3 Macurco ™ Combustible Gas Detector , Controller and T ransducer User Instructions IMPORT ANT : Keep these User Instructions for reference. GD-6.
1 T ABLE OF CONTENTS GENERAL SAFETY INFORMA TION ................................................................................................................ 2 Intended Use ..........................................................................
2 3 W WARNING GENERAL SAFETY INFORMA TION Intended Use The 3M™ Macurco™ GD-6 Combustible Gas Detector , Controller and T ransducer is a low voltage device with selectable 4-20mA output, buzzer and digital display options.
4 5 Ifyouhaveanydoubtsabouttheapplicabilityoftheequipmenttoyourjobsitua tion, consultanIndustrialHygienistorcall3M Macurco T echnical Ser vice at 1-800-243-4630. In Canada, call 1-800-267-4414.
6 7 Installation 1. The 3M™ Macurco™ GD-6 Combustible Gas Detector mounts on a type 4S electrical box supplied by the contractor . 2. Connect the 3M™ Macurco™ GD-6 Combustible Gas Detector to Class 2 power supply only .
8 9 T ypical Multiple 3M™ Macurco™ GD-6 Combustible Gas Detector Installation INSTALLA TION NOTES 1. One sensor per 900 square feet (approximately). 2. If the gas used is natural gas (methane) or Hydrogen (H2) mount the 3M™ Macurco™ GD-6 Combustible Gas Detector high on a wall about one foot down from the ceiling.
10 11 GD-6 Main Fan Power 120VAC ALARM 120VAC Power Exhaust Fans coil coil power output GD-6 – + power output – + 8 7 6 5 4 4 3 3 2 2 1 1 1 1 3 3 4 5 6 7 8 9 2 24 V RET N.
12 13 T o change settings, remove the Philips screw on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector . Pull off the front cover of the unit. Gas Selection T o select the Gas Option , in normal mode, press the Next button once to display the current gas selection ( mE is Methane, Pro is Propane and Hy is Hydrogen) .
14 15 Selecting Fan Minimum Run Time – “Frr” T o select the Fan Minimum Runtime setting, in normal mode, press the Ne xt button twice to get to “Con” or the Configuration menu. Then press the Enter button to enter the Con menu. The ninth selection is the “Frr” or Fan Minimum Run Time.
16 17 Operation T est 1. Remove the single screw in the middle of the front cover of the 3M™ Macurco™ GD-6 Combustible Gas Detector . 2. Remove the front cover . 3. Observe the LED light on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector .
18 19 Gas T esting T esting the Fan Relay Note: The gas concentration to activate the fan relay depends on the setting. 1. Remove the Philips screw on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector . Remove the front cover . 2. Connect the 10% LEL cylinder of Combustible Gas to the regulator .
20 21 5. The 4-20mA output should ramp up from 4mA in clean air to 20mA at 50% LEL. See 4-20mA diagram in these User Instructions . Note: If the 4-20mA output does not ramp up within 2 minutes, consider these possibilities: a. Gas cylinder is empty , check the pressure gauge.
22 23 7. Press the Enter button and the display will read 10 alternating with the gas, mE, Pro or Hy (blinking), indicating the sensor is looking for gas. 8. Start applying gas to the gas sensor . Note: The sensor will look for the gas for 45 seconds.
24.
3M Occupational Health and Environmental Safety Division 3M Center , Building 0235-02-W-70 St. P aul, MN 55144-1000 Printed in U.S.A. © 3M 2008-2011. All rights reserved.
Requester: Farrel Allen Creator: deZinnia File Name: 34870758629.indd Structure #: SS-41964 Date: 6/17/11 Printed Colors – Front: Printed Colors – Back: Match Colors: This artwork has been created as requested by 3M. 3M is responsible for the artwork AS APPROVED and assumes full responsibility for its correctness.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il 3M GD-6 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del 3M GD-6 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso 3M GD-6 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul 3M GD-6 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il 3M GD-6, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del 3M GD-6.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il 3M GD-6. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo 3M GD-6 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.