Manuale d’uso / di manutenzione del prodotto MODBUS IP del fabbricante Emerson
Vai alla pagina of 372
Li eb er t ® Inte lliS lot ® Modbu s 485, Modbu s IP and BA Cnet IP Re fe r en ce G u id e.
.
i T ABLE OF CONTENTS 1.0 L IEBERT E QUIPMENT C OMP ATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 What’s New in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii Table 18 Liebert XDC ™ - Status and Co il . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Table 19 Liebert XDC ™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii Table 51 Liebert Nfinity ® - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Table 52 Liebert NX ™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv Table 79 Extra Notes to Table 78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 Table 80 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Lieber t Deluxe System/3 ™ , Liebert DS ™ , Liebert DS E ™ , Liebert HPM ™ , Liebert PeX ™ - Multistate Data .
Liebert Equipment Compatibility - What’s New in This Manual 1L i e b e r t ® IntelliSlot ® Modbus/BACnet IP 1.0 L IEBERT E QUIPMENT C OMP ATIBILITY 1.1 What’ s New in This Manu al Emerson Network Power ® has introduced a new Liebert IntelliSlot ® card platform —the Liebert IntelliSlot Unity ™ card.
Liebert Equipment Compatibility - Compatibility with Liebert Equipme nt Liebert ® IntelliSlot ® Modbus/BACnet IP 2 1.3 Comp atibility with Liebert Equipment T able 1 Liebert Equipment and Compatib l.
Liebert Equipment Compatibility - Compatibility with Liebert Equipme nt 3L i e b e r t ® IntelliSlot ® Modbus/BACnet IP • Power Distributi on & Power C onditioning Prod ucts Liebert Datawave .
Liebert Equipment Compatibility - Compatibility with Liebert Equipme nt Liebert ® IntelliSlot ® Modbus/BACnet IP 4 BACNET IP PROT OCOL • Thermal Manageme nt Products Liebert Challenger 3000 ™ 76.
Modbus Communicatio ns - Implementation Basics 5L i e b e r t ® IntelliSlot ® Modbus/BACnet IP 2.0 M ODBUS C OMMUNICATIONS 2.1 Implement ation Basics Modbus protocol pr ovides control and data acquisit ion, through query and response, between master and slave devices.
Modbus Commu nications - RTU Framing Liebert ® IntelliSlot ® Modbus/BACnet IP 6 2.3.2 Function Code The function code field tells the addressed slaves what function to perfor m. Function codes are designed to invoke a specif ic action by the slav e device.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 7L i e b e r t ® IntelliSlot ® Modbus/BACnet IP 3.0 M ODBUS 485 AND M ODBUS IP P ROTOCOLS 3.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 8 Compressor Pump Down Issue 2 10044 — 1 Active on Ala rm 1, 2, 3, 4, 5, 6 Dig Scroll Com.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 9L i e b e r t ® IntelliSlot ® Modbus/BACnet IP Electric Reheater Hours Exceeded 2 10085 — 1 Active on Alarm 1, 2, 3, 4, 5, 6 Elec.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 10 RAM Battery Issue 10227 — 1 Active on Alarm 1, 2, 3, 4, 5, 6 W ater Leakage Detector S.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 11 Liebert ® IntelliSlot ® Modbus /BACnet IP Remote Sensor Over T emperature 6 10361 — 1 Active on Alarm 2, 3, 4, 5, 6 Remote Sens.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 12 Condenser Circuit Unspecified General Event 10494 — 1 Active on Alarm 3, 4, 5, 6 Input.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 13 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 8 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Li.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 14 Compressor Hours Threshold 1 30071 4007 1 1 — hr 1, 2, 3, 4, 5, 6 Compressor Hours Thr.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 15 Liebert ® IntelliSlot ® Modbus /BACnet IP Dig Scroll Comp Discharge T emp 2 30751 — 1 — deg F 1, 2, 3, 4, 5, 6 Return Humidit.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 16 Infrared Humidifier Flush Rate 30273 4027 3 1 — % 1, 2, 3, 4, 5, 6 Fan Control Mode 30.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 17 Liebert ® IntelliSlot ® Modbus /BACnet IP Ext Condenser Pump High W ater - Eve nt Control 30297 40297 1 — 0 = disabled 1 = enab.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 18 Service Required - Event Contro l 30317 40317 1 — 0 = disabled 1 = enabled 1, 2, 3, 4,.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 19 Liebert ® IntelliSlot ® Modbus /BACnet IP Compressor Low Suctio n Pressure - Event T ype 1 30337 4 0337 1 — 0 = Message 1 = W a.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 20 Ext Air Sensor A Low Humidity - Event Control 30357 40357 1 — 0 = disabled 1 = enabled.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 21 Liebert ® IntelliSlot ® Modbus /BACnet IP Condenser Issue - Event Control 1 30377 40377 1 — 0 = disabled 1 = enabled 1, 2, 3, 4.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 22 Adjusted Humidity 30499 — 1 10 % RH 2, 3, 4, 5, 6 Return Dew Point 30500 — 1 1 0 deg.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 23 Liebert ® IntelliSlot ® Modbus /BACnet IP Remote Sensor T emperature 9 30559 — 1 10 deg C 2 , 3, 4, 5, 6 Remote Sensor T empera.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 24 Condenser Low Noise Mode St art Time 30681 40681 2 — Seconds since Midnight 3, 4, 5, 6.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 25 Liebert ® IntelliSlot ® Modbus /BACnet IP Instantaneous Power 1 30860 — 1 - W 6 Instantaneous Power 2 30861 — 1 — W 6 Insta.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 26 T able 10 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Li.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 27 Liebert ® IntelliSlot ® Modbus /BACnet IP Compressor Capacity Control St a t e Compressor capacity control state. When 'O N', the cooling capacity of the compressor has been reduced.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 28 Compressor Utilization Present compressor utilization expressed as a percentage of the ma ximum rated capacity . Condenser Circuit Unspecified General Event One or more unspecified condenser circuit events active.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 29 Liebert ® IntelliSlot ® Modbus /BACnet IP Customer Input 4 - Event Control Enable/disable the activation of the [Custome r Input 4] event. If set to 'disabled', the event will not be annunciated.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 30 Ext Air Sensor A High Humidity Threshold Threshold va lue used in the [External Air Sensor A High Humidity] event. Ext Air Sensor A High Humidity [Ext Air Sensor A Humidity] has exceeded [Ext Air Senso r A High Humidity Threshold].
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 31 Liebert ® IntelliSlot ® Modbus /BACnet IP Ext Dew Point Over T emp Threshold Threshold va lue used in the [Ext Dew Point Over T emperature] even t.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 32 Ext S tandby Glycol Pump On - Event T ype The event type for the [Ext S tandby Glycol Pump On] event. Ext S tandby Glycol Pump On The st andby glycol pump is on, as indicated by an external input signal.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 33 Liebert ® IntelliSlot ® Modbus /BACnet IP Free Cooling Internal T emperature Delta Minimum temperature delta required between supply fluid and internal ambient air temperatures in order to enable free cooling.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 34 Humidifier Issue Humidifier issue detec ted, causing it to be locked out. Humidifier Lockout Enable/disable the use of the humidifi er . Humidifier Low Water The water level in the humidifier has droppe d below its threshold.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 35 Liebert ® IntelliSlot ® Modbus /BACnet IP Master Unit Communication Lost - Event T ype The event type for the [Master Unit Communication Lo st] event. Master Unit Communication Lost Communi cation with master unit has been lost.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 36 Return Air Over T emperature Return ai r high temperature event. Return Air Sensor Event Control Enable/disable the activation of events re lated to measurements by the return air sensor .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 37 Liebert ® IntelliSlot ® Modbus /BACnet IP Supply Air T emperatu re Sensor Control Control mode to be used with th e supply air temperature se nsor . Supply Air T emperat ure Set Point Desired s upply air temperatur e.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 38 Unit Shutdown An event has occurred requiring the unit to be shutdown and disabled to prevent damage to the system. Unit S tandby Unit was placed in standby mode.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 39 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 1 1 Liebert CR V ™ - St atus and Coil Controller Liebert iCOM ® v4 Data Label.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 40 Supply Chilled Water Over T emp 10047 — 1 — Active on Alarm Chilled Water Control V .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 41 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 12 Liebert CRV ™ - Input and Holding Controller Liebert iCOM ® v4 Dat a Label Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 42 Remote Sensor T emperature Module Inde x 4 30427 — 1 10 deg C Remote Sensor T emperatu.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 43 Liebert ® IntelliSlot ® Modbus /BACnet IP Fan Control Sensor 30 463 40463 1 — 0 = Supply 1 = Remote 2 = Return Remote Sensor Fu.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 44 Condenser Low Noise Mode Sched ule Control 30491 4 0491 1 — 0 = disabled 1 = enabled C.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 45 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 13 Liebert CRV ™ - Glossary Controller Liebert iCOM ® v4 Data Label Data Description Air T emperature Con trol Sensor Sensor from which air tempe rature measurements will be used for cooling and heating control.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 46 Condenser Refrigerant Pressure Over Threshold Condenser refrigeran t pressure has exceeded a threshold. Condenser Refrigerant Pressure Sensor Issue Condenser refrigeran t pressure sensor is disconne cted or the signal is out of range.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 47 Liebert ® IntelliSlot ® Modbus /BACnet IP Fan S peed Proportio nal Band T emperature control band above the te mperature set point cal culated for proportional fan speed control.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 48 Return Air Over T emp Threshold Threshold value us ed in the [Return Air Over T emperature] event. Return Air O ver T emperature Return air high te mperature event.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 49 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 14 Liebert HPC ™ (Chiller) - St atus and Coil Controller Liebert iCOM ® v4 Da.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 50 Fluid Low Fluid Pressure 10070 — 1 Active on Alarm 1, 2 Supply (Outlet) Fluid — Supp.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 51 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 15 Liebert HPC ™ (Chiller) - Input and Holding Controller Liebert iCOM ® v4 D.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 52 Condensers 4 Condenser Fan S peed 30417 — 1 — Units: % Uint16 1, 2 Fluid Fluid Press.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 53 Liebert ® IntelliSlot ® Modbus /BACnet IP Evaporators Evaporator Return Fluid T e mperature 30469 — 1 10 Units: deg C Int16 1, .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 54 System Operations Return Fluid T emperature 30491 — 1 10 Units: deg C Int16 1, 2 Retur.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 55 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 16 Extra notes key to T able 15 Number Descriptio n 1 Thi s point is supported o.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 56 Evaporator Fluid Freeze - Auto Reset Evaporator outl et fluid temperature has dropped below the fre eze threshold. Evaporator has been sh ut down, but will restart when th e temperature rises above the threshold.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 57 Liebert ® IntelliSlot ® Modbus /BACnet IP Reheat Utilization Present reheating utili zation expressed as a percentage of the ma ximum rated capacity . Return Fluid Over T emp Alarm Threshold Threshol d value used to generate a [Return Fl uid Over T emp] alarm.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 58 T able 18 Liebert XDC ™ - St atus and Coil Controller Liebert iCOM ® v4 Data Des crip.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 59 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 19 Liebert XDC ™ - Input and Holding Controller Liebert iCOM ® v4 Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 60 System S tatus 30422 — 1 — 1 = Normal Opera tion 2 = S tartup 8 = Normal with Warnin.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 61 Liebert ® IntelliSlot ® Modbus /BACnet IP External Air Ext Air Sensor A Over T em perature 1001 1 — 1 Active on Alarm Ext Air S.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 62 T able 21 Liebert XDP ™ - Input and Holding Dat a Label Input Holding # of Reg Scale N.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 63 Liebert ® IntelliSlot ® Modbus /BACnet IP Minimum Room T emperature Set Point 30403 40403 1 10 Units : deg C Minimum Room T e mpe.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 64 Hot Aisle Over T emp Threshold 30459 40459 1 — Units : deg C Hot Aisle Over T emp Thre.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 65 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 20 Communication St atus 30976 — 1 — 0 = Connected 1 = Not Co nnected Fan.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 66 XD System 1 Secon dary Fans Fan S tate 31032 — 1 — 0 = off 1 = on 2 = economy Fan Ec.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 67 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 4 Secon dary Fans Fan S tate 31 137 — 1 — 0 = off 1 = on 2 = economy Fan .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 68 XD System 7 Secon dary Fans Fan S tate 31242 — 1 — 0 = off 1 = on 2 = economy Fan Ec.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 69 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 10 Secondary F ans Fan S tate 31347 — 1 — 0 = off 1 = on 2 = economy Fan .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 70 XD System 13 Secondary F ans Fan S tate 31452 — 1 — 0 = off 1 = on 2 = economy Fan E.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 71 Liebert ® IntelliSlot ® Modbus /BACnet IP XD System 16 Secondary F ans Fan S tate 31557 — — — 0 = off 1 = on 2 = economy Fa.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 72 XD System 19 Secondary F ans Fan S tate 31662 — 1 — 0 = off 1 = on 2 = economy Fan E.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 73 Liebert ® IntelliSlot ® Modbus /BACnet IP Ext Air Sensor A Under T emperature [Ext Air Sensor A T emper ature] has dropped below [Ext Air Under T emp Threshold]. Ext Air Sensor B Dew Point T emp Dew point temper ature as measured by external air sensor B.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 74 Pump Hours Exceeded [Pump Hours] has exceeded [Pu mp Hours Threshold]. Pump Hours Threshold Thresho ld value used in the [Pump Hours Exceeded] event.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 75 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 23 Liebert DS ™ and Liebert PeX ™ - St atus and Coil Controller Liebert iCOM.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 76 Comp 1 Overload 10039 — 1 — — Comp 1 Pumpdown Fail 10040 — 1 — — Comp 2 High.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 77 Liebert ® IntelliSlot ® Modbus /BACnet IP HW/HG Hrs Exceeded 10087 — 1 — — Hum Hrs Exceeded 10088 — 1 — — Dehum Hrs E.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 78 T able 24 Liebert DS ™ and Liebert PeX ™ - Input an d Holding Controller Liebert iCOM ® v3 Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 79 Liebert ® IntelliSlot ® Modbus /BACnet IP Electrical Heaters #1 Run Hours Threshol d 30076 40076 — — Hours Electrical Heaters.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 80 Daily Low T emp Time 30154 — — — Hh :mm Daily High Humidity 30155 — — — %RH .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 81 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 25 Liebert XDF ™ - St atus and Coil Controller Liebert iCOM ® v3 Data Descrip.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 82 T able 26 Liebert XDF ™ - Input a nd Holding Controller Liebert iCOM ® v3 Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 83 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 27 Liebert Challenger 3000 ™ , Liebert Deluxe System/3 ™ , Liebert Himod ™.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 84 Inverter on Bypass — 40291 1 — Bit 3 S tandby Fan On — 40291 1 — Bit 4 Loss of E.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 85 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 28 Liebert Dat aMate ™ , Liebert Mini-Mate Plus ™ , Liebert Mini-Mate2 ™ -.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 86 T able 29 Liebert Dat aMate ™ , Liebert Mini-Mate2 ™ - Input and Holding - MM2 Controller MM2 Liebert Products Liebert DataMate Liebert Mini-Mate2 A vailable Poin t s Data Description Input Register Holding Regist er # of Reg.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 87 Liebert ® IntelliSlot ® Modbus /BACnet IP Setpoints (V iew) T emperature — 40010 1 — — T emp T olerance — 4001 1 1 — .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 88 T able 30 Liebert Mini-Mate2 ™ 8 T on - Input and Holding - L8T Controller L8T Liebert Products Lieber t Mini-Mate2 8 T on A vailable Poin t s Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 89 Liebert ® IntelliSlot ® Modbus /BACnet IP EPO Shutdown — 40291 1 — Bit 8 Local Alarm 3 — 43291 1 — Bit 9 Local Alarm 4 .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 90 T able 31 Liebert Atlas Air ™ , Liebert Atlas PEC ™ , Liebert LECS 15 ™ - Input an.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 91 Liebert ® IntelliSlot ® Modbus /BACnet IP Setpoints (V iew) Return Air T emperature — 40016 1 10 d e g C (R/W) Return Air Humid.
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products Liebert ® IntelliSlot ® Modbus/BACnet IP 92 T able 32 Liebert Atlas Air ™ , Liebert Atlas PEC ™ , Liebert CE MS 100 ™ - Input .
Modbus 485 and Modbus IP Protocols - Thermal Managem ent Products 93 Liebert ® IntelliSlot ® Modbus /BACnet IP Humidity Low Level — 402 90 1 — Bit 4 Battery Level Low — 402 90 1 — Bit 5 Loss.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 94 3.2 Power Distribution and Po wer Conditioning Produ ct s T able .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 95 Liebert ® IntelliSlot ® Modbus /BACnet IP Alarm Point s Discrete alarm objects available; use auto-discove.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 96 T able 34 Liebert Datawave ™ , Liebert FPC ™ , Liebert PPC .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 97 Liebert ® IntelliSlot ® Modbus /BACnet IP T able 35 Liebert FDC ™ , Liebert FPC ™ , Liebert RDC ™ , .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 98 Panel 4 Panel Summary Alarm 101 16 — 1 — Active on Alar m Pan.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 99 Liebert ® IntelliSlot ® Modbus /BACnet IP Panel 4 Position 1 Branch Overcurrent 13409 — 1 — Active on .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 100 T able 36 Liebert FDC ™ , Liebert FPC ™ , Liebert RDC ™ , .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 101 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Power 2 Output V oltage X-Y 30430 — 1 — V AC Output .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 102 Panel Main Current Ix 30471 — 1 — A AC Panel Main Current Iy.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 103 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Panel Main V oltage V y THD 30514 — 1 10 % THD Panel Main V o.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 104 Panel 1 Position 1 Breaker position 30587 — 1 — — Branch C.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 105 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Panel 2 Position 2 Breaker position 31607 — 1 — — Branch .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 106 Panel 3 Position 84 Breaker position 33599 — 1 — — Branch .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 107 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Subfeed 1 Subfeed Current Ix 34 619 — 1 — A AC Subfeed Curr.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 108 Subfeed 64 Subfeed Current Ix 35 879 — 1 — A AC Subfeed Curr.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 109 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 37 Liebert FDC ™ , Liebert FPC ™ , Liebert RDC ™ ,.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 110 Output V oltage THD Unit outpu t V oltage T otal Harmonic Distortion has exceeded the limit. Output V oltage Vx THD Unit V oltage T otal Harmonic Disto rtion for phase X.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 111 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Phase Rotation Error Unit input phase sequence is not A, B, C. The p hase sequence should be verified and correcte d.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 112 T able 38 Liebert STS ™ , Liebert STS/PDU ™ - Input and Holding - STS Controller STS Liebert Products Liebert STS Liebert STS/PDU A vailable Poin t s Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 113 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Source 2 Overload — 40290 1 — Bi t 3 Power Supply 2 Fault .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 114 T able 39 Liebert STS2 ™ , Liebert STS2/PDU ™ - Input and Ho.
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 115 Liebert ® IntelliSlot ® Mo dbus/BACnet IP LoadKV A % — 40026 1 — % Source 1 V olts A-N — 40027 1 .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 116 Internal Comm Fail — 40290 1 — Bit 5 External Comm Fail — .
Modbus 485 and Modbus IP Protocol s - Power Distribution and Power Conditioning Products 117 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Load Over-current — 40292 1 — Bit 13 Ground Over-curre nt .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 118 3.3 UPS Systems T able 40 Liebert APM ™, Liebert NXC ™ , Liebert NXR ™ - St atus and Coil Data La.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 119 Liebert ® IntelliSlot ® Mo dbus/BACnet IP User Operation Invalid 10050 — 1 — Active on Alarm Power Sub Module Fault 1 0051 — 1 — Active on Alarm Battery Discharging 1 0052 — 1 — Active on Al arm UPS Output on Bypass 10053 — 1 — Active on Alarm Output Load on Maint.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 120 T able 41 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Input and Holding Data Label Input Register Holding Regist er # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 121 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Power Factor Phs C 30431 — 1 100 — System Output Pct Power Phase A 30432 — 1 — %.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 122 T able 42 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Glossary Data Label Dat a Description B.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 123 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Load Sharing Fau lt Difference between any phase inverter curr ent of u nit and t he relevant average output current of parallel system is more t han a specific percent of nominal current.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 124 System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor P.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 125 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Output Overload 10050 — 1 Active on Alarm Output Off Pending 10051 — 1 Active on Alarm Syst.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 126 T able 44 Liebert APS ™ - Input and Holding Data Label Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 127 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery Battery T ime Remainin g 30437 — 1 — Units : min Uint 16 Battery V olts for Cabinet 30438 .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 128 System Output Apparent Power L1 30473 — 1 100 Units : kV A Uint 16 System Output Apparent Power L2 30.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 129 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Auto Restart — — 40519 1 0 = disabled 1 = enabled Auto Restart Delay — — 405 20 1 Units : sec .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 130 BatteryModule 2 Module Operating S tatus 3 0670 — 1 — 0 = Normal 1 = W arning 2 = Alarm 4 = Fault B.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 131 Liebert ® IntelliSlot ® Mo dbus/BACnet IP.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 132 T able 45 Liebert APS ™ - Glossary Data Label Data Description Accumulated Discharge T ime The highest accumulated battery discharg e time among installed battery modules.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 133 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Frame Capacity T otal system capacity supp orted when the maximum number of power modules are installed. Frame Fan Fault The frame t op outlet fan has faile d.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 134 Output Qualificati on S tatus output qualific ation status Power Module Failure One or more conditio ns indica te a power module fai lure, service is required.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 135 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Power L 2 The sy stem output powe r on Line 2.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 136 T able 46 Liebert GXT2 ™ and Liebert GXT3 ™ - S tatus and Coil Data Description Stat us C oi l Numb.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 137 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 47 Liebert GXT2 ™ and Liebert GXT3 ™ - Inp ut and Holding Data Description Input Regist er Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 138 Output Current L1 30164 — 1 — A Input Maximum V oltage L1 30180 — 1 — V Input Minimum V oltage .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 139 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 50 Liebert Nfinity ® - St atus and Coil Data Description St a tus C oi l Number of Bits Sc ale.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 140 T able 51 Liebert Nfinity ® - Input a nd Holding Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 141 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 52 Liebert NX ™ - St atus and Coil Data Description Statu s Coi l Number of Bit s Scale Notes.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 142 DC Bus Balancer Faul t 10240 — — — — DC Bus 1 Power Su pply Fail 10251 — — — — Rectifie.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 143 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 53 Liebert NX ™ - Input and Holding Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 144 Input Current L1 30154 — 1 — A Input Power Factor L1 30155 — 1 1 00 — Bypass V oltage L1 30159 .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 145 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 54 Liebert NX 225-600kV A UPS - Input and Holding 3 Data Description Input Holding Register # of Reg Scale Notes/Unit s Identification Modbus Protocol V ersion — 40002 1 — XX.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 146 Output Source — 40050 1 — 1 = Other 2 = None 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Redu.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 147 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Diagnostic T est Failed — 400 89 1 — Bit 3 Communications Lost — 400 89 1 — Bit 4 Shutdown Pen.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 148 T able 55 Liebert NXL ™ - 60Hz, UL version (Model 40) - St atus and Coil Data Label St atus Coil # of.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 149 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery Over T emperature 10350 — 1 Acti ve on Warning N+1, 1+N, 1+1, SMS DC Bus Ground Fault - Posi.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 150 Controls Reset Required 10397 — 1 Active on Alarm SCC, N+1, 1+ N, 1+1, SMS Battery T est Failed 10398.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 151 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 56 Liebert NXL ™ - 60Hz, UL version (Model 40) - Input and Holding Dat a Label Input Register.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 152 System Output Pct Power Phase A 30165 — 1 — % N+1, 1+ N, 1+1, SMS System Output Power Factor Phs A .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 153 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery T otal Discharge Time 30316 — 1 — hr N+1, 1+N, 1+1, SMS Battery Discharge Power 3 0317 —.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 154 Rectifier Active Filter 30340 — 1 — 0 = Not Installed 1 = Installed N+1, 1+N, 1+1, SMS Rectifier S .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 155 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery V olts for Cabinet 4 3036 1 — 1 — VDC N+1, 1+N, 1+1, SMS Battery V olts for Cabinet 5 3036.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 156 Maintenance Isola tion Breaker (MIB) 30383 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC, 1+N, 1+1.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 157 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Configuration Description 30497 — 1 — 0 = Single Module System 33 1 = Single Module System 34 2 = .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 158 Sum of MMS Output RMS Currents for Phase B 30512 — 1 — Units : A AC 1+N, SCC Sum of MMS Output RMS .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 159 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Bypass Isolation Breaker for Module 1 (BIB1) 30537 — 1 — 0 = Open 1 = Close 2 = Not Installed SCC,.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 160 MMS Module Output V oltage S tatus 30557 — 1 — 0 = Fail 1 = Marginal Low 2 = Normal 3 = Marginal Hi.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 161 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS Module T otal kV A Output 30651 — 1 — Units : kV A SCC MMS Module DC Bus V o ltage 30652 — 1.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 162 EcoModeSchedule 2 Schedule Operation S tate - ECO Mode 30682 — 1 — 0 = disabled 1 = enabled SMS, 1+.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 163 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 57 Liebert NXL ™ - 60Hz, UL version (Model 40) - Glossary Data Label Dat a Description Auto R.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 164 Battery T otal Discharge T ime The cu mul ative battery discharge time Battery V olts at Main Disconnec.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 165 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Inlet Air T emperature The te mperature of the inlet ai r Input Breaker (CB1/RIB) Input breaker (CB1/R.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 166 Multiple Fan Failure Multiple fan failure On Generator A generator is su pplying the power to the syste.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 167 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Input RMS Current Phase C The system input RMS current for Phase C System Output Apparent Power.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 168 T able 58 Liebert NXL ™ - 50Hz, CE version (Models 48 and 49) - S tatus and Coil Data Description Sta.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 169 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus Low Fault 10074 — 1 Active on Alarm Output System Shutdown - EPO 10085 — 1 Active on Alarm .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 170 UPS Output on Bypass 10177 — 1 Active on Alarm Output Load on Maint.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 171 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 59 Liebert NXL™ - 50Hz, CE versi on (Models 48 and 49) - Input and Holding Data Label Inpu t .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 172 Battery V olts for Cabinet 4 3042 8 — 1 — Units : VDC Uint16 Battery V olts for Cabinet 5 3042 9 .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 173 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus DC Bus V ol tage 30465 — 1 — Units : VDC Uint16 DC Bus Current 30466 — 1 — Units : A DC.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 174 Inverter Inverter Overload Time Remaining 30510 — 1 — Units : sec Uint16 Inverter Output Qualif ica.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 175 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Wire Configuration 3 0556 — 1 — 0 = T wo Wi re (single phase + return) 1 = T w o Wire (2 ph.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 176 Ratings Bypass Nominal V oltage 3057 6 — 1 — Units : V AC Uint16 System Input Nominal V oltage 3057.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 177 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Module Output Breaker 30609 — 1 — 0 = Open 1 = Close 2 = Not Installed MultiModule Multi-module Sy.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 178 Module Output Breaker for Module 3 30646 — 1 — 0 = Open 1 = Close 2 = Not Installed Module Output B.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 179 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS UPS Output Source 30665 — 1 — 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 180 Intelligent Paralleling Intelligent Paralle l Operation S tate 30796 — 1 — 0 = disable d 1 = enable.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 181 Liebert ® IntelliSlot ® Mo dbus/BACnet IP EcoModeSch edule 14 Schedule Operation St ate - ECO Mod e 31019 — 1 — 0 = disabled 1 = enabled Sch.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 182 T able 60 Liebert NXL ™ - 50Hz, CE version (Models 48 and 49) - Gloss ary Data Label Data Description.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 183 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery T ime Remainin g The calculated available ti me on battery Battery T otal Discharge T ime The .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 184 Controls Reset Required A controls reset is required due to one or more critical settings chang ing DC Bus Current The current at the battery input terminals .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 185 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Internal Communications Failure T he control has detecte d a communication fai lure of a component on .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 186 MMS Output Pct Power Phase A The multi-module system output power on phase A as a percent age of the ra.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 187 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Output Series S tatic Switch o utput series static switch Output Wire Configuratio n Output wire confi.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 188 Schedule Minute - ECO Mode This setting represents the minute of the hour when an associated schedule entry action will take effect.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 189 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Nominal V oltage The no mi nal (or rated) system output voltage System Output Pct Power .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 190 T able 61 Liebert PowerSure ™ Interactiv e (before July 2008 ) - St atus and Coil Data Description St.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 191 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 62 Liebert PowerSure ™ Interactive (b efore July 2008) - Input and Holding Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 192 T able 63 Liebert PowerSure ™ Interactiv e 2 - St atus and Coil Applies only to PSI units manufacture.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 193 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 64 Liebert PowerSure ™ Interactive 2 - Input and Holding Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153) Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 194 T able 65 Liebert Series 300 ™ UPS - St atus and Coil Data Description Status C oi l Number of Bits S.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 195 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 66 Liebert Series 300 ™ UPS - Input and Holding Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 196 Bypass Current L2 30210 — 1 — A Output V oltage L2 30213 — 1 — V Output Current L2 30214 — 1 .
Modbus 485 and Modbus IP Protoc ols - UPS Systems 197 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 67 Liebert Series 600 ™ UPS - St atus and Coil Data Description Stat us C oi l Number of Bit .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 198 T able 68 Liebert Series 600 ™ UPS - Input and Holding Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 199 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 69 Liebert Series 610 ™ SCC UPS - St atus and Coil Data Description Stat us C o il Number of .
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 200 T able 70 Liebert Series 610 SCC UPS - Input and Holding Data Description Input Register Holding Regist er # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 201 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 71 Liebert HiPulse ™, Liebert SICE 7200 ™ - Input and Holding - SMM/SSM Controller Multi Module Series - SMM Liebert Products Liebert HiPulse Liebert SICE 7200 A vailable Poin t s Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 202 Rectifier Block — 40290 1 — Bit 7 Rectifier Current Limit — 40290 1 — Bit 8 Rectifier Overtempe.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 203 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 72 Liebert SICE 7200 ™ - Input and Holding - SSC Controller System Control Cabinet - SSC Liebert Produ cts Liebert SICE 7200 A vailable Poin t s Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 204 Output Undervoltage — 4029 0 1 — Bi t 7 Output Waveform Error — 4029 0 1 — Bit 8 T ransfer Coun.
Modbus 485 and Modbus IP Protoc ols - UPS Systems 205 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 73 Liebert Npower ™ - Input and Holding - IMP Controller Single Mo dule Series - SMS Liebert Product s Liebert Npower - SMS A vailable Poin t s Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protoc ols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 206 Equipment Over T emperature — 40290 1 — Bit 0 Any of Battery / Heatsink / Ambient / Timeout Shutdow.
Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 207 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 3.4 Battery Monitoring Product s T able 74 Alber ® BDSU ™ - St atus and Coil Data D.
Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products Liebert ® IntelliSlot ® Modbus/BACnet IP 208 Thermal Runaway Charger Current Level One Event S tring 1 - 32 13297-13328 — 1 Active.
Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 209 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 75 Alber ® BDSU ™ - Input and Holding Data Description Input Register Holding Register # of Reg.
Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products Liebert ® IntelliSlot ® Modbus/BACnet IP 210 Cell to Cell T emperature Deviation Threshold S tring 1 - 32 33042-33073 — 1 — Unit.
Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 211 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Cell T emp erature Low Global Th reshold S tring 1 - 32 32818-32849 — 1 Scale : x / .
Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products Liebert ® IntelliSlot ® Modbus/BACnet IP 212 Cell to Ambient T emperature Deviatio n Threshold S tring 1 - 32 39123-39152 — 1 Scal.
Modbus 485 and Modbus IP Protocols - Batte ry Monitoring Products 213 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Cell T emp erature Cell 321 – 360 39195-39234 — 1 Scale : x / 10 Units : deg C Cel.
BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 214 4.0 BAC NET C OMMUNICATIONS 4.
BACnet Communications - BACnet Protocol Implementation Conformance Statement 215 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 4.1.2 Supported Services Service Originate Res pond Alarm and Event Service.
BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 216 4.1.3 St andard Object T ypes Supported Object T ype X=Supported Accumulator.
BACnet Communications - BACnet Protocol Implementation Conformance Statement 217 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 4.1.4 Object Properties The following object properties are supported. Device Object The Device object represents the agent (t he card) rather than the managed device.
BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 218 Analog Object Unit s Possible values of the Units prop erty include the BACn.
BACnet Communications - BACnet Protocol Implementation Conformance Statement 219 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Binary Object Properties Multist ate Object Properties Binary Object Proper.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 220 4.2 Thermal Management Product s T able 76 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™.
BACnet Communicati ons - Thermal Management Pro ducts 221 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressors - Compressor 1 Compressor Hours Exceeded Binary_V alue 77 5269 _1_1 RD Active on Alarm.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 222 Free Cooling / Chilled Water Free Cooling V alve Ho urs Exceeded Binary_ V alue 1 17 5306_1 RD Acti.
BACnet Communicati ons - Thermal Management Pro ducts 223 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Condensers Condenser TVSS Issue Binary_V alue 218 5073_1 RD Acti ve on Alarm 1, 2, 3, 4, 5, 6 Cond.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 224 Supply Chilled Water Over T emp Binary_V a lue 271 4626_1 RD Acti ve on Alarm 1, 2, 3, 4, 5, 6 Unit.
BACnet Communicati ons - Thermal Management Pro ducts 225 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Events - iCOM DO Board 3 Digital Output Board Not Detected Binary_V alue 349 5 417_1_3 RD A.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 226 Low S tatic Pressure Binary_V alue 565 563 1_1 RD Active on Alarm 3, 5, 6 S tatic Pressure Sensor O.
BACnet Communicati ons - Thermal Management Pro ducts 227 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 78 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Delu.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 228 Return Air T emperature Set Point Analog_V alue 100 32 5333_1_1_deg _F RW Units: deg F 1 Return Air.
BACnet Communicati ons - Thermal Management Pro ducts 229 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T oday's High Humidity Analog_V alue 68 5343_1 RD Units: % RH 1, 2, 3, 4, 5, 6 T oday's .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 230 Compressors - Compressor 2 Compressor Hours Analog_ V alue 1 10 5267_1 _2 RW Units: hr 1, 2, 3, 4, .
BACnet Communicati ons - Thermal Management Pro ducts 231 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Humidifier Humidifier Hours Analog_V alue 186 5369_ 1 RW Uni ts: hr 1, 2, 3, 4, 5, 6 Humidifier Ho.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 232 Calculated Next Maintenance Month Analog_V alue 284 4868_1 RD — 1, 2, 3, 4, 5, 6 Calculated Next .
BACnet Communicati ons - Thermal Management Pro ducts 233 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sensor Average T emperature Analog_V alue 314 5007_1 RD Units: deg C 2, 3, 4, 5, 6 Remote S.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 234 Condenser Low Noise Mode - Interval Days Analog_V alue 533 5550_1_1 RW 1 = Monday 2 = Tuesday 4 = W.
BACnet Communicati ons - Thermal Management Pro ducts 235 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Fluid 1 Fluid Input T emperature Analog_ V alue 87 1 5897_1 RD Units: deg C 6 Fluid Input T empera.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 236 T able 80 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Delux.
BACnet Communicati ons - Thermal Management Pro ducts 237 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Fan Control Mode MultiS tate_V alue 82 5 373_1 RW 1 = Auto 2 = Manual 3 = Economy 4 = Delta 1 Fan .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 238 System Event Configuration Customer Input 1 - Event Control MultiS tate_V alu e 126 4718_1 RW 1 = d.
BACnet Communicati ons - Thermal Management Pro ducts 239 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ext Over T empera ture - Event Control MultiS tate_V alu e 146 5090_1 RW 1 = disabled 2 = enabled .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 240 Clogged Air Filter - Event T ype MultiS tate_V alu e 167 5136 _1 RW 1 = Message 2 = W arning 3 = Al.
BACnet Communicati ons - Thermal Management Pro ducts 241 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressor Pump Down Issue - Event T ype MultiSt ate _V alue 207 53 96_1_2 RW 1 = Message 2 = W ar.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 242 Low Return Hu midity - Event Ty p e MultiS tate_V alue 237 51 40_1_1 RW 1 = Message 2 = W arning 3 .
BACnet Communicati ons - Thermal Management Pro ducts 243 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Reheat Reheater Lockout MultiS tate_V alue 316 5582_1 R W 1 = disabled 2 = enabled 2, 3, 4, 5, 6 H.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 244 T able 82 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Delux.
BACnet Communicati ons - Thermal Management Pro ducts 245 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressor Capacity Control S tate Compressor cap a city control state. When 'ON', the cooling capacity of the compressor has been reduced.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 246 Condenser Circuit Unspecified General Event One or more unsp ecified condenser circuit eve nts active. See local unit display for further details. Condenser Issue - Event Control Enable/disable the activa tion of the [Condenser Issue] event.
BACnet Communicati ons - Thermal Management Pro ducts 247 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Customer Input 4 Customer Input 4 Dehumidifier Hours Exceeded Operating ho urs for the dehumidifier have exceeded th e threshold. Dehumidifier Hours Threshold Threshold value used in the [Deh umidifier Hours Exceeded] event.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 248 Ext Air Sensor A Issue The external air sensor A is disconnected or the signal is out of ra nge. Ext Air Sensor A Low Humidity - Event Control Enable/disable the activation of the [Ext Air Sensor A Low Humidity] event.
BACnet Communicati ons - Thermal Management Pro ducts 249 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ext Free Cooling Lockout - Event Control Enable/disable the acti vation of the [Ext Free Cooling Lockout] event. If set to 'disabled', the event will not be annuncia ted.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 250 Fan Hours Exceeded - Event Control Enable/disable the acti vation of the [F an Hours Exceeded] event. If set to 'disabled', the event will not be annuncia ted.
BACnet Communicati ons - Thermal Management Pro ducts 251 Liebert ® IntelliSlot ® Mo dbus/BACnet IP High Power Shutdown - Event T ype The event type for the [High Power Shutdown] event. High Power Shutdown Supply to high power components has been shutdown.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 252 Humidity Set Point Desired relative humidity . Infrared Humidi fier Flush Rate A multiple of an internal time consta n t that determines the flush duration of the infrared humidifier water pan.
BACnet Communicati ons - Thermal Management Pro ducts 253 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sensor Average T emperature Average val ue of remote sensor te mperature measurements. Remote Sensor Average Under T emperature [Remote Sensor Average T emperature] has dropped bel ow [Remote Sensor Under T emp Threshold].
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 254 Service Required Unit requi res servicing. Shutdown - Loss Of Power - Event Control Enable/disable the acti vation of the [Shutd own - Loss Of Power] event .
BACnet Communicati ons - Thermal Management Pro ducts 255 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T emperature Control Sensor Issue The air sensor selected for coolin g control is disconnected or the signal is out of range. T oday's High Air T emperature T i me [T od ay's High Air T emperature] w as measured at this time.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 256 T able 83 Liebert CRV ™ - Binary Dat a Controller Liebert iCOM ® v4 Dat a Label Object T ype Ins.
BACnet Communicati ons - Thermal Management Pro ducts 257 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sen sors 10 Remote Sensor Issue Binary_V a lue 151 5060_10 RD Active on Alarm Compressor Co.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 258 Unit Partial Shutdown Binary_V alue 237 51 12 _1 RD Active on Alarm Unit Shutdown Binary_V a lue 23.
BACnet Communicati ons - Thermal Management Pro ducts 259 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 84 Liebert CRV ™ - Analog Dat a Controller Liebert iCOM ® v4 Dat a Label Object T ype In.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 260 Remote Sen sors 1 Remote Sensor T emperature Anal og_V alue 56 5059_1 RD Units: deg C Remote Sensor.
BACnet Communicati ons - Thermal Management Pro ducts 261 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Condenser Low Noise Mode - Interval Days Analo g_V alue 287 5550_1_1 RW 1 = Monday 2 = T uesday 4 .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 262 T able 85 Liebert CRV ™ - Multist ate Dat a Controller Liebert iCOM ® v4 Data Label Object T ype.
BACnet Communicati ons - Thermal Management Pro ducts 263 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Event Configuration System Event Acknowledge/Reset MultiS tate_V alue 171 4717_1 WO 1 = Reset 2 = .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 264 Ext Reheat Lockout - Event T ype MultiS tate_V al ue 191 5085_1 RW 1 = Message 2 = W arning 3 = Ala.
BACnet Communicati ons - Thermal Management Pro ducts 265 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 86 Liebert CRV ™ - Glossary Data Label Data Description Air T emperature Con trol Sensor Sens or from which air temperature mea surements will be used for coo ling and heating control.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 266 Condenser Low Noise Mode S top Time The time of day at which the condenser will transition out of low noise mo de.
BACnet Communicati ons - Thermal Management Pro ducts 267 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Customer Input 3 - Event T y pe The event type fo r the [Customer Input 3] event. Customer Input 3 Customer input 3. Customer Input 4 - Event Control Enable/disable the activation of the [Custo mer Input 4] event.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 268 Fan Hours Exceeded Operating hours fo r the unit blower fan have exceede d the threshold. Fan S peed Manual Set Point Manual fan speed. Fan S peed Maximum Set Point Maximum fan speed.
BACnet Communicati ons - Thermal Management Pro ducts 269 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Remote Sensor T emperature Calculation Calculation method applie d to temperatur e readings from the remote sensors to determine a single te mperature measur ement value fo r cooling and heating control.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 270 System Operating S tate Current operating state of the system. System S tatus T he operating status for the system T op Fan Issue T he top fan is not operating within its normal parameters.
BACnet Communicati ons - Thermal Management Pro ducts 271 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 87 Liebert HPC ™ - Binary Data Controller Liebert iCOM ® v4 Dat a Label Object T ype Ins.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 272 Fluid - Supply (Outlet) Flu id Supply Fluid Over T emp Binary_V alue 84 4645_ 1_1 RD Active on Alar.
BACnet Communicati ons - Thermal Management Pro ducts 273 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 88 Liebert HPC ™ - Analog Data Controller Liebert iCOM ® v4 Dat a Label Obje ct T ype In.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 274 Free Cooling Free Cooling External T emperature Delta A nalog_V alue 1 12 5301_1 RW Units: deg C 1,.
BACnet Communicati ons - Thermal Management Pro ducts 275 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 89 Liebert HPC ™ - Multist ate Data Controller Liebert iCOM ® v4 Dat a Label Object T yp.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 276 T able 90 Extra Notes Number Descript ion 1 This point is supported on: FDM v32 iCOM Controller V ersion 2.02.xxx 2 This point is supported on: FDM v10 1 iCOM Controller V ersion 2.
BACnet Communicati ons - Thermal Management Pro ducts 277 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Customer Input 1 Customer input 1. Customer Input 2 Customer input 2. Customer Input 3 Customer input 3. Customer Input 4 Customer input 4. EEV Unspecified General Event One or more unspecified el ectronic expansion valve events active.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 278 Pump Hours Threshold Threshold value us ed in the [Pump Hours Exceeded] event. Pump Hours Operating hours for pump since last reset of this value. RAM Battery Issue RAM or RAM backup battery is no t operating correctly .
BACnet Communicati ons - Thermal Management Pro ducts 279 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 92 Liebert XDP ™ , Liebert XDC ™ - Binary Data Controller Liebert iCOM ® v4 Data Label.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 280 XD System 1 Ext System Condensation Detected Binary_V al ue 1 12 5 492_1 RD — Ext Fan Issue Binar.
BACnet Communicati ons - Thermal Management Pro ducts 281 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 93 Liebert XDP ™ , Liebert XDC ™ - Analog Data Controller Liebert iCOM ® v4 Data Label.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 282 XD System 1 T empe rature Sensor 4 Remote Sensor T emperature Analog_V alue 143 5059_1_4 RD — XD .
BACnet Communicati ons - Thermal Management Pro ducts 283 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 94 Liebert XDP ™ , Liebert XDC ™ - Multistate Dat a Controller Liebert iCOM ® v4 Data .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 284 Refrigerant Supply Refrig Over T emp - Event Control Multistate_V alue 41 4635_1 RD 1 = Di sabled 2.
BACnet Communicati ons - Thermal Management Pro ducts 285 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressors Compressor 1A S tate Multistate_V a lue 91 4665_1 RD 1 = Off / 2 = On Compressor 1B S .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 286 Circuit 2 Low Suction Pressure - Event Ty p e Multistate_V alue 1 14 4698_1 RW 1 = Message 2 = W ar.
BACnet Communicati ons - Thermal Management Pro ducts 287 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Fan Button Control Multistate_V alue 175 5488_2 RW 1 = Enabled 2 = Disabled Visual ID Control Mult.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 288 Sensor Issue - Event T ype Multistate_V a lue 812 5499_20 R W 1 = Message 2 = W arning 3 = Alarm Ex.
BACnet Communicati ons - Thermal Management Pro ducts 289 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Smoke Detected - Event T ype Multistate_V alue 859 4722_1 RW 1 = Message 2 = W arning 3 = Alarm W .
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 290 T able 95 Liebert XDP ™ , Liebert XDC ™ - Glossary Data Label Data Description Auto Restart Delay If power is lost, the control will delay this amount of time after power is restored before restarting the un it.
BACnet Communicati ons - Thermal Management Pro ducts 291 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Compressor 1B Short Cycle - Event T ype Th e event ty pe for the [Compressor 1B Short Cycle] event. Compressor 1B Short Cycle Compressor 1B short cycle.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 292 Ext Air Sensor A Over T emp - Event Control Enable/disable the activation of the [Ext Air Sensor A Over T emperature] event. If set to 'dis abled', the event wil l not be annunciated.
BACnet Communicati ons - Thermal Management Pro ducts 293 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ext Remote Shutdown Uni t is shut down by a remote signal. Ext System Condensation Detected - Event Control Enable/disable the activation of the [Ext System Condensation Detected] event.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 294 Pump Hours Operating hours for pump since last reset of this value. Pump Short Cycle - Event Control Enable/disable the activation of the [Pump Sh ort Cycle] event.
BACnet Communicati ons - Thermal Management Pro ducts 295 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Supply Fluid Over T emp Thre shold Threshold value used in the [Supply Fluid Over T emp ] event. Supply Fluid Over T emp [Supply Fluid T emperature] has e xceeded [Supply Fluid Over T emp Threshold].
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 296 Unit Code Missing Unit code has not been ente red and saved. Unit Communication Lost Master has l ost comm unication with one or more networked units.
BACnet Communicati ons - Thermal Management Pro ducts 297 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 96 Liebert Dat aMate ™ , Liebert Mini-Mate2 ™ - MM2 Controller MM2 Liebert Products Lie.
BACnet Communicati ons - Thermal Management Pro ducts Liebert ® IntelliSlot ® Modbus/BACnet IP 298 T able 97 Liebert Mini-Mate2 ™ 8 T on - L8T Controller L8T Liebert Product s Liebert Mini-Mate2 8.
BACnet Communications - UPS Systems 299 Liebert ® IntelliSlot ® Mo dbus/BACnet IP 4.3 UPS Systems T able 98 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Binary Data Data Label Object T ype .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 300 Power Sub Module Fault Binary_V alue 51 5158_1 RD Active on Alarm Battery Discharging Binary_V alue 52 4168 _1 RD Active on Alarm UPS Output on Bypass Binary_V alue 53 4298_1 RD Active on Alarm Output Load on Maint.
BACnet Communications - UPS Systems 301 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 99 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Analog Dat a Data Label Object T ype Inst ance Objec.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 302 MMS Output Apparent Power Analog_V alue 69 4812_1 RD Units: kV A MMS Output Power Analog_V alue 70 481 1_1 RD Units: .
BACnet Communications - UPS Systems 303 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 101 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Gl ossary Data Label Data Description Battery Auto .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 304 Load Sharing Fault Difference between any phase inverter current of unit and the relevant average output current of parallel system is more than a specific percent of nom i nal current.
BACnet Communications - UPS Systems 305 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Pct Power Phase B The system output power on phase B as a percentage of the rated capacity System Outp.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 306 T able 102 Liebert APS ™ - Binary Data Data Label Object T ype Instance Object Name Access Note s Input Rectifier F.
BACnet Communications - UPS Systems 307 Liebert ® IntelliSlot ® Mo dbus/BACnet IP PowerModule 1 Power Module Fan Fault Binary_V alue 99 5838_1 RD Active on Alarm Power Module Over T emperature Binar.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 308 T able 103 Liebert APS ™ - Analog Dat a Data Label Object T ype Instance Object Name Access Notes Input System Inpu.
BACnet Communications - UPS Systems 309 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Apparent Power L2 Analog_V alue 71 5869_1 RD Units: kV A System Output Power Analog_V alue 72 4208_1 R.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 310 T able 104 Liebert APS ™ - Multistate Dat a Dat a Label Object T ype Instance Object Name Access Notes Protocol Ser.
BACnet Communications - UPS Systems 311 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Auto Restart Minimum Battery Setting MultiS tate_V al ue 64 5832_1 RW 1 = 0% 2 = 10% 3 = 20% 4 = 30% 5 = 40% 6 = 50%.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 312 T able 105 Liebert APS ™ - Glossary Data Label Data Description Accumulated Discharge T ime The highest accumulated ba ttery discharge time among installed battery modules.
BACnet Communications - UPS Systems 313 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus Current The current at the battery input te rminals. In charging mode, the current will be a positive value.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 314 Output Load on Maint. Bypass Th e output power is supplied by the maintenance bypass Output Off Pending Outp ut off pending - shutdown imminent. Output On Dela y When a value is written to this poin t the output will be turned on after the specified time has elapsed.
BACnet Communications - UPS Systems 315 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Output Off The system output is off System Output Pct Pow er L1 The system output power on Line 1 as a perce .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 316 T able 106 Liebert NXL ™ - 60Hz, UL version (Model 40) - Binary Data Dat a Label Object T ype Instance Object Name .
BACnet Communications - UPS Systems 317 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Battery Self T est Binary_V alue 46 4741_1 RD Active on Alarm SMS, 1+N, N+1 Main Battery Disconnect Open Binary_ V a.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 318 Output Amp Over User Limit-Phs A Bi nary_ V alue 91 4286_1 RD Active on Alarm SMS, 1+N, SCC Output Amp Over User Limi.
BACnet Communications - UPS Systems 319 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Input Contact 09 Binary_V alue 146 42 78_1 RD Active on Alarm SMS, 1+N, N+1, SCC Input Contact 10 Binary_V alue 147 .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 320 Input Filter Cycle Lock Binary_V alue 192 4755_1 RD Active on Alarm SMS, 1+N, N+1 EMO Shutdown Binary_V alue 1 93 576.
BACnet Communications - UPS Systems 321 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 107 Liebert NXL ™ - 60Hz, UL version (Model 40) - Analog Dat a Dat a Label Object T yp e Instance Object Na.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 322 Battery V olts for Cabinet 8 Analog_V a lue 45 4155_1_8 RD Units: VDC SMS, 1+N, N+1 Battery T emperature for Cabinet .
BACnet Communications - UPS Systems 323 Liebert ® IntelliSlot ® Mo dbus/BACnet IP DC Bus DC Bus V oltage Analog_V alue 72 4148_1 RD Units: VDC SMS, 1+N, N+1 DC Bus Current Analog_V alue 73 4149_1 RD.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 324 Environment Inlet Air T emperature Analog_V alue 126 4291_1 RD Units: deg C SMS, 1+N, N+1 Inlet Air T emperatu re Ana.
BACnet Communications - UPS Systems 325 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MultiModule Multi-module System Output V o ltage RMS A-B Analog_V a lue 177 4801_1 RD Units: V AC 1+N, SCC Multi-mod.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 326 ModuleList 2 MMS Module T o tal kW Output Analog_V alue 226 4861_2 RD Units: kW SCC MMS Module T otal kV A Output Ana.
BACnet Communications - UPS Systems 327 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 108 Liebert NXL ™ - 60Hz, UL version (Model 40) - Multist ate Dat a Dat a Label Object T ype Instance Objec.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 328 System UPS Module T ype MultiS tate_V alu e 84 4303_1 RD 1 = Single Module System 2 = Module (1 + 1) 3 = Module (1 + .
BACnet Communications - UPS Systems 329 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System S tatus MultiS tate_V alue 91 4123_1 RD 1 = Normal Operation 2 = S tartUp 3 = Normal with Wa r n i n g 4 = No.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 330 Module Output Breaker (MOB) MultiS tate_V alue 126 477 5_1 RD 1 = Open 2 = Close 3 = Not Installed 1+N, SCC MultiModu.
BACnet Communications - UPS Systems 331 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System Isolation Output Breaker (IOB) MultiS tate_V alue 1 55 4854_1 RD 1 = Open 2 = Close 3 = Not Installed SCC SCC.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 332 MMS Module Inverter S tatus MultiS tate_V alue 276 4858_8 RD 1 = off 2 = on 1+N MMS Module Output V oltage S tatus Mu.
BACnet Communications - UPS Systems 333 Liebert ® IntelliSlot ® Mo dbus/BACnet IP T able 109 Liebert NXL ™ - 60Hz, UL version (Model 40) - Glossary Data Label Data Description Auto Restart I n Pro.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 334 Battery T ime Remain ing The calculated availabl e time on battery Battery T otal Discharge T i me The cumulative bat.
BACnet Communications - UPS Systems 335 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Continuous Operation - ECO Mode This se tting gives the user the ability to En able/Disable ECO Mode continuous operation.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 336 Intelligent Parallel Minimum R edundancy This is the minimum Number of Redundant Modules that the system will allow before bringing one or more modules back to norma l operation and terminating Intelligent Paralleling.
BACnet Communications - UPS Systems 337 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS Module DC Bus V oltage DC bus voltage of this module in a multi-module system MMS Module Inverter S tatus Multi-.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 338 Multi-module System Output V o ltage RM S A-N Multi-module system output RMS voltage between phase B and Neutral Mult.
BACnet Communications - UPS Systems 339 Liebert ® IntelliSlot ® Mo dbus/BACnet IP SCC Event Summary Summary of any active user alarms or faults on the SCC Schedule Action - ECO Mode This setting gives the user the abil it y to choose the action of a schedule entry to be either stop or start.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 340 System Output Frequency The system outpu t frequency System Output Low Power Factor The s ystem output pow er factor .
BACnet Communications - UPS Systems 341 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ta b l e 11 0 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—Binary Dat a Data Label Object T ype .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 342 DC Bus DC Bus Low Fault Bina ry_V alue 74 5563_1 RD Active on Alarm Output System Shutdown - EPO Binary_V alue 85 421.
BACnet Communications - UPS Systems 343 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Rectifier Rectifier Failure Bina ry_V alue 160 4295_1 RD Active on Alarm Vdc Backfeed Binary_V alue 162 587 9_1 RD A.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 344 Program Input Contact 09 Binary_V alue 237 589 2_1 RD Active on Alarm Program Input Contact 10 Binary_V alue 238 589 .
BACnet Communications - UPS Systems 345 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ta b l e 11 1 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—An alog Data Dat a Label Object T ype.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 346 DC Bus DC Bus V oltage Analog_V a lue 66 414 8_1 RD Units: VDC DC Bus Current Analog_V alue 67 4149_1 RD Units: A DC .
BACnet Communications - UPS Systems 347 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MultiModule Multi-module System Output V o ltage RM S A-B Analog_V alue 155 480 1_1 RD Un its: V AC Multi-module Sys.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 348 Ta b l e 11 2 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—Multist ate Data Data Label Object T y.
BACnet Communications - UPS Systems 349 Liebert ® IntelliSlot ® Mo dbus/BACnet IP System UPS Module T ype MultiS tate_V alue 87 4303_1 RD 1 = Single Module System 2 = Module (1 + 1) 3 = Module (1 + .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 350 Configuration Descri ption MultiS tate_V alue 91 4751_1 RD 1 = Single Module System 33 2 = Single Module System 34 3 .
BACnet Communications - UPS Systems 351 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ratings Input Isolation Transformer Mu ltiS tate_V alue 109 4266_1 RD 1 = Not Installed 2 = Installed Device S tatu .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 352 Module Output Breaker for Module 7 MultiSt ate_V alue 147 4842_ 1 RD 1 = Open 2 = Close 3 = Not Installed Module Outp.
BACnet Communications - UPS Systems 353 Liebert ® IntelliSlot ® Mo dbus/BACnet IP ModuleList 1 MMS Inter-M odule Comm S tatus MultiS tate_V alue 173 4856_1 RD 1 = Failed 2 = Normal MMS Event Summary.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 354 ECO Mode ECO Mode Operation S tate MultiS tate_V alue 3 04 5454_1 RW 1 = disabled 2 = enabled Continuous Operation - .
BACnet Communications - UPS Systems 355 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Ta b l e 11 3 L i e b e r t N X L ™ - 50 Hz, CE version (Models 48 and 49)—Glossary Data Label Data Description .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 356 Battery V olts at Main Disconnect The voltage between the positive and the negative battery terminals of the common b.
BACnet Communications - UPS Systems 357 Liebert ® IntelliSlot ® Mo dbus/BACnet IP ECO Mode Operation S tate This setting is used to enable or disable ECO Mode. ECO Mode Suspend ed ECO Mode session is suspe nded. EMO Shutdown An Emerge ncy Module Off command has been detected.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 358 Inverter Overload Phase C Inverter is operating with an overload on phase C Inverter Overload Time Remaining The calc.
BACnet Communications - UPS Systems 359 Liebert ® IntelliSlot ® Mo dbus/BACnet IP MMS Output Power The sum to tal power of all system output modules MMS Overload Multi-module system overload MMS UPS.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 360 Program Input Contact 03 When the signal from [Program Input Cont act 03] is active the function assi gned to this contact is executed.
BACnet Communications - UPS Systems 361 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Sum of MMS Output RMS Current s for Phase A The sum of the multi-module syste m output RMS currents for phase A Sum .
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 362 System Output Pct Pwr (V A) Phs B The system output apparent power on phase B as a percentage of the rated capacity S.
BACnet Communications - UPS Systems 363 Liebert ® IntelliSlot ® Mo dbus/BACnet IP Notes.
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 364.
.
While eve r y precaution has been take n to ensure the accuracy and complete ness of this litera ture, Liebert Corporation assume s no responsibility and disclaims all liability for damages re sulting from use of this inform ation or for any errors or omissions.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Emerson MODBUS IP è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Emerson MODBUS IP - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Emerson MODBUS IP imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Emerson MODBUS IP ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Emerson MODBUS IP, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Emerson MODBUS IP.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Emerson MODBUS IP. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Emerson MODBUS IP insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.