V ektor -CD Dir ect or Belt Drive The V ektor -CD fan is a side inlet centrifugal blower with a high plume dilution nozzle designed for laboratory exhaust systems.
Remove any accumulations of dirt, water , ice or snow and wipe dry before moving to indoor storage. T o avoid “sweating” of metal parts allow cold parts to reach r oom temperature. T o dry parts and packages use a portable electric heater to get rid of any moisture build up.
3 V ektor -CD Centrifugal Laboratory Exhaust ® REMOVING FROM ST ORAGE As fans are r emoved from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation.
4 V ektor -CD Centrifugal Laboratory Exhaust ® Curb Installations Greenheck supplies gasketing material for all multi- section curbs and/or plenums. Install gasketing prior to bolting split curbs and or plenums together .
5 V ektor -CD Centrifugal Laboratory Exhaust ® Riser Installation Check curb or structural supports for levelness. Both must be level to ensure pr oper drainage from plenum and fan(s). For side inlet fans, remove panel at end of plenum. This opening is the designed connection spot for user connected ductwork from building.
6 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum Installation The figures depicted illustrate thr ee common methods used to install V ektor -CD bypass plenums. Methods used to attach a V ektor unit are dependent on local codes, roof construction design and r oof construction materials.
7 V ektor -CD Centrifugal Laboratory Exhaust ® Fan Installation Fan Housing Installation If the windband is shipped attached to the fan housing or if the windband is secured to the fan housing prior to mounting to the plenum, the fan / windband assembly should be lifted by the lifting lugs located on the fan housing.
8 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum and Fan Drainage Piping and T rap Detail (by others) There ar e multiple locations for pipe connections, one on each plenum section, and another on each tubular fan housing located at the bottom of the scroll.
9 V ektor -CD Centrifugal Laboratory Exhaust ® Disconnect is mounted to fan housing. T ransformer is mounted to bypass air plenum near isolation damper actuator motor . For systems that ship un-assembled because of physical size, this connection at disconnect from transformer must be field installed.
10 V ektor -CD Centrifugal Laboratory Exhaust ® Unit Start-Up 1. Disconnect and lock-out all power switches to fan. 2. Check for bearing alignment and lubrication. 3. Check the V -belt drive for proper alignment and tension (belt drive). 4. Check rigid coupling for proper alignment and connect between motor shaft and fan shaft (direct drive).
11 V ektor -CD Centrifugal Laboratory Exhaust ® Serviceable Components Windband Bypass Air Plenum Bypass Damper Weatherhood Isolation Damper Nozzle Fan Assembly Roof Curb or Structural Support Fan Operation All fans should be run every thirty (30) days, or at least “bumped” every thirty days.
12 V ektor -CD Centrifugal Laboratory Exhaust ® Motors Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only . Removing dust and grease buildup on the motor housing assists proper motor cooling.
13 V ektor -CD Centrifugal Laboratory Exhaust ® Bearing Replacement Both drive bearings are accessible fr om the ground on all V ektor -CD fans. Whether direct or belt driven, the bearings, along with other serviceable drive components (belts, motors, sheaves) are accessible by removing the motor cover panel.
14 V ektor -CD Centrifugal Laboratory Exhaust ® Problem Cause Corrective Action Excessive noise Wheel rubbing inlet Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft. V -belt drive Tighten sheaves on motor/fan shaft. Adjust belt tension.
15 V ektor -CD Centrifugal Laboratory Exhaust ® Date __________________ Time _____________ AM/PM Notes:___________________________________________ _________________________________________________ __.
16 471555 • Model V ektor -CD IOM, Rev. 1, February 2008 Copyright 2008 © Greenheck Fan Corp. Greenheck warrants this equipment to be fr ee from defects in material and workmanship for a period of thr ee years from the pur chase date.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Greenheck Fan 47555 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Greenheck Fan 47555 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Greenheck Fan 47555 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Greenheck Fan 47555 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Greenheck Fan 47555, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Greenheck Fan 47555.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Greenheck Fan 47555. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Greenheck Fan 47555 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.