1 • Refer to Service Manual RS6100004 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information.
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
PRODUCT DESIGN 4 These GSH13 SEER heat pump models are shipped with a nitrogen holding charge only and are available in 3, 4 and 5 ton sizes for 208/230 volt 3 phase applications and for 4 and 5 tons in 460 volt 3 phase. These units are designed for free air discharge.
5 W D H PRODUCT DIMENSIONS M o d el D i men s i o n s - W x D x H GSH130363 A E/A F 29 x 29 x 38 ¼ GSH130483 A E 29 x 29 x 34 ¼ GSH130483 B* 29 x 29 x 34 ¼ GSH130603 A C 35½ x 35½ x 34¼ GSH13048.
6 GSH130[36-60]3* GSH130[48-60]4* HEA T PUMP SPECIFICA TIONS (1) Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. (2) Maximum Overcurrent Protection: Must use fuses or HACR-type Circuit Breakers of the same size as noted.
7 COOLING PERFORMANCE DA T A GSH130363AE EXPA NDED PERFORMA NCE DATA COOLI NG OPER A TION M O D EL: G SH1 3 0363A* / ARUF49- 00 *-1* / ARUF 36421A* Outdoo r Ambient Temp eratur e 65 75 85 95 105 115 Enter ing Indoor Wet Bulb Temper ature I D B * A i r f l o w 5 96 36 77 15 96 36 7 7 15 96 36 77 15 96 36 7 7 15 9 6 36 77 15 96 3 6 77 1 MBh 34.
8 COOLING PERFORMANCE DA T A GSH130363AE EX PAN DE D P ER FO R M ANC E D ATA C OOL ING OP ER AT IO N MOD EL: GSH 130 363 A* / A RU F 49 - 00* - 1* / AR UF 364 21A * O u t d o or Amb i ent T em p er at.
9 COOLING PERFORMANCE DA T A GSH130363AF EX P AND ED P E RFORM A NCE DA T A C OO L ING O P E R AT IO N MOD EL : GSH1 30 3 63A * / ARU F 4 9- 00* -1* / A RU F 3 64 21A * O ut doo r Am bient T e m pe ra.
10 COOLING PERFORMANCE DA T A GSH130363AF EX P AND ED P E RF ORMA NCE DA T A C OOL ING O P ER A T IO N MOD EL : GSH1 30 3 63A * / AR U F 4 9-00* -1* / A RU F 3 64 21A * O ut doo r Am bi ent T e m pe r.
11 COOLING PERFORMANCE DA T A GSH130483AE EX P AND ED PE RF ORM A NCE DA T A CO OLING OP E R A TION MOD EL: G S H1 304 83A * / AR U F 6 1 - 00* -1* / A R UF 4 86 01A * O utdoo r Am bi en t T e m pe r .
12 COOLING PERFORMANCE DA T A GSH130483AE EX P AND ED PE RFO RMA NCE DA T A CO OLING OP E RA T ION MOD EL: G S H1 304 83A * / AR U F 6 1-00* -1* / A RUF486 01A * O utdoo r Am bi en t T e m pera tur e .
13 COOLING PERFORMANCE DA T A GSH130603AC EX P AND E D PE RF ORMA NCE DA T A CO O LI N G O PE R A TI O N M OD EL : GSH1 306 03A * / AR U F 6 1-00* -1* / A R UF 4 86 0 1A * Out d o o r A mb i ent T e m.
14 COOLING PERFORMANCE DA T A GSH130603AC EX P A ND E D P E RF ORMA NCE DA T A CO O L I N G O PE RA TI O N M OD EL : GSH1 306 03A * / ARU F 6 1-00* -1* / A RUF 486 01A * Ou t d o o r A mbi en t T e m .
15 COOLING PERFORMANCE DA T A GSH130484AC EX P AND E D PE RF ORMA NCE DA T A CO O LI N G O PE R A TI O N M OD EL : GSH1 304 84A * / AR * f486 016B Out d o o r A mb i ent T e m p er a t u re 65 7 5 85 .
16 COOLING PERFORMANCE DA T A GSH130484AC E X P AND E D P E RF OR M A NCE DA T A C OOL ING OP E R ATI ON M OD EL : GSH1 304 84A * / AR* f486 016B O utdoo r Am bi e nt T e m pe ra t ur e 65 7 5 85 95 1.
17 COOLING PERFORMANCE DA T A GSH130484AD EX PA NDED PERFORM A NCE DA T A COOL I NG OP ER AT I ON MOD EL: GSH 130484A * / A R * F4860 16B * O utdoo r A mbient Temperature 65 75 85 95 105 115 Enter ing I ndoor W et Bulb Tem pe ratu re IDB A irfl ow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 M Bh 43.
18 COOLING PERFORMANCE DA T A GSH130484AD EX PA NDED PERF ORM A NCE DA T A COOL I NG OP ER A T I ON MOD EL : GSH 130484A * / A R * F48 6016B * O utdoor A m bient Tem perature 65 75 85 95 105 115 Enter ing Indo or W et Bulb Tem pera ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 9 6 36 77 1 M Bh 45.
19 COOLING PERFORMANCE DA T A GSH130604AC EX P AND E D PE RF ORMA NCE DA T A CO O LI N G O PE R A TI O N M OD EL : GSH1 306 04A * / AR * F 4 860 16 B * Out d o o r A mb i ent T e m p er a t u re 65 7 .
20 COOLING PERFORMANCE DA T A GSH130604AC E X P AND E D P E RF OR M A NCE DA T A C OOL ING OP E R ATI ON M OD EL : GSH1 306 04A * / AR* F 4 860 16B* O utdoo r Am bi e nt T e m pe ra t ur e 65 7 5 85 9.
21 COOLING PERFORMANCE DA T A GSH130483B* EXPA NDED PERFORM A NCE DA T A C OO L I NG OPERAT I ON MODE L: G SH 130483B* / A R*F486016B * O utdoor A m bient Te mper ature 65 75 85 95 105 115 Enteri ng Indoor W et Bulb Tem peratur e IDB Ai rflow 59 63 67 7 1 59 63 67 71 59 6 3 67 71 59 63 67 71 59 63 67 71 59 63 67 71 MBh 43.
22 COOLING PERFORMANCE DA T A GSH130483B* EXPA NDED PERFOR M A NCE DA T A C O O LIN G O PE R A TIO N MODE L: GSH13 0483B* / A R*F486016B * O utdoor A m bi ent Tem perat ure 65 75 85 95 105 115 Enter ing I ndoor W et Bulb Tem perature I D B * A i r f l o w 5 96 36 77 15 96 36 77 15 96 36 77 15 9 6 3 6 7 7 15 96 36 77 15 96 36 77 1 M Bh 45.
23 High pressure is measured at the suction service valve ( the larger valve). AMPS = Outdoor unit amps (com p.+fan) Low pressure is measured at the gauge port connection. KW = Total system power Calculations are based on nominal CFM and 70 °F indoor dry bulb.
24 HEA TING PERFORMANCE DA T A GSH130[48-60]4AC High pressure is measured at the suction service valve ( the larger valve). AMPS = Outdoor unit amps (com p.+fan) Low pressure is measured at the gauge port connection. KW = Total system power Calculations are based on nominal CFM and 70 °F indoor dry bulb.
WIRING DIAGRAMS 25 HI GH V OL T AG E! DISC ONNECT ALL POWER BEFORE SERVICI NG OR INS T A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE P RESENT .
WIRING DIAGRAMS 26 HI GH V OL T AG E! DISC ONNECT ALL POWER BEFORE SERVICI NG OR INS T A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAMAG E, PERSONAL INJURY OR DE A TH . Wiring is subject to change.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.