Ser vi ce & P ar ts Manu al 200 7 Compact Programmable Models CP14N10 CP18N30 CP24N30 CP-14-18-24-Svc-Prts-07 (3-07).
2 T ab le o f Co n t en ts Per formanc e Data .............................................................................................................. .......................................................... 3 Outer Comp onent Identi fi cation .
3 Model CP14N10 CP18N30 CP24N30 Function COOLING COOLING COOLING Rated V oltage 1 15V ~ 230/208V~ 230/208V~ Rated Frequency 60Hz 60Hz 60Hz T otal Capacity (Btu/h) 14000 18000/17600 23500/23100 Power Input (W) 1430 1850/1810 2740/2710 Rated Input (W) 1540 2478 3538 Rated Current (A) 15 12.
4 Out er Compo ne nt Ide n ti fi ca ti on Models : CP1 4N 1 0 , CP 1 8N3 0, CP2 4N30 Cabinet Air inlet louver F ront grille Pow e r co r d Control panel co ver F ront intake grille Air filter (behind.
5 Installat ion D imensions Models : CP1 4N 1 0 , CP 1 8N30, CP24 N30 (Top View) Fence / obstruction Over 2' Over 1' Over 1' Wall Or window (Front View) (Side View) Ceiling Over 1' Over 1' 25.
6 CP24N30 CP18N30 / CP14N10 Wirin g Dia gram s.
7 F unct ional C omponent De fi niti ons MEC HANIC AL C OMPONEN TS Ve nt d o o r A l l o w s i n t r o d u c t i o n o f f r esh air into the ro om and/or exhausts stale r oom air outsi de ( on select mo dels. ) Plenum assembly D i f f u s e r w i t h d i r e c t i o n a l l o u v e r s u s e d t o d i r e c t the c onditione d air fl ow .
8 In the c ase of the c apillar y tube thi s is acc omplished (by design ) throug h size ( and length ) of device, and th e pressure di f ference present ac ross t he device.
9 EQUIP MENT RE QUIRED 1. Vo l t m e t e r 2. Ammeter 3. Ohmmeter 4. E.P . A . A pproved Ref riger ant Rec overy S ystem. 5. V acuum Pump (capable of 20 0 mic rons or le ss vacuum. ) 6. Acetylene Welder 7 . Elec troni c Halo gen Leak Detec tor (G.E . T yp e H - 6 or equivalen t.
10 NOTE : I n o r d e r t o a c c e s s t h e s e a l e d sy s t e m i t w i l l b e n e c e s s a r y t o i n s t a l l S c h r a d e r t y p e fi t tings to the proce ss tubes on the discharge and suct ion of the c ompress or . Proper refr igerant recovery proc edures need to be adhered t o as outlined in EP A R egulations.
11 A n u n d e r c h a r g e d s y s t e m w i l l r e s u l t i n p o o r p e r f o r m a n c e ( l o w pres sures, etc. ) in both the heatin g and co oling cycl e. Whenever you ser vice a unit wit h an under charge of refrigera nt, always suspect a le ak.
12 RESTRICTED REFRIGERANT SYSTEM A quick c he c k for either c ondit ion begins at t he evaporator . W ith a par tial re stric tion, t here may be gurgling soun ds at the meterin g device entr ance to the evapor ator .
13 Problem Possible Cause Action Compressor does not run Low voltage Check voltage at compressor . 1 15V & 230V units will operate at 10% voltage variance T -stat not set cold enough or inoperative Set t-stat to coldest position. T est t-stat & replace if inoperative Compressor hums but cuts off on B10 overload Hard start compressor .
14 Problem Possible Cause Action Unit does not run Fuse blown or circuit tripped Replace fuse, reset breaker . If repeats, check fuse or breaker size. Check for shorts in unit wiring & components .
15 Problem Possible Cause Action Compressor runs for short periods only . Cycles on overload Overload inoperative. Opens too soon Check operation of unit.
16 Problem Possible Cause Action W ater "spitting" into room Sublimation: When unconditioned saturated, outside air mixes with conditioned air , condensation forms on the cooler surfaces Ensure that foam gaskets are installed in between window panes & in between the unit & the sleeve.
17 Problem Possible Cause Action Room temperature uneven (Heating cycle) Heat anticipator (resistor) shorted (on applicable models) Disconnect power to unit. Remove resistor from t- stat bulb block. Plus in unit & allow to operate. Feel resistor for heat.
18 Problem Possible Cause Action Unit cools when heat is called for Incorrect wiring Refer to applicable wiring diagram Defective solenoid coil Check for continuity of coil Reversing valve fails to shift Block condenser coil & switch unit to cooling.
19 Com pon en ts Model CP 1 4N 1 0.
20 No Description Qty Friedrich Part# Code 1 Supporter Assy 1 67700200 2 Screw ST4.2X13 7 67700154 3 Window locking bracket 2 677001 13 4 Screw 4X20 6 67700151 5 Seal strip 1 1 67700128 6 Seal strip 2 1 67700129 7 Curtain Assemby Left and Right 1 67700201 8 Right Curtain 1 67700202 9 Left Curtain 1 67700203 10 Cabinet Assy 1 67700204 1 1 Screw ST4.
21 No Description Qty Friedrich Part# Code 37 Clapboard of Snail Shell 1 67700108 38 Base Plate of Air Flue 1 67700106 39 Evaporator Assy 1 67700103 40 Sensor Holder 1 67700213 41 Compressor 44B124HXC.
22 No Description Qty Friedrich Part# Code 1 Supporter Assy 1 67700132 2 Self-threading Screw ST4.2x22 7 67700154 3 Window Locking Bracket 2 677001 13 4 Screw 4X20 6 67700151 5 Seal Strip 1 1 67700128.
23 No Description Qty Friedrich Part# Code 36 Blower Wheel 1 677001 16 37 Front Clapboard of Snail Shell 1 67700108 38 Base Plate of Air Flue 1 67700106 39 Evaporator Assy 1 67700103 40 Insert Block 2.
24 Com pon en ts Model CP2 4N30.
25 No Description Qty Friedrich Part# Code 1 Supporter Assy 1 67700200 2 Screw ST4.2X13 7 67700154 3 Window locking bracket 2 677001 13 4 Screw 4X20 6 67700151 5 Seal strip 1 1 67700128 6 Seal strip 2 1 67700129 7 L T & R T Curtain Assembly 1 67700201 8 Right Curtain 1 67700202 9 Left Curtain 1 67700203 10 Cabinet Assy 1 67700238 1 1 Screw ST4.
26 No Description Qty Friedrich Part# Code 38 Base Plate of Air Flue 1 67700106 39 Evaporator Assy 1 67700103 40 Sensor Holder 1 67700213 41 Compressor 44B124HXCEF 1 67700244 42 Overload Protector 1 6.
Friedrich Air Conditioning Company P.O. Box 1540 San Antonio, TX 78295 210.357.4400 www.friedrich.com ROOM AIR CONDITIONERS LIMITED WARRANTY FIRST YEAR A NY PART: If any part supplied by FRIEDRICH fai.
CP-14-18-24-Svc-Prts-07 (3-07) F r iedrich Air Condition ing Co. Post Of f ice Box 15 4 0 • San Ant onio , T exa s 782 9 5 - 15 4 0 420 0 N. Pan A m Expr es sw ay • San Anto ni o, T exa s 7821 8 -5212 (210) 357 - 4 4 0 0 • F A X (210) 357 - 4 4 8 0 w w w.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Friedrich CP14N10 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Friedrich CP14N10 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Friedrich CP14N10 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Friedrich CP14N10 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Friedrich CP14N10, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Friedrich CP14N10.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Friedrich CP14N10. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Friedrich CP14N10 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.