UE08/UE10/UE12 (05/05) Thru-the-Wall Series Thru-the-Wall Series Ser vice and P ar ts Man ual 115 Volts UE08 230 Volts UE10 UE12.
—2— 1. PREF A CE 1.1 SAFETY PRECAUTIONS ...............................2 1.2 INSULATION RESISTANCE TEST.................2 1.3 SPECIFICATIONS ..........................................3 1.4 FEATURES .................................................
—3— 1.3 SPECIFICA TIONS 1.3.1 FOR UE08A13B/UE10A33B/UE12A33B REMARK POWER SUPPLY CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R. (Btu/W.h) CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) INDO.
1.4 FEA TURES • Designed for cooling only. • Powerful and quiet cooling. • Top-down chassis for the simple installation and service. 1.5 CONTR OL LOCA TIONS • Built in adjustable THERMISTOR and THERMOSTAT. • Washable one-touch filter. • Compact size.
—5— 2.1 MECHANICAL P AR TS 2.1.1 FRONT GRILLE 1. Open the inlet grille downward. 2. Remove the screw which fastens the front grille. 3. Pull the front grille from the right side. 4. Remove the front grille. (See Fig. 1) 5. Re-install the component by referring to the removal procedure.
Figure 7 —6— 2.2 AIR HANDLING P AR TS 2.2.1 ORIFICE, HEA TER ASSY AND TURBO F AN 1. Remove the front grille. (Refer to section 2.1.1) 2. Remove the cabinet. (Refer to section 2.1.2) 3. Remove the 2 screws which fasten the evaporator at the left side and the right side.
—7— 2.2.3 SHROUD 1. Remove the fan. (Refer to section 2.2.2) 2. Remove the screw which fastens the shroud. 3. Remove the shroud. (See Fig. 9) 4. Re-install the components by referring to the removal procedures, above. 2.3 ELECTRICAL P AR TS 2.3.1 MO T OR 1.
—8— 2.3.4 PO WER CORD 1. Remove the control box. (Refer to section 2.1.3) 2. Unfold the control box. (Refer to section 2.3.3) 3. Disconnect the grounding screw from the control box. 4. Disconnect 2 receptacles. 5. Remove a screw which fastens the clip cord.
—9— 2.4 REFRIGERA TION CYCLE 2.4.1 CONDENSER 1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the brace and the shroud cover. (Refer to section 2.
—10— — Replacement of the refrigeration components 1. When replacing the refrigeration components , be sure to discharge the refrigerant system using a FreonTM recovery System. Install a valve for the recovery before venting the Freon. Remove the valve when finished.
—11— Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
— 12 — 3. TR OUBLESHOO TING GUIDE 3.1 OUTSIDE DIMENSIONS 19- 21 / 32 " (499mm) 24- 21 / 32 " (626mm) 14- 13 / 32 " (366mm) CONDENSER COILS EV APORA TOR COILS FA N M OTO R : REFRIGERANT FLOW TURBO F AN CAPILLAR Y TUBE COMPRESSOR 3.
— 13 — 3.3 TR OUBLESHOO TING GUIDE In general, possible trouble is classified in two causes. The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
— 14 — Fails to Start Check circuit break er and fuse. Gas leakage at f eeler bulb of ther mostat Check control s witch. Only f an f ails to star t. Improper wiring. Def ect of f an motor capacitor . Irregular motor resistance ( ). Irregular motor insulation ( ).
— 15 — — 15 — COMPLAINT CAUSE REMEDY Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram for terminal identification.
— 16 — NAME PLATE RATING MINIMUM MAXIMUM 115V 103.5V 126.5V 208/230V 187V 253V COMPLAINT CAUSE REMEDY Check voltage. See the limits at the bottom of this page. If not within limits, call an electrician. Check the wire connections, if loose, repair or replace the terminal.
— 17 — COMPLAINT CAUSE REMEDY Check the voltage. See the limits on the preced- ing page. If not within limits, call an electrician. Check overload, if externally mounted. Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.
— 18 — 4. SCHEMA TIC DIA GRAM 4.1 CIRCUIT DIA GRAM • MODEL : UE08A13B/UE10A33B/UE12A33B 6411A20048F 6411A20048L 67300502 67303019 67303010 4681A20041M 67300714 67300711 67300404 67301625 6730162.
— 19 — 5. EXPLODED VIEW • MODEL: UE08A13B/UE10A33B/UE12A33B 354210 753010 753011 349480 554031 W48602 559010 346811 349600 567502 349001 130410 352113 35211A 352115 W48602 249950 137215 149410 W.
6. REPLA CEMENT P AR TS LIST • MODEL: UE 08A13B R: Service Parts N: Non Service parts LOCATION NO. MODEL FRIEDRICH # DESCRIPTION 130410 UE08A13B 67302917 BASE ASSEMBLY,SINGLE 1 R 130900 UE08A13B 673.
— 21 — • MODEL: UE10A33B R: Service Parts N: Non Service parts LOCATION NO. MODEL FRIEDRICH # DESCRIPTION 130410 UE10A33B BASE ASSEMBLY,SINGLE 1 R 130900 UE10A33B 67303705 CABINET 1 R 135312 UE1.
— 22 — • MODEL: UE12A33B R: Service Parts N: Non Service parts LOCATION NO. MODEL FRIEDRICH # DESCRIPTION 130410 UE12A33B 67302918 BASE ASSEMBLY,SINGLE 1 R 130900 UE12A33B 67303705 CABINET 1 R 1.
UE08/UE10/UE12 (05/05) Printed in the U.S.A Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540 • (210) 357-4400 • FAX (210) 357-4480 FRIEDRICH AIR CONDITIONING CO.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Friedrich UE08, UE10, UE12 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Friedrich UE08, UE10, UE12 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Friedrich UE08, UE10, UE12 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Friedrich UE08, UE10, UE12 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Friedrich UE08, UE10, UE12, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Friedrich UE08, UE10, UE12.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Friedrich UE08, UE10, UE12. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Friedrich UE08, UE10, UE12 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.