Manuale d’uso / di manutenzione del prodotto SH15L30-A del fabbricante Friedrich
Vai alla pagina of 20
SH15L30-A SH20L30-A SH20L50-A HG-SVC-PRTS-05 (4-05) Ser vic e & P ar ts Manual R oom Air Conditioners 50 & 60 Hz M ode ls 20 05.
2 TA B L E O F C O N T E N T S Specifi cations ............................................................................................................... .................... 3 Performance Data ...................................................
3 EV APORA TOR AIR TEMP . DEG. F EV APORA TOR TEMP . DEG. F CONDENSER TEMP . DEG. F Discharge Te m p Suction Te m p Liquid Te m p Super Heat Sub- Cooling OPERA TING PRESSURES ELECTRICAL RA TINGS R-22 REF . Evap CFM Motor RPM BREAKER FUSE Discharge Air Te m p .
4 COMPRESSOR WINDING TEST (Figure 2.) Remov e the co mpressor ter minal box cover and disconnect the wires from the ter minals. Using an ohmmet er , check c ontinuity across the following: COMPONENT OPERA TION AND TESTING COMPRESSORS Com pr ess ors ar e s ing le p has e , 2 08 /230 v ol t.
5 F AN MOTOR (Figure 4) A 230 volt single phase permanent spl it capacitor motor is used to dr ive the evaporator blower and c ondens er fan. A running capacitor is wired a cross the star t and run terminals of the motor . The motor is t otally enclosed and is prot ected with a line voltage ov erload loc ated int ernally of the motor .
6 RED DOT RUN CAP ACITOR FA N MOTOR COMPRESSOR FIGURE 7 RUN CAP ACITOR HOOK–UP CAP ACITOR, RUN A run capacitor is wired across the auxiliar y and main winding of a single ph ase permanent split capacitor motor s uch as the compressor and fan motors.
7 Note: The t emperature mu st be within the range li sted to check the th ermostat. Ref er to the trou bleshooti ng section in this manual for additional in formation on ther most at te sting. TEST Remo ve the wires from the th ermostat. T urn the thermostat to its coldest position.
8 LOW AMBIENT BYP ASS V AL VE (Figure 9) T h e H a z a r d G a r d u n i t i s d e s i g n e d t o o p e r a t e a t l o w outside ambient temperatures.
9 NOTE: This procedur e can be sped up by the use of heat lam ps, or by brea king the vacuum with refrigerant or dr y nitrogen at 5,00 0 microns. Pressure s ystem to 5 PSIG an d leav e in the sys- tem a minimum o f 1 0 minutes. R ecover refriger - ant, an d proceed with evacu ation to a pressu re of 200 mic rons or a minimum of 1 0 % .
10 NOTE: All inoperative compressors returned to Friedrich must have all lines properly plugged with the plugs from the replacement compressor . REFRIGERANT CHARGE 1 . The refrigerant charge is e xtremely c ritic al. Measure the charge carefully an d as e xactly as possible t o the namepl ate ch arge.
11 TROUBLESHOOTING PROBLEM POSSIBLE CAUSE TO CORRECT UNI T DOES N OT RUN. Power disconnected. Check power sourc e. System switch in “O f f ” position. Se t switch co rrec tly . Branch c ircuit fuse blown or circuit breaker tripped. Replace fuse, reset break er .
12 TROUBLESHOOTING (Co ntinu ed ) PROBLEM POSSIBLE CAUSE T O CORRECT COM PRESSO R AT T E M P T S T O ST ART , O R RUNS FO R S H O R T PERIOD S ONL Y . C Y CLES ON OV ER LOA D. Compress or attempts to st ar t before system pressures are equal ized . Allow a minimum of t wo ( 2) minutes to allow pressures to equalize before attempting to st ar t.
13 TROUBLESHOOTING (Co ntinu ed ) PROBLEM POSSIBLE CAUSE T O CORRECT FA N M O T O R D O E S NOT R UN. Defective switch (O n- Of f ) . Check c ontinuit y across ter minals 2 and 3. Fan c a p a c i t o r o p e n . Check by substituting a known good c apac itor of the same rating .
14 WIRING D IA GR AM MODELS SH 1 5L3 0 - A , SH20 L30 - A , SH20L5 0 - A.
15 HAZARDGARD CABINET P ARTS.
16 HAZARDGARD CHASSIS P ARTS.
17 HAZARDGARD P ARTS LIST REF DESCRIPTION P ART NO# MODELS CODE ELECTRICAL P ARTS SH15L30-A SH20L30-A SH20L50-A 1 COMPRESSOR 61 193549 1 600 1 COMPRESSOR 61 193550 1 600 1 COMPRESSOR 61 193565 1 600 2.
18 REF DESCRIPTION P ART NO# MODELS CODE CHASSIS P ARTS SH15L30-A SH20L30-A SH20L50-A 26 SHROUD, CONDENSER 61803601 17 2 0 26 SHROUD, CONDENSER 61804901 11 7 2 0 27 BRACE, COND.SHROUD 61802600 33 3 7 2 2 22 F AN BLADE, COND. 60542003 17 1 0 22 F AN BLADE, COND.
19.
HG-SVC-PRTS-05 (4-05) Use Factory Certifi ed Parts. FRIEDRICH AIR CONDITIONING CO. P ost Office Box 1540 · San Antonio, T exas 78295-1540 4200 N. P an Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · F AX (210) 357-4480 www .friedrich.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Friedrich SH15L30-A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Friedrich SH15L30-A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Friedrich SH15L30-A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Friedrich SH15L30-A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Friedrich SH15L30-A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Friedrich SH15L30-A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Friedrich SH15L30-A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Friedrich SH15L30-A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.