Manuale d’uso / di manutenzione del prodotto 10-40kW del fabbricante American Power Conversion
Vai alla pagina of 31
APC Silcon 10-40kW 400V UPS User Guide Copyright ©2000 APC Denmark ApS Information in this document is subject to change without notice and does not represent a commitment on the part of the vendor.
2 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Thank You Thank you for chosing APC Silcon. Please read this User Guide thoroughly prior to installing the system as it provides important information on safe and efficient installation and use.
990-4043 User Guide APC Silcon 10-40kW 400V UPS 3 Contents: 1.0 Introduction 4 1.1 Display Unit 4 2.0 Stop/Start UPS and Operating the External Service Bypass Panel 5 2.1 Stop UPS (for stand-by) 5 2.2 Start UPS (from stand-by) 5 2.3 Stop UPS (for complete power down) 6 2.
4 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Introduction 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years. The system requires only a minimum of maintenance, but we recommend you follow the maintenance guidelines described in section 6.
Stop/Start UPS and Operating the External Service Bypass 990-4043 User Guide APC Silcon 10-40kW 400V UPS 5 2.0 Stop/Start UPS and Operating the External Service Bypass Panel Only qualified electricians should start up or shut down APC Silcon UPS systems and instructions in the Installation Guide should be followed.
6 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Stop/Start UPS and Operating the External Service Bypass 2.3 Stop UPS (for complete power down) 2.3.1 Switching off the UPS CAUTION! If the UPS system.
Stop/Start UPS and Operating the External Service Bypass 990-4043 User Guide APC Silcon 10-40kW 400V UPS 7 The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out. 2.4 Start UPS (from complete power down) 2.4.1 UPS start-up CAUTION! Recharge batteries out of service every 3 months to prevent damage.
8 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Stop/Start UPS and Operating the External Service Bypass System start-up now completed. WARNING! If “ Autostart ” is active the UPS will start aut.
Stop/Start UPS and Operating the External Service Bypass 990-4043 User Guide APC Silcon 10-40kW 400V UPS 9 2.5 Operating the External Service Bypass Switch (single systems) 2.5.1 Bypassing the Single System UPS APC Silcon UPS Mains Load Service Bypass Switch Action 1.
10 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Stop/Start UPS and Operating the External Service Bypass 2.5.2 Switching the Single System UPS from External Bypass into Normal UPS Operation CAUTION! Do not leave UPS out of service for more than 48 hours.
Stop/Start UPS and Operating the External Service Bypass 990-4043 User Guide APC Silcon 10-40kW 400V UPS 11 NOTICE! If battery has been disconnected, please refer to section 2.4.1 UPS start-up. Action 1. Set the input s witch (Q001) to position 1 2. W ait 5 sec.
12 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Stop/Start UPS and Operating the External Service Bypass 2.6 Operating the External Service Bypass Switch (parallel systems) 2.
Stop/Start UPS and Operating the External Service Bypass 990-4043 User Guide APC Silcon 10-40kW 400V UPS 13 Action Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass operation 1. Press on the ke yboard 2. Press or on the keyboard until 3.
14 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Stop/Start UPS and Operating the External Service Bypass 2.6.2 Switching the Parallel System from External Bypass into Normal UPS Operation NOTICE! If battery has been disconnected, please refer to section 2.
Stop/Start UPS and Operating the External Service Bypass 990-4043 User Guide APC Silcon 10-40kW 400V UPS 15 Action 1. Check that the output s witch (Q004) is set to position 0 2. Check that all output s witches (Q002) are set to position 1 3. Set input switches (Q001) to position 1 4.
16 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Stop/Start UPS and Operating the External Service Bypass 2.7 Isolating one UPS in a Parallel Configuration for Service/Maintenance 2.7.1 Isolating one UPS in a Parallel/Redundant System In a redundant system one UPS may be isolated for service/maintenance without affecting other parallel UPS(s).
Stop/Start UPS and Operating the External Service Bypass 990-4043 User Guide APC Silcon 10-40kW 400V UPS 17 NOTICE! With Q002 in position 0, the UPS can be operated and tested as a single system without affecting the other parallel UPS(s) if correct monitoring device has been installed.
18 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Operation 3.0 Operation The display unit will read parameters, alarms/messages and measured values. LED alarm incorporates audible alarm, indicating unusual operating situations. The keyboard is used to program and control parameters and to display alarm messages and measured values.
Operation 990-4043 User Guide APC Silcon 10-40kW 400V UPS 19 3.2 Display of Measured Values To read measurements, press one or two keys simultaneously as shown below. (Illustrated values are examples only). 3.3 Using the Remote Display The remote display is an inactive unit that is unable to influence the operation of the APC Silcon UPS.
20 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Operation 3.4 Economy Mode When the UPS is running in Economy Mode, the load will be supplied directly from mains and output voltages are UPS monitored. In the event of a mains disruption, the UPS will switch to battery mode without affecting the load.
Parameter Settings 990-4043 User Guide APC Silcon 10-40kW 400V UPS 21 4.0 Parameter Settings Below tables show operating parameters programmable from keyboard.
22 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Parameter Settings 4.1 Programming Keys 4.2 Switching to Bypass Operation Programming Example Scrolls up through list Scrolls down through list Store.
Parameter Settings 990-4043 User Guide APC Silcon 10-40kW 400V UPS 23 To return to normal operation Follow same procedure to program other parameters. Action 6.
24 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Alarms and Events 5.0 Alarms and Events Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise.
Alarms and Events 990-4043 User Guide APC Silcon 10-40kW 400V UPS 25 5.3 Possible Alarms Alarms Description Action 1. Peak current limiter active Peak current limiter activated and UPS switched to bypass operation. System overload Check for blown fuses in installation 2.
26 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Alarms and Events Alarms Description Action 23. Main inverter failure Temperature of main inverter, too high or inverter fuse blown Check fan, check for airflow obstructions, check for overload, check fuse 24.
Alarms and Events 990-4043 User Guide APC Silcon 10-40kW 400V UPS 27 5.4 Rectifying Alarm Messages Following actions may rectify alarm: • Check local mains supply.
28 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Maintenance & Testing 6.0 Maintenance & Testing UPS maintenance should be carried out by trained service engineers only. Service and maintenance contract is recommended. 6.1 Fan It is recommended to replace fans every 3 years.
Maintenance & Testing 990-4043 User Guide APC Silcon 10-40kW 400V UPS 29 If the UPS is to be taken out of operation for an extended period, disconnect the battery in order to prevent discharging. For details, refer to Installation Guide. Action 1.
30 User Guide APC Silcon 10-40kW 400V UPS 990-4043 Warranty 7.0 Warranty 7.1 APC Silcon UPS Limited Factory Warranty APC warrants that the unit, when properly installed and commissioned by APC or APC .
How to Contact APC 990-4043 User Guide APC Silcon 10-40kW 400V UPS 31 8.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Telephone: 401 789-5735 Fax: 401 789-3710 PowerFax™: 800 347-FAXX Pre-sales Technical Support 877-474-5266 (1-877-4Silcon) Post-sales Technical Support 877-287-7835 (1-877-2UPS-TEK) Web: www.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il American Power Conversion 10-40kW è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del American Power Conversion 10-40kW - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso American Power Conversion 10-40kW imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul American Power Conversion 10-40kW ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il American Power Conversion 10-40kW, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del American Power Conversion 10-40kW.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il American Power Conversion 10-40kW. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo American Power Conversion 10-40kW insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.