Unifit Cool Svc Parts 2010 (05/10) Thru-the-Wall Series Thru-the-Wall Series Ser vice and P ar ts Man ual 115 Volts US08C10 US10C10 US12C10 Uni- Fit R Unifit.
—2— 1. PREF A CE 1.1 SAFETY PRECAUTIONS ...............................2 1.2 INSULATION RESISTANCE TEST.................2 1.3 SPECIFICATIONS ..........................................3 ~8 1.4 FEATURE S .............................................
—3— 1.3 SPECIFICA TIONS US08C10 POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
US10C10 1.3 SPECIFICA TIONS POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
—5— US10C30 POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
US12C10 POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
US12C30 POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
US14C30 POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (Btu/w.h) REFRIGERANT (R-410A) CHARGE OPERATING INDOOR (°F) TEMPERATURE OUTDOOR (°F) EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
— 9 — 1.4 FEA TURES • Designed for cooling only. • Powerful and quiet. • Slide out chassis for the simple installation and service. 1.5 CONTR OL LOCA TIONS 1.5.1 COOLING ONL Y MODEL • OPER A TION • Built in adjustable THERMOSTAT . • Washable one-touch filter .
— 10 — 2.1 MECHANICAL P AR TS 2.1.1 FRONT GRILLE 1. Open the inlet grille downward. 2. Remove the screw which fastens the front grille. 3. Pull the front grille from the right side. 4. Remove the front grille. (See Fig. 1) 5. Re-install the component by referring to the removal procedure.
Figure 7 — 11 — 2.2 AIR HANDLING P AR TS 2.2.1 ORIFICE, AND TURBO F AN 1. Remove the front grille. (Refer to section 2.1.1) 2. Remove the cabinet. (Refer to section 2.1.2) 3. Remove the 2 screws which fasten the evaporator at the left side and the right side.
— 12 — 2.2.3 SHROUD 1. Remove the fan. (Refer to section 2.2.2) 2. Remove the shroud. (See Fig. 9) 3. Re-install the components by referring to the removal procedures, above. 2.3 ELECTRICAL P AR TS 2.3.1 MO T OR 1. Remove the cabinet. (Refer to section 2.
— 13 — 2.3.4 PO WER CORD 1. Remove the control box. (Refer to section 2.1.3) 2. Unfold the control box. (Refer to section 2.3.3) 3. Disconnect the grounding screw from the Base pan. 4. Disconnect 2 receptacles. 5. Remove a screw which fastens the clip cord.
— 14 — 2.4 REFRIGERA TION CYCLE 2.4.1 CONDENSER 1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the brace. (Refer to section 2.2.1) 3. Remove the 7 screws which fasten the condenser. 4. After discharging the refrigerant completely into a Freon TM Recovery System, unbraze the interconnecting tube at the condenser connections.
— 15 — — Replacement of the refrigeration cycle. 1. When replacing refrigeration components, be sure to discharge the refrigerant system using a Freon TM recovery System. Install a valve for the recovery, before venting the Freon, remove the valve when finished.
— 16 — Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment, Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
— 17 — 3. TR OUBLESHOO TING GUIDE 3.1 OUTSIDE DIMENSIONS 20- 3 / 32 " (499mm) 24" (610mm) 14- 3 / 8 " (366mm) CONDENSER COILS EV APORA TOR COILS FA N M OTO R : REFRIGERANT FLOW TURBO F AN CAPILLAR Y TUBE COMPRESSOR 3.
— 18 — 3.3 TR OUBLESHOO TING GUIDE In general, possible trouble is classified in two causes. One is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and/or improper application.
— 19 — Fails to Start Check circuit break er and fuse. Check control board Only f an fails to start. Improper wiring. Def ect of fan motor capacitor .
Y D E M E R E S U A C T N I A L P M O C Check voltage at outlet. Correct if none. Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal. Test capacitor. Replace if not within ± 10% of manufacturer's rating.
—2 1 — M U M I X A M M U M I N I M G N I T A R E T A L P E M A N V 5 . 6 2 1 V 5 . 3 0 1 V 5 1 1 V 3 5 2 V 7 8 1 V 0 3 2 / 8 0 2 Y D E M E R E S U A C T N I A L P M O C Check voltage. See the limits on the preceding. page. If not within limits, call an electrician.
— 22 — COMPLAINT CAUSE REMEDY Check the voltage. See the limits on the preced- ing page. If not within limits, call an electrician. Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.
— 23 — 4. SCHEMA TIC DIA GRAM 4.1 CIRCUIT DIA GRAM (SMPS) MEZ62420710 250V/T2A (250V/T3.15A) WIRING DIAGRAM.
567502 550140 359012 352380 346811 149980 130410 435300 435301 147582-1 147581 135303 152302 147582-2 135312 349480 W48602 731273 C B 567480 W0CZZ 249950 238310 237200 A 264110 MO E D M I T R E W O P .
W 0CZZ CAPACITOR,FILM,BOX 67300709 130410 BASE ASS EMBLY,SINGLE 67302925 130900 CABINET 67303717 132100 FRAME 67308102 135303 GRILLE,INLET 67306106 135312 GRILLE ASSEMBLY ,FRONT(SINGLE) 673060 12 2383.
W 0CZZ CAPACITOR,FILM,BOX 67300724 130410 BASE ASS EMBLY,SINGLE 67305520 130900 CABINET 67303717 132100 FRAME 67308102 135303 GRILLE,INLET 67306106 135312 GRILLE ASSEMBLY ,FRONT(SINGLE) 67306012 23831.
W 0CZZ CAPACITOR,FILM,BOX 67300709 130410 BASE ASS EMBLY,SINGLE 67302925 130900 CABINET 67303717 132100 FRAME 67308102 135303 GRILLE,INLET 67306106 135312 GRILLE ASSEMBLY ,FRONT(SING LE) 67306012 2383.
—2 8 — W 0CZZ CAPACITOR,FILM,BOX 67300729 130410 BAS E ASSEMBLY ,SINGLE 67305520 130900 CABINET 67303717 132100 FRAME 67308102 135303 GRILLE,INLET 67306106 135312 GRILLE ASS EMBLY,FRONT(SINGLE) 67.
—2 9 — W 0CZZ CAPACITOR,FILM,BOX 67300726 130410 BASE A SSEMBLY ,SINGLE 67305520 130900 CABINET 67303717 132100 FRAME 67308102 135303 GRILLE,INLET 67 306106 135312 GRILLE ASSEMB LY,FRONT(SINGLE) 6.
— 30 — W 0CZZ CAPACITOR,FILM,BOX 67300709 130410 BASE ASS EMBLY,SINGLE 67302926 130900 CABINET 67303717 132100 FRAME 67308102 135303 GRILLE,INLET 67306106 135312 GRILLE ASSEMBLY ,FRONT(SINGLE) 673.
Unifit Cool Svc Parts 2010 (05/10) Printed in the U.S.A Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540 • (210) 357-4400 • FAX (210) 357-4480 FRIEDRICH AIR CONDITIONING CO. Visit our web site at www.friedrich.com P/NO.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Friedrich US10C30 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Friedrich US10C30 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Friedrich US10C30 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Friedrich US10C30 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Friedrich US10C30, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Friedrich US10C30.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Friedrich US10C30. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Friedrich US10C30 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.