C US ® Copyright © 2006-2007, 2009 Goodman Manufacturing Company, L.P. This manual is to be used by qualified, professionally trained HV AC technicians only . Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person.
PRODUCT IDENTIFICA TION 2 Furnace Type S : Single Stage/Multi-Speed The model and manufacturing number are used for positive identification of component parts used in manufacturing. When engineering and manufacturing changes take place where interchangeability of components are affected, the manufactur- ing number will change.
PRODUCT IDENTIFICA TION 3 The model and manufacturing number are used for positive identification of component parts used in manufacturing. When engineering and manufacturing changes take place where interchangeability of components are affected, the manufactur- ing number will change.
4 PRODUCT DESIGN 2. Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace. 3. Conversion kits for high altitude natural or propane gas operation are available.
5 COMPONENT IDENTIFICA TION 1 Gas Valve 2 Gas Line Entrance (Alternate) 3 Combustion Air Intake Connection / “Coupling” 4 Hot Surface Igniter 5 Burners 6 Rollout Limit 7 Flame Sensor 8 Flue Pipe C.
COMPONENT IDENTIFICA TION 6 GKS9 NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues.
7 PRODUCT DESIGN * GKS9 furnaces are shipped without coil cover pressure switches. All GKS9 models are shipped from the factory as Dedicated Upflow but can be installed as a Horizontal Left or a Horizontal Right, ONLY after installing GKS9 Horizontal Installation Kit 0270K00012, which contains Pressure Switch 20197312.
8 PRODUCT DESIGN Part Numbe r 20162903 20162904 20162906 Open Setti ng (°F) 160 150 170 GKS90453B X* 1 GKS90703B X* 1 GKS90704C X* 1 GKS90904C X* 1 GKS90905D X* 1 GKS91155D X* 1 T.
9 PRODUCT DESIGN Coil Matches: Coil Matches (for Goodman ® unit s using R22 and R-410A): • All CAPF coils in B, C, & D widths have insulated blank off plates for use with one size smaller furnaces.
10 PRODUCT DESIGN Thermost ats: NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets. Filters: Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or CAN/ULCS111 standards.
FURNACE SPECIFICA TIONS 11 1. These furnaces are manufactured for natural gas operation. Optional kits are available for conversion to propane operation. 2. For elevations above 2000 feet the rating should be reduced by 4% for each 1000 feet above sea level.
BLOWER PERFORMANCE SPECIFICA TIONS 12 1. CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart assumes both filters are installed. 2. All furnaces ship as high speed cooling.
BLOWER PERFORMANCE SPECIFICA TIONS 13 30 40 50 60 70 80 90 11 0 12 0 100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTP UT BT U/HR x 1 000 BTU OUTPU T vs TEMPERAT URE RISE CHART T EM P ER AT U R E R I SE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT = CF M x 1 .
14 WIRING DIAGRAMS HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AILURE TO DO SO MA Y CAUS E PROPERTY DAMAG E, PERSONAL I NJUR Y OR DE A TH . Wiring is subject to change.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Goodman Mfg GKS9 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Goodman Mfg GKS9 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Goodman Mfg GKS9 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Goodman Mfg GKS9 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Goodman Mfg GKS9, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Goodman Mfg GKS9.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Goodman Mfg GKS9. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Goodman Mfg GKS9 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.