Manuale d’uso / di manutenzione del prodotto 1018959 del fabbricante GE
Vai alla pagina of 24
GE Digital Energy Power Quality Installation Guide Digital Energy™ SNMP / WEB ADAPTER P/N 1018959 3-ph SNMP/Web plug-in adapter P/N 1019070 1-ph SNMP/Web plug-in adapter P/N 23954 SP SNMP/Web plug-i.
Model: 3-ph SNMP/Web plug-in adapter 1-ph SNMP/Web plug-in adapter SP SNMP/Web plug-in adapter 1-ph SNMP/Web external adapter Date of issue: 13.05.2008 File name: ISG_CN T_SNM_BAS_CRD_V012 Revision: 1.2 Identification N o. P/N 1018959 P/N 1019070 P/N 23954 P/N 1019071 Up-dating Revision Concerns Date 1.
Dear Customer , We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE . We trust that the use of the SNMP/Web adapters for our Uninterruptible Power Supply systems, developed and produced to the highest standards of quality, will give you complete satisfaction.
Table of contents Page 1 SAFETY RULES ............................................................................................................................... .................. 5 1.1 WARNINGS AND CAUTIONS ......................................
1 SAFETY RULES With this document, GE gives to the user all the necessa ry inform ation about the correct insta llation of the SNMP/Web adapters. Please read carefu lly this Instal lation Manual before installing or operating the adapters. We recommend that this manual be kept next to the UPS for future references.
1.1 WARNINGS AND CAUTIONS GENERAL • Always strictly observe the “ UPS Sa fety Rules ” • Check carefully the integr ity of the equipment. In case you note some visible damage, do no t install the equipment but contact the nearest Se rvice Centre .
ENVIRONMENT • Please take care of packaging mate rial: either save it for later use or recy cle/dispose in compliance with local and other applicable regulations. • The SNMP/Web adapt ers contain a removab le, Lithiu m coin-c ell bat tery . Dispose of used batteries in compliance with local and other applicable regulations.
1.2 EMC COMPATIBILITY 1-ph SNMP/Web plug-in adapter (P/N 1019070) 1-ph SNMP/Web external adapter (P/N 1019071) This device has been tested for co mpliance with the following standards: • EN 61000-6-.
2 INTRODUCTION 2.1 CHECKING PACKAGE CONT ENTS The SNMP/Web adapters are delivered in d i fferent kits accord ing to the model. 3-ph SNMP/Web plug-in adapter (P/N 1018959) • 3-ph SNMP/Web plug-in ada.
• Third Party License ReadMe • CD-ROM AC ada p ter Serial cable 2.2 OVERVIEW 3-ph SNMP/Web plug-in adapter (P/N 1018959) LP 33 Series UPS SitePro / SG Serie s UPS Reset RS-232 UTP 10/100 Active LA.
• 1 – RJ45 Connector Ethernet connection, 10Base-T or 100B ase-TX • 2 – LEDs Ref. specific section • 3 – RS-232 port Local console connection (115200-N-8-1) • 4 – Reset b utton HW rese.
LEDs The various front panel LEDs have the following meaning: • LAN / Netlink Status Meaning Off No LAN connection detected LAN connection establishe d, no communication On LAN connection establishe.
2.5 ADDITIONAL DOCUMENTS The SNMP/Web adapter is provided with a CD-ROM containing the following documentation: • Installation Manual • Operating Manual • SNMP Management Information Base (MIB) • Release notes and other in structions, as applicable Modifications reserv ed Page 13/24 ISG_CNT_SNM_BAS_CRD_1GB_V012.
3 INSTALLATION NOTE ! Strictly observe the ‘ UPS Safety Rules ’. Read carefully the UPS ‘ Operating Manual & Installation Guide ’ before installing or operating th e equipment. If any problems are encounte red with the installation procedure here described, please contact the nearest Service Centre before proceeding.
Modifications reserv ed Page 15/24 ISG_CNT_SNM_BAS_CRD_1GB_V012.doc Installation Guide SNMP/Web Ada pter 3.1.2 Installing the SNMP Card in option slot IMPORTANT: Switch off the UPS, and wait approx. 2 minut es or switch the UPS to the manual bypass. In the latter case, please ensu re that the mains inpu t is reliable during this period.
Install procedure for SG Series SGT5000_050-080_UPS_GE_03 Q1 OFF ON Q2 ON OFF 1. Change the front plate with the smaller one delivered with the Kit. 2. Insert the SNMP adapter in the options slot. 3. Fix the front plate of the SNMP adapter to the connectivity box, using the screw include d in the SNMP/Web adapter kit.
• Make all necessary connections (see architecture diagram in section 2.4 ). Contact i /f • Switch on the UPS or go back to normal mode from bypass. 3.3 SP SNMP/WEB PLUG-IN AD APTER (P/N 1019070) • Switch off the UPS, and wait approx. 2 minutes or switch the UPS to the manual bypass.
• Connect the power to the box (left-most connector in the picture abov e). Make sure that the SNMP/WEB Interface box is powered b y the UPS output! • The UPS / Fail LED will switch OFF once th e connection to the UPS is established. If the LED remains continuously on, chec k the UPS connection and related cabling.
4 CONFIGURATION 4.1 CONFIGURATION METHODS The SNMP/Web plug-in adapters can be co nfigured using different interfaces. 4.1.1 Configuration via serial connection • Connect the SNMP adapter to a computer using a standard 1:1 serial co mmunication cable.
NOTE : Although the console interface provides a full set of comman ds, access using the serial connection is only needed for initial configuration when no DHCP server is available, or the IP-address is unknown. The quick network configuration menu pr ovides a simple interface for basic network configuration.
4.2 NETWORK PARAMETERS The SNMP/Web adapter connects to the ne twork using the foll owing parameters: • IP address identifies the adapter on the network. • Subnet mask defines a range of addresses within the organisation. • Gateway the node used for connection to addresses outside the subnet.
5 ACCESS 5.1 WEB INTERFACE After the installation and configuration of the SNMP/Web adapter, th e connection can be tested with a web browser. • Launch the browser • Enter the URL of the SNMP/Web adapter: http://< IP>/ (e.g. http://192.168.24 .
6 CUSTOMER SUPPORT 6.1 FIRST LINE SUPPORT Please contact your local GE distri butor for problems with the ins talla tion of t he product or its use. 6.2 INTERNET On-line support available on requ est (Internet acce ss required). 6.3 WWW SERVER We have a WWW server running at www.
7 APPENDIX A SitePro EARTH CONNECTION In order to guarantee correct func tional behaviour, the SNMP/Web plug-in adapter must be connected to protective earth (UPS chassis). On SiteP ro UPSs manufactured before 2003 the square plates (delivered with the 3-ph adapter kit) must be mounted – refer to the pictures below for the installation details.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il GE 1018959 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del GE 1018959 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso GE 1018959 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul GE 1018959 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il GE 1018959, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del GE 1018959.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il GE 1018959. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo GE 1018959 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.