www.Fisher.com D100305X012 Type 6 55 a nd 6 55R A ctuators for S elf-Operated C ontrol Contents Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Scope of Manual 1 . . . . . . . . . . . . . . . . . . . . . . . . . Description 1 .
655 and 655R Actuators Instruction Manual Form 1292 July 2007 2 Table 1. Specifications Actuator Sizes and Maximum Casing Pressures ACTUATOR MAXIMUM CASING PRESSURE ACTUATOR SIZE Bar Psig 3A, 4A 17.2 250 3B, 4B 12.1 175 32, 42 6.9 100 33, 43 4.5 65 34, 44 3.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 3 CAUTION To avoid premature wear of the diaphragm due to debris in the pressure line to the diaphragm, install a strainer in the pipeline ahead of the regulator or relief valve. Before installing the actuator, inspect it for any damage.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 4 T able 2. Actuator Pressure-Setting Ranges (1) ACTUA- TOR SPRING PART PRESSURE REDUCTION PRESSURE RELIEF ACTUA- TOR SPRING PART PRESSURE.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 5 T able 3. Effective Diaphragm Area (1) ACTUA- TRAVEL DOWN FROM UPPER CASING STOP, mm (IN.) ACTUA - TOR 0 3 (0.125) 5 (0.1875) 6 (0.25) 10 (0.375) 11 (0.4375) 13 (0.5) 14 (0.5625) 19 (0.75) 22 (0.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 6 f. Stroke the actuator, and measure the stem movement to check travel. If the movement is more than full travel, turn the valve stem out of the actuator stem the amount of over-travel.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 7 4. Slowly open the upstream shutoff valve. Startup For Pressure-Relief Service 1. Open the needle valve in the control line. 2. Open the downstream shutoff valve. 3. Slowly open the upstream shutoff valve.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 8 pressurized, even when the valve has been removed from the pipeline. Process fluids may spray out under pressure when removing the packing hardware or packing rings, or when loosening the packing box pipe plug.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 9 diaphragm casing (key 5). Some Type 655R actuators will have travel stops (key 13, not shown) in place of three of these six cap screws. 9. If a top-mounted handwheel assembly is used, refer to steps 4 through 8 of the Disassembly portion of the Top-Mounted Handwheel section.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 10 16. To start up and adjust the actuator, follow the procedures outlined in the Startup section of this instruction manual.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 11 tightened to the proper load to prevent leakage, but not crush the material. Perform the following tightening sequence with a manual torque wrench. CAUTION Over-tightening the diaphragm cap screws (key 19) can damage the diaphragm.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 12 Parts Ordering When corresponding with your Emerson Process Management sales office about this equipment, refer to the serial number found on the actuator nameplate (key 17, figure 4).
655 and 655R Actuators Instruction Manual Form 1292 July 2007 13 Figure 4. Type 655 Actuator 30A8341-A/DOC 30A8342-A/DOC SIZE 3A AND 4A ACTUA TOR DIAPHRAGM CASINGS A APPL Y MOL Y-GREASE LUBRICANT TO A.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 14 Figure 6. Size 3B and 4B Top-Mounted Handwheel Assembly 38A1217-B/DOC APPL Y LUB P ARTS NOT SHOWN : 30 & 31 Key 6 Spring, steel COLOR CODE SPRING RATE SAFE LOAD COLOR CODE N/mm Lb/in.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 15.
655 and 655R Actuators Instruction Manual Form 1292 July 2007 16 Emerson Process Management Marshalltown, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461 www.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Fisher 655R è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Fisher 655R - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Fisher 655R imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Fisher 655R ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Fisher 655R, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Fisher 655R.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Fisher 655R. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Fisher 655R insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.