Manuale d’uso / di manutenzione del prodotto 36 DV EFIII del fabbricante FireplaceXtrordinair
Vai alla pagina of 52
TM • Built-In Direct Vent Fireplace • Natural Gas or Propane • Residential or Mobile Home Featuring the Burner Tested and Listed by Omni-Test Laboratories, Inc. B eav er t on, O r egon R epor t # 028- S - 20b- 1 A NS I Z 21. 88, CS A 2. 33 MR 8, CA N/ CG A 2.
2 Introduction Travis Industries 4040708 100-01160 Introduction We welcome you as a new owner of a Fireplace Xtrordinair gas fireplace. In purchasing a Fireplace Xtrordinair you have joined the growing ranks of concerned individuals whose selection of an energy system reflects both a concern for the environment and aesthetics.
Table of Contents 3 Travis Industries 4040708 100-01160 Introduction Introduction & Important Information ................2 Safety Precautions Safety Precautions ......................................4 Features & Specifications Features ......
4 Safety Precautions Travis Industries 4040708 100-01160 • IF YOU SMELL GAS: * Do not light any appliance * Extinguish any open flame * Do not touch any electrical switch or plug or unplug anything .
Safety Precautions 5 Travis Industries 4040708 100-01160 • Do not place clothing or other flammable items on or near the heater. Because this heater can be controlled by a thermostat there is a possibility of the heater turning on and igniting any items placed on or near it.
6 Features and Specifications Travis Industries 4040708 100-01160 Features: - Works During Power Outages (millivolt system) - High Efficiency - Optional Thermostat or Remote Control - Realistic ".
Installation (for qualified installers only) 7 Travis Industries 4040708 100-01160 Installation Warnings: ! Failure to follow all of the requirements may result in property damage, bodily injury, or even death.
8 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Fireplace Placement Requirements Minimum Framing Dimensions A 1/2" clearance is required along the sides and back of the fireplace.
Installation (for qualified installers only) 9 Travis Industries 4040708 100-01160 Corner Installations A typical 45 ° installation uses the minimum framing dimensions shown in the illustration below (NOTE: all clearances still apply).
10 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Hearth Requirements The hearth must tuck underneath this ledge. 16” Min. 36" Min. for arch face 38-1/4" Min. for rectangular face Cement Board Tile, Marble, Brick, or other Non-Combustible Decorative Trim (may be combustible) Min.
Installation (for qualified installers only) 11 Travis Industries 4040708 100-01160 Facing Requirements NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
12 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Facing Detail 3-3/4" 35-1/4" 26-3/4" 6-3/4" 21-1/2" 23" 1" 1" Make sure these shaded areas are faced over when using the arched face.
Installation (for qualified installers only) 13 Travis Industries 4040708 100-01160 Face Dimensions Rectangular Bevel Face (Black or Gold) Access Door 38 ” 27-1/2 ” Classic Arched (Gold, Black, or Artisan*) 29" 5" 36 ” Access Door Radius = 35 ” * Artisan faces may vary slightly in size due to the forging process.
14 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Facing and Hearth Examples Fireplace Face 3/8" Thick Tile 1/2" Cement Board Wood Sub Floor 1" Side Vi.
Installation (for qualified installers only) 15 Travis Industries 4040708 100-01160 Facing and Hearth Examples (continued) 36 DV Fireplace Face 3/8" Thick Tile 1/2" Cement Board Wood Sub Flo.
16 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Mantel Requirements • The combustible area above the facing must not protrude more than 3/4" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Installation (for qualified installers only) 17 Travis Industries 4040708 100-01160 Vent Requirements ! The vent must maintain the required clearance to combustible materials to prevent a fire (see “ Clearances ” below). Do not fill air spaces with insulation.
18 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Vent Installation • In addition to the requirements below, follow the requirements provided with the vent.
Installation (for qualified installers only) 19 Travis Industries 4040708 100-01160 Approved Vent Configurations Restrictor Position • A vent restrictor is built into the appliance to adjust the flow rate of exhaust gases. This ensures proper combustion for all vent configurations.
20 Installation (for qualified installers only) Travis Industries 4040708 100-01160 V er t i c al T er m i n at i o n s w i t h 0, 2, o r 4 45° Of f s et s u s i n g 6- 5/8” D i a.
Installation (for qualified installers only) 21 Travis Industries 4040708 100-01160 Horizontal Terminations using 6-5/8” Diameter Vent Use a single 90 ° elbow (NOTE: an additional 45 ° elbow may be used on the horizontal run). The termination must fall within the shaded area shown in the chart.
22 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Ve rti ca l T e rmina ti ons w ith T wo or T hr e e 9 0 ° E l bow s U si ng 6 - 5 / 8 ” D ia . V e nt The termination must fall within the shaded area shown in the chart.
Installation (for qualified installers only) 23 Travis Industries 4040708 100-01160 H or i z onta l T e rm i na ti ons us ing 8 ” D i a m e te r V e nt The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.
24 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Termination Requirements (see the illustration below) A Minimum 9" clearance from any door or window B Minimum .
Installation (for qualified installers only) 25 Travis Industries 4040708 100-01160 Gas Line Requirements ! The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.
26 Installation (for qualified installers only) Travis Industries 4040708 100-01160 Electrical Connection ! Make sure the household breaker is shut off prior to working on any electrical lines.
Finalizing the Installation 27 Travis Industries 4040708 100-01160 1 Remove the glass frame (and arch covers) following the directions below. Warning: The appliance must be completely cool before removing the glass. Note : If using an arch face, attach the arch covers after re-installing the glass.
28 Finalizing the Installation Travis Industries 4040708 100-01160 Glass Frame Removal (continued) - Spring Pin Installation The spring pin can come loose from the latch assembly. This occurs when it is turned 1/4 turn when it is disengaged. Follow the directions below to re-install the spring pin if it becomes loose.
Finalizing the Installation 29 Travis Industries 4040708 100-01160 ? If converting to propane or using the firebacks, do so now before installing the logs (page 43 and 54). 2 Install the log set following the directions below. Step 1 Install the logs (see the illustration below).
30 Finalizing the Installation Travis Industries 4040708 100-01160 Step 2 Install the twigs and ember chunk (see the illustration below). Place the left and right twigs as shown. Place the ember chunk as shown. Step 3 Install the embers along the front of the burner (see the illustrations below).
Finalizing the Installation 31 Travis Industries 4040708 100-01160 4 Replace the glass frame (and arch covers when using arched faces - see page 27). 5 Install the faceplate following the instructions included with the faceplate.
32 Finalizing the Installation Travis Industries 4040708 100-01160 8 Turn the flame adjust knob to its highest position - the flames should be approximately 10" tall. Check the flame on low position. The flames should burn off of each burner hole.
Operation 33 Travis Industries 4040708 100-01160 Before You Begin ! Read this entire manual before you use your new fireplace (especially the section "Safety Precautions" on pages 4 & 5). Failure to follow the instructions may result in property damage, bodily injury, or even death.
34 Operation Travis Industries 4040708 100-01160 Starting The Pilot Flame The pilot flame is required to ignite the main burners (it also plays a safety role). It should be left on once lit. It will stay lit unless the gas control valve is turned to "OFF".
Operation 35 Travis Industries 4040708 100-01160 Starting the Fireplace for the First Time + Burn the heater at a high setting with the blower off for an extended period (up to 48 hours). This will cure the painted surfaces. Fumes from the paint curing and oil burning off the steel will occur.
36 Operation Travis Industries 4040708 100-01160 Adjusting the Blower Speed The internal blower helps transfer the heat from the fireplace into the room. It will not turn on until the fireplace is up to temperature (approximately 10 minutes after starting).
Maintenance 37 Travis Industries 4040708 100-01160 Maintaining Your Fireplace's Appearance ! Fingerprints or other marks left on the optional gold surface may become etched in place if they are not wiped clean prior to turning the fireplace on. Clean the gold with denatured alcohol and a soft cloth (with the fireplace cool).
38 Maintenance Travis Industries 4040708 100-01160 Troubleshooting Table Problem: Possible Cause: Don't Call for Service Until You: Pilot Will Not Light A gas shut off valve is turned off The gas.
Maintenance 39 Travis Industries 4040708 100-01160 How this Fireplace Works ! This fireplace was designed with safety as the primary concern. Many of the components inside this fireplace are for safety purposes. Therefore, only certified gas service technicians should service this fireplace.
40 Maintenance Travis Industries 4040708 100-01160 Wiring Diagram Fireplace Blower Rheostat Junction Box Hot (black) Common (white) Ground (green) Blower Snap Disk Optional Power Heat Duct Molex Conne.
Safety Label 41 Travis Industries 4040708 100-01160 The safety (listing) label is adhered to the base of the fireplace near the gas control valve. A copy of the safety label is shown below. Fireplace Xtrordinair 36 DV XL Direct V ent V ented Gas Fireplace Heater T ested and certified by OMNI-T est Laboratories, Inc.
42 Limited 7 Year Warranty Travis Industries 4040708 100-01160 To register your TRAVIS INDUSTRIES, INC. 7 Year Warranty, complete the enclosed Warranty card and mail it within ten (10) days of the appliance purchase date to: TRAVIS INDUSTRIES, INC., 4800 Harbour Pointe Blvd.
Optional Equipment (for qualified installers only) 43 Travis Industries 4040708 100-01160 LP Conversion Instructions Install the conversion kit prior to installing the gas line to ensure proper gas use. 1 Remove the glass (see page 27). Remove the logs and coals (if installed - page 28) 2 Remove the burner (see illustration below).
44 Optional Equipment (for qualified installers only) Travis Industries 4040708 100-01160 3 Follow the directions below to replace the orifices. 1/2" Wrench Use a 1/2 ” open end wrench to unscrew both orifices. Front Burner Orifice Screw the LP orifice in so the orifice shoulder protrudes 5/16 ” (indicating full insertion).
Optional Equipment (for qualified installers only) 45 Travis Industries 4040708 100-01160 5 Install the logs and embers. 6 Replace glass and face. 7 Remove the regulator from the front of the gas control valve. Replace with the propane regulator, using the new gasket and screws included with the regulator.
46 Optional Equipment (for qualified installers only) Travis Industries 4040708 100-01160 POWER HEAT DUCT (part # 98500769) The optional heat duct allows the fireplace to transfer heat to separate locations in the home. One or two ducts may be used . Installation should take place prior installing drywall.
Optional Equipment (for qualified installers only) 47 Travis Industries 4040708 100-01160 • Attach the blower box to the framing or floorboards of the home following the instructions below. Wall or Ceiling Mounting b Attach the wall mounting brackets to the blower box.
48 Optional Equipment (for qualified installers only) Travis Industries 4040708 100-01160 • Attach the starter ring to the fireplace following the directions below (use the most convenient side). Bend the tabs on the bottom of the starter ring up to lock it in place.
Optional Equipment (for qualified installers only) 49 Travis Industries 4040708 100-01160 • Attach the grill (and wall adapter, if necessary). Grill Wall Adapter (for use when the blower box protrud.
50 Optional Equipment (for qualified installers only) Travis Industries 4040708 100-01160 • Follow the directions below to wire the blower box. Remove the cover from the blower box. a b Insert sheathed cable through the cable clamp. After the wires have been connected tighten the clamp to secure the cable.
Optional Equipment (for qualified installers only) 51 Travis Industries 4040708 100-01160 • Run the free wire from the rheostat junction box to the fireplace.
52 Index Travis Industries 4040708 100-01160 Approved Vent Configurations ..........................1 8 Adjusting the Blower Speed ..............................3 5 Adjusting the Flame Height ...............................3 4 Air Shutter Adjustment .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il FireplaceXtrordinair 36 DV EFIII è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del FireplaceXtrordinair 36 DV EFIII - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso FireplaceXtrordinair 36 DV EFIII imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul FireplaceXtrordinair 36 DV EFIII ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il FireplaceXtrordinair 36 DV EFIII, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del FireplaceXtrordinair 36 DV EFIII.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il FireplaceXtrordinair 36 DV EFIII. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo FireplaceXtrordinair 36 DV EFIII insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.