www.rosemount.com ¢00825-0100-4801J¤ Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S Rosemount 3051S Series Pressure T ransmitter with HART ® Protocol Rosemount 3051.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 2 © 2010 Rose mount Inc. Al l right s reserved. Al l marks prop erty of owner . Rosemount and th e Rosemount logo type are register ed trademarks of Rosemount Inc. Rosemount Inc.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 3 S TEP 1: M OUNT THE T RANSMITTER Liquid Flow Applications 1. Place tap s to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 4 S TEP 1 CO NTINU ED ... Panel Mount Pipe Mount Coplan ar ™ Flange T raditional Flange In-line Housings PlantWeb ™ Junction Box Remote Mount Display 4801_QIG_RevKB.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 5 S TEP 1 CO NTINU ED ... Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 6 S TEP 1 CO NTINU ED ... Figure 2. T orque values for the flange and fla nge adapter bolts O-rings with Flange Adapte rs W ARNING Whenever the flanges or adapters are removed, visually inspect the o-rings.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 7 S TEP 1 CO NTINU ED ... Inline Gage T ransmitter Orientation The low side pressure port (atmospheric refe rence) on the inline gage transmitter is located under the sensor module neck label.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 8 S TEP 4: C ONNECT W IRIN G AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erminals.” 2. Connect the positive lead to the “+” termi nal, and the negative lead to the “–” terminal.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 9 S TEP 4 CO NTINU ED ... Signal Wi ring Groundin g Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the T erminal Compartment.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 10 S TEP 4 CO NTINU ED ... Remote Display Wiring and Power Up The Remote Mount Display and Interface system consists of a local transmitter and a remote mount LCD display assembly .
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 11 S TEP 4 CO NTINU ED ... Intrinsic Safety Consideration: The tra nsmitter assembly with remote display has been approved with Belden 3084A DeviceNet cable.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 12 S TEP 4 CO NTINU ED ... NOTE Wire colors provided on page 1 1 are per Belde n 3084A DeviceNet cable. Wire color may vary depending on cable selected. Belden 3084A DeviceNet cable includes a ground shield.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 13 S TEP 4 CO NTINU ED ... Conduit Electrica l Connector W iring (Option GE or GM) For 3051S transmitters with conduit electrical connectors GE or GM, refer to the cor dset manufacturer ’ s installation instructions for wiring details.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 14 S TEP 5: V ERIFY C ONFI GURATION Use any HART -compliant master to commun icate with and verify configuration of the 3051S. For the HART Diagnostics transmitte r (option code DA1), DD revision 3051S HDT Dev .
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 15 A check ( ⻫ ) indicates the basic configuration parame ters. At a minimum, these parameters should be verified as part of the configuration and startup procedure. T able 1.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 16 T able 2. Device Dashboard - Device Revision 7 and DD Revision 9 Fast Key Sequence Function Fast Key Sequence Alarm an.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 17 S TEP 6: T RIM THE T RANSMI TTER T ransmitters are shipped fully calibrated per r equest or by the factory default of full scale (lower range value = zero, upper range value = upper r ange limit).
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 18 S AFETY I NSTRUMENTED S YSTEMS Additional Safety Instrumented Systems inform ation is available in t he Rosemount 3051S reference manual (document number 00809-0100-4801) .
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 19 NOTES 1. T ransmitter output is not safety-rated during t he follo wing: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during tra nsmitter configuration and maintenance activities.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 20 Operation and Maintenance Proof T est and Inspectio n The following proof tests are recommended. Proof test results and corrective actions taken must be documented at http://rosemount.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 21 Reference Certification The 3051S Safety-Certified Pressure Transmi tter was designed, developed, and audited to be compliant to IEC 61508 safety-certified SIL 2 Claim Limit.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 22 P RODUCT C ERTIFICATIONS Approved Manufactur ing Locations Rosemount Inc.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 23 European Certifications I1 A TEX Intrinsic Safety -HART/Remote Display/Quick Connect/HART Diagnostics Certificate No.: BAS01A TEX1303X II 1 G Ex ia IIC T4 (-60 °C T amb 70 °C) 1 180 Special Conditions for Safe Use (X) 1.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 24 ND A TEX Dust Certificate No.: BAS01A TEX1374X II 1 D Ex tD A20 T105 °C (-20 °C T amb 85 °C) V max = 42.4 volts max A = 22 m A IP66 1 180 Special Conditions for safe use (x): 1.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 25 Jap anese Certifications E4 TIIS Flameproof Ex d IIC T6 China (NEPSI) Certifications E3 China Flameproof, Dust Ignition-proof Certificate No. (manufactured in Chanhassen, MN): GYJ091035 Certificate No.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 26 INMETRO Certifications I2 Brazilian Approval (INMETRO Approval) - Intrinsic Safety Certificate number: CEPEL-EX-0722/0.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 27 IECEx Dust Certificate No. IECExBAS09.0014X Ex tD A20 T105 °C (-20 °C ≤ Ta m b ≤ 85 °C) Vmax = 42.4 V A = 22 m A IP66 Special conditions for safe use (x) 1. Cable entries must be used which maintain the ingress protectio n of the enclosure to at least IP66.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 28 N7 IECEx T ype n Certificate No.: IECExBAS04.0018X Ex nC IIC T5 (T a = -40 ° C to 70 °C) Ui = 45 Vdc MAX IP66 Special conditions for safe use (x) The apparatus is not capable of withstanding the 500 V insulation test requir ed by Clause 6.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 29 DOC 4801_QIG_RevKB.fm Page 29 Frid ay, December 3, 2010 1:17 AM.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 30 4801_QIG_RevKB.fm Page 30 Frid ay, December 3, 2010 1:17 AM.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 31 Schedule EC Declaration of Conformity RMD 1044 Rev. I File ID: 3051S CE Marking Page 3 of 5 K:prodapprEUCDOCS3051S_RMD1044I(3).
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 32 4801_QIG_RevKB.fm Page 32 Frid ay, December 3, 2010 1:17 AM.
Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 33 4801_QIG_RevKB.fm Page 33 Frid ay, December 3, 2010 1:17 AM.
Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 34 4801_QIG_RevKB.fm Page 34 Frid ay, December 3, 2010 1:17 AM.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Emerson 3051S è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Emerson 3051S - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Emerson 3051S imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Emerson 3051S ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Emerson 3051S, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Emerson 3051S.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Emerson 3051S. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Emerson 3051S insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.