Manuale d’uso / di manutenzione del prodotto Goodman 90%-95% Gas Furnace Units del fabbricante Goodman Mfg
Vai alla pagina of 37
C US ® Cop yright ©2009-2010 Goodman Manufacturing Co mpany, L.P. RT6612021 Rev. 3 August 2010 This manual is to be used by qualified, professionally trained HV AC technicians only . Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person.
PRODUCT IDENTIFICA TION 2 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
3 PRODUCT IDENTIFICA TION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
4 PRODUCT DESIGN installation (1 or 2 pipes). The optional Combustion Air Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. 2. Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace.
5 PRODUCT DESIGN quired due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range. High altitude kits are purchased according to the installa- tion altitude and usage of either natural or propane gas.
COMPONENT IDENTIFICA TION 6 Counterflow /Horizontal Upflow/Horizontal 1 Two-Stage Gas Valve 2 Gas Line Entrance (Alternate) 3 Pressure Switch(es) 4 Gas Manifold 5 Combustion Air Intake Connection 6 Ho.
7 PRODUCT DIMENSIONS GMVC95/AMVC95___X* NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues.
PRODUCT DIMENSIONS 8 GCVC9/ACVC9_____X* NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues.
9 PRODUCT DESIGN LOW F IR E HIGH FI R E LOW F IR E HI G H FIR E LOW FIRE HIGH FI R E LOW FIRE HI G H FIRE G MV C 95 0453 BX* G MV C 95 0704 CX* A M VC 9504 53BX * A M VC 9507 04CX * -0 . 45 - 0 . 9 0 -0 . 5 0 -0 .9 5 -0 . 25 - 0 . 2 5 -0. 25 -0 . 2 5 G MV C 95 0905 CX* A M VC 9509 05CX * - 0.
10 PRODUCT DESIGN LO W FIRE HI G H FIRE LO W FIR E HIG H FI RE LO W FIRE HIGH F IRE LO W FIR E HIGH F I RE G M VC 9504 53B X * G M VC 9507 04C X * AMV C95 0453 BX* AMV C95 0704 CX* - 0.10 - 0.1 0 20 1973 08 - 0 .30 - 0.75 111 7711 3 - 0.1 0 - 0. 10 - 0 .
11 PRODUCT DESIGN Pa rt N u m b e r 20 16 290 3 201 62 904 2 01 629 05 20 16 290 7 201 62 908 0 130 F 001 05 Open Setting (° F) 16 0 1 50 14 5 15 5 1 7 0 130 G MV C950 453B X* A MV C 95 0 4 53 B X* -.
12 PRODUCT DESIGN P art N um b e r 10 1235 34 101 2 3535 10 1235 37 1 012 3536 101 235 33 0130 F 000 38 Ope n Se t ting ( ° F) 220 1 50 190 18 0 200 12 0 G MV C95 045 3BX * AMV C 950 453 B X* - -- 2 .
13 PRODUCT DESIGN Coil Matches: A large array of Amana® brand coils are available for use with the GCVC9 and ACVC9 furnaces, in either counterflow or horizontal applications & with GMVC95 and AMVC95 furnaces, in either upflow or horizontal applications.
14 PRODUCT DESIGN Thermost at s: ComfortNet™ CTK01A* Thermostat Kit Filters: Filters are required with this furnace and must be provided by the installer.
15 PRODUCT DESIGN Counterflow Filters "A" Min Return Air Optional Ac ce ss Door Return air filters may be installated at the at the counterflow top return. A field supplied center filter support must be provided by the installer in order to use the top return.
FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 17 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 19 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
FURNACE SPECIFICA TIONS 21 1. These furnaces are manufactured for natural gas operation. Optional Kits are available for conversion to propane gas operation. 2. For elevations above 2000 ft. the rating should be reduced by 4% for each 1000 ft. above sea level.
BLOWER PERFORMANCE SPECIFICA TIONS 22 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 23 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 24 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 25 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 26 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 27 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 28 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 29 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 30 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 31 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
BLOWER PERFORMANCE SPECIFICA TIONS 32 1. Units are shipped without filter(s). CFM in chart is without filter(s). 2. All furnaces shipped with heating speed set at "B" and cooling speed set at "D". Installer should adjust blower speed as needed.
PERFORMANCE 33 30 40 50 60 70 80 90 1 1 0 12 0 100 13 0 14 0 150 100 90 80 70 60 50 40 30 20 10 OU TPUT B TU/ HR x 1 000 BTU OUTPUT vs T EM PERA TURE RISE CHAR T TE M PE R AT U R E R ISE 600 CFM 700 900 100 0 1 100 1200 1400 1600 180 0 2000 2200 2400 CFM FORM ULA S BTU OUTPUT = C FM x 1.
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH. 34 WIRING DIAGRAMS Wiring is subject to change.
HI GH VO L T AGE! DISC ONNECT ALL POWE R BEFORE SERVICI NG OR INS T A LLING THIS UNIT . MUL TIPL E POW ER SOURCES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAG E, PERSONAL I NJURY OR DEA TH . 35 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH. 36 SCHEMA TICS BLOWER ASSEMBLY SCHEMATIC ACVC9/AMVC95/GCVC9/GMVC95_____X* MODEL FURNACES This schematic is for reference only.
HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . MUL TIPL E POW ER SOURCES M A Y BE P RESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAM AGE, PERSONAL INJURY OR DEA TH.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Goodman Mfg Goodman 90%-95% Gas Furnace Units è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Goodman Mfg Goodman 90%-95% Gas Furnace Units - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Goodman Mfg Goodman 90%-95% Gas Furnace Units imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Goodman Mfg Goodman 90%-95% Gas Furnace Units ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Goodman Mfg Goodman 90%-95% Gas Furnace Units, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Goodman Mfg Goodman 90%-95% Gas Furnace Units.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Goodman Mfg Goodman 90%-95% Gas Furnace Units. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Goodman Mfg Goodman 90%-95% Gas Furnace Units insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.