as W indows ® Hype rT erm inal.
PDU: User’s Manual 13 Configuratio n Access to menus When you log in as User , you can view information but cannot configure settings or enter data. When you log in as Administrat or , you can view information, configure settings, and enter data. Any changes take effect immediately .
14 PDU: User’s Manual Conf igurati on Main me nu Status Information option Choosing th is option di sp lays the fo llo win g inform atio n about the PDU . • The cu rrent in amps • The stat us (whether i t is within the configur ed limit s for output current or has reached or exceeded tho se limits).
PDU: User’s Manual 15 Configuratio n Device Data option Choosing th is opt ion di sp lays the following inform atio n: Factory Data option Choosing th is option di sp lays the fo llo win g inform atio n about the PDU .
16 PDU: User’s Manual Conf igurati on System Management option Choosing th is option di sp lays the fo llo win g additional opti ons Menu Number Menu Nam e Definition Access 1 Restart RMPDU Res tart th e PD U, using the parameters that ar e cu rrent ly config ured.
PDU: User’s Manual 17 Down loading the Late st Firmwa r e Re vision How to downl oad firmw ar e to a Rack-moun t PDU 1. Go to www .apcc.com/tools/download/ , and check to see if there is a version of firmware for your type of Rack - mount PD U later than the v ersion you are currently usin g.
18 PDU: User’s Manual Specifications AP7620 Electrical S p ecifications Input 10 0–12 0 V ; 50–60 Hz ; 16 A Output 100– 120 V ; 50–60 Hz ; 16 A Physical Specific ations Dime nsions 1.75 × 3. 5 × 48 in 4.5 × 8.9 × 121.9 cm W eight 11 . 7 5 lb 5.
PDU: User’s Manual 19 Specifi cations AP7621 Electrical S p ecifications Input 200– 240 V ; 5 0–60 Hz ; 16 A Output 200–240 V ; 50–60 Hz; 10 A (IEC C1 3 outlets); 16 A (IEC C19 outlets) Physical Specific ations Dime nsions 1.7 5 × 3.5 × 48 in 4.
20 PDU: User’s Manual Specifica tions AP7622 Electrical S p ecifications Input 200–24 0 V ; 50–60 Hz ; 16 A Output 200– 240 V ; 50–6 0 Hz ; 16 A Physical Specific ations Dime nsions 1. 75 × 3.5 × 48 in 4.5 × 8. 9 × 121 .9 cm W eight 14.0 lb 6.
PDU: User’s Manual 21 Specifi cations AP7626 Electrical S p ecifications Input 200– 240 V ; 5 0–60 Hz ; 16 A Output 200–240 V ; 50–60 Hz; 10 A (IEC C1 3 outlets); 16 A (IEC C19 outlets) Physical Specific ations Dime nsions 1.7 5 × 3.5 × 48 in 4.
22 PDU: User’s Manual W arr anty and Serv ice Limited warranty APC warrants t he Power Dist ribution Unit to be free from defects in mat erials and workmans hip for a period of two years from the date of purchase. Its obligation under this warranty is limited to repai ri n g or replacing, at its o wn so le option , any such defective pro duct s .
PDU: User’s Manual 23 replacement. 4. Pack the unit carefully . The warranty do es not cover damage sust ained in transit. Enc lose a letter with your name, addres s, RMA number and d aytime phon e numb e r; a copy of the s ales receipt; and a che ck as payment, if applicable.
24 PDU: User’s Manual Life-Support Policy General poli cy American Power Conv ersion ( APC ) does not recommend the use of an y of its products in the follow ing situations : • In li fe-suppor t a.
.
.
Radio Fr equency Inter fer ence This equipment has been tested and fou nd to compl y with the limits for a Class A digit al device, pu rsu ant to part 15 of the FCC Ru les. These limi ts are desi gned to p rovide reas onable protecti on against harm ful inte rference when the equipmen t is operated in a commercial environment.
APC W orldwide Customer Support Cus tomer supp ort f or this or any othe r APC product is available at n o charge in any of the following ways: • V isit the APC W eb site t o fin d answers to frequ ently a sked questio ns ( FA Q s), to access docum ents in the APC Knowledge Base , and to s u bmit cust om e r supp ort requests.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il American Power Conversion AP7621 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del American Power Conversion AP7621 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso American Power Conversion AP7621 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul American Power Conversion AP7621 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il American Power Conversion AP7621, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del American Power Conversion AP7621.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il American Power Conversion AP7621. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo American Power Conversion AP7621 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.