AC P ow er For Business-Criti cal C on tinuity™ HE LP F4 F3 F2 F1 EM ERSO N ™ Net work P owe r Liebert ® P re ss a ny ke y ba ck to mai n me nu Li eber t N X 081 k VA -3 x3 12 - 16 -2009 Si ngle .
.
i T ABLE OF CONTENTS I MPORT ANT S AFETY I NSTRUCTION S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii FIGURES Figure 1 Remote Monitoring Panel components and functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Figure 2 Remote Monitoring Panel layout constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 I MPORT A NT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains importa nt safety and operating inst ructions concerning the installation and operation of the Liebert NX Remote Monitoring Pane l (RMP). R ead all safety, i nstallation and operat- ing instructions befo re beginning installation .
Introd uction 2 1.0 I NTRODUCTION The Liebert NX Remote Monitoring Panel (RMP) is designed as a remote user interface to monitor Liebert NX Uninterruptible Power Systems. The RM P monochrome liquid cr ystal di splay measures 122 x 92mm (4.8 x 3.6 inches).
Introd uction 3 Figure 2 Remote Monitoring Panel layout constraint s T able 1 RMP component location in Figure 1 1 Bypass Inpu t 10 F3 Function Key 2 Inver ter—DC to AC 11 F4 Functi on Key 3 Rectifi.
Installation 4 2.0 I NST ALLATION 2.1 Preliminary checks Before beginning to install the RMP, v erify that the equipment ha s reached site in its own pack aging and in good general condition. Pl ease notify immedi ately the shipper, E merson Network Po wer and your local Liebert rep res entative of any damage.
Installation 5 Figure 4 Communication cable connection 2.5 Mounting the RMP on Drywall To hang the RMP on drywall o r similar surface: 1. Dri ll four holes ( 6mm-by-26mm) in the w all, spacing them as show n in Figure 5 . 2. Insert the four factory-supplied , plastic anchors into the holes.
Installation 6 2.6 Electrical connections Connect the power and co mmunication cabl es to the RMP as shown in Figure 6 . Figure 6 Power and communication cable routing Extract four screws to remove th.
Installation 7 Connect the RS-485 communi cation cable to the Lie bert NX as shown in Figure 7 . Figure 7 RS-485 cable connection to Liebert NX Connect the other end of the RS-485 sign al cable to the X4 slot on the monitor board. The monitor board is inside the UPS front door.
Operation 8 3.0 O PERATION 3.1 St artup and Reset The RMP will start as soon as the power supply is connected. The LCD will illuminate without any data display ed; the LEDs will light up yellow. After 20 seconds, all LEDs will turn off and the LCD will show the op ening screen, shown in Figure 8 , for 10 seconds.
Operation 9 Figure 10 UPS and RMP firmwa re are comp atible screen When the Silence On/Off button is pushed, the relevant screen in Fi gure 11 will be displa yed for 5 seconds.
Operation 10 Figure 12 Communication with UPS failed If the RMP is functioning properly and the connection with UPS is correct, but the UPS does not sup- port the communication f unction with RMP, then the RMP wi ll display a the screen shown in Figure 13 to report “Firmware is not Compatible with UPS.
Operation 11 3.2 LED Mimic Power Flow The LEDs mounted on the mimic flow chart repres ent the various power paths and current UPS oper- ational status.
Operation 12 3.4 Direct Access Push Buttons—Keys The NX Remote Monitoring Panel has one direct access push button: Silence ON/OFF . The Silence ON/OFF button is a toggle ty pe buzzer mute; any new fault re-enables the buzzer.
Operation 13 The summary menu tree is shown in Figure 15 . Refer to Table 12 for a detailed de scription of each menu item. Figure 15 Menu tree Battery Battery voltage (V) Battery current (A) Battery temperature (°C) Remain Time Min.
Operation 14 3.6 Det ailed Descrip tion of Menu Items The description that follows refers to the graphic LCD monitor window shown on Figure 14 . UPS System Window: This fixed-pane window displays current time and date and identifies the UPS, its configuration and its status.
Operation 15 Current Record Window Keeps a log the eve nts that resulted in the current mode of operation. Ignores transient conditions that have been resolved . Use “page” (F1) and up / down arrow to read the events. For a complete history log, refer to the Records tab of the Me nu and Data Window.
Operation 16 3.7 St atus and Event Messages Refer to Table 13 for descriptions of events and alarms. T able 13 RMP messages Message Description / Suggested Action (if any) Inverter Comm. Fail Internal RS485 communic ation failure between mo nitor and inverter Rectifier Comm.
Operation 17 Inverter Asynchronous This alarm is triggered by an in verter softwa re routine when the inverter and bypass waveforms are misaligned by more than 6 degrees in phase. This ala rm resets automatically once the condition is no longer true .
Operation 18 Bypass Phase Reversed The phase sequence direction of bypass voltage is reversed. Normally, the phase of phase B lags 120 deg r ees behind phase A, and the phase of phase C lags 120 degrees b ehind phase B.
Operation 19 UPS Shutdown UPS Shutdown, output power-down Check UPS Output Inverter off during normal startup (diagno stics information only) Generator Connected Generator active signal received. Source share mode may be activate d pending UPS settings.
Operation 20 3.8 Prompt (Popup) Windows The prompt window is displayed duri ng the operation of the system to alert the user to certain condi- tions and / or to require user confirmation of a command.
Operation 21 Figure 16 Help screen 3.10 Default screen saver This default screen is displ ayed following 2 minu tes of operation with no new alarm or activity. After another 2 minutes of inactivity, the backlight turns off. Press an y key (F1-F4 or Help) to reactivate the screen.
T e chnical Specifications 22 4.0 T ECHNICAL S PECIFICATIONS T able 16 Mechanical specifications Mechanical Characteristics Units Value Height mm 100 Width mm 400 Depth mm 290 Weight kg 5.
T e chnical Specifications 23 4.1 Agency and Certifications Safety Standard : IEC/EN/AS 62040-1-1 incorporatin g applic able portions of IEC/EN/UL/AS 60950-1 Certification : CE and UL 60950 -1:2003, First Edition CSA C22.
EmersonNetworkPower.com Ensuring The Hi gh Av ailab ilit y Of Mission-Critic al Data And Ap plic ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Emerson Remote Monitoring Panel è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Emerson Remote Monitoring Panel - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Emerson Remote Monitoring Panel imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Emerson Remote Monitoring Panel ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Emerson Remote Monitoring Panel, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Emerson Remote Monitoring Panel.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Emerson Remote Monitoring Panel. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Emerson Remote Monitoring Panel insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.