Manuale d’uso / di manutenzione del prodotto 7684-S-8 del fabbricante 3M
Vai alla pagina of 22
3M ™ C old Shrink QT - II I Si licone R ub b e r Sk ir ted T ermination K it With Hi gh-K Stress R el i ef Fo r T ap e Shield ed, W ire S hielde d a nd U niS hield ® Ca ble 7 68 4-S -8 Ins tr uc tions IEEE Std. No. 48 Class 1 T ermination 35 kV Class 200 kV BIL F CAUTION Working around energized systems may cause serious injury or death.
2 78-81 17-0985-2 Rev C 1.0 Kit Contents 3 High-K, T racking Resistant, Silicone Rubber T erminations 3 Preformed Ground Braids 3 Constant Force Springs 3 3M™ EMI Copper Foil Shielding T ape 1 181 S.
78-81 17-0985-2 Rev C 3 Instruc tions For T a pe Shielded Ca ble 2.0 Pr epare Cable 2.1 Check to be sure cable size fits within kit size range as shown in T able 1 (page 2). 2.2 Prepare cable using dimensions shown in Figure 1. Be sure to allow for depth of terminal lug.
4 78-81 17-0985-2 Rev C 3.0 Install Ground Br aid 3.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a single wrap of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 2). Cut off excess.
78-81 17-0985-2 Rev C 5 3.3 W rap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. W rap spring in same direction as ground braid (Figure 4). Cinch (tighten) the spring after wrapping the final winding.
6 78-81 17-0985-2 Rev C 4.0 Install Lug or Connector 4.1 Check to insure 3M™ Cold Shrink QT -III Silicone Rubber T ermination assembly fits over the selected lug or connector . If lug or connector (Figure 6) will not fit through the termination core, clean the insulation (per Step 5.
78-81 17-0985-2 Rev C 7 6.0 Install T er mination 6.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 7). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 7).
8 78-81 17-0985-2 Rev C In structions fo r Wire Sh iel ded Ca ble 7.0 Prepare Cable 7.1 Check to be sure cable size fits within kit size range as shown in T able 1 (page 2). 7.2 Prepare cable using dimensions shown in Figure 8 and 9. Refer to T able 3 for semi-con cutback dimension.
78-81 17-0985-2 Rev C 9 8.0 Install Ground Braid 8.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a single wrap of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 10). Cut off excess.
10 78-81 17-0985-2 Rev C 8.3 W rap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. W rap spring in same direction as ground braid (Figure 12). Cinch (tighten) the spring after wrapping the final winding.
78-81 17-0985-2 Rev C 11 9.0 Install Lug or Connector 9.1 Check to insure 3M™ Cold Shrink QT -III Silicone Rubber T ermination assembly fits over the selected lug or connector . If lug or connector (Figure 14) will not fit through the termination core, clean the insulation (per Step 10.
12 78-81 17-0985-2 Rev C 11.0 Install T er mination 1 1.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 15). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 15).
78-81 17-0985-2 Rev C 13 Ins t ru c t ion s for U niS hield ® Shielde d Cable 12.0 Prepare Cable 12.1 Check to be sure cable size fits within kit size range as shown in T able 1 (page 2). 12.2 Prepare cable using dimensions shown in Figure 16, 17 and 18.
14 78-81 17-0985-2 Rev C 12.4 Remove constant force spring. Carefully bend shield wires back upon cable jacket 1 1/2" (38 mm). Cut excess shield wire and discard (Figure 17). 1 1/2 (38 mm) Semi-Conductive Ja ck et F old Back Shield Wires Depth of T er minal Lug + Growth All ow ance [A] + 3” (76 mm) Figure 17 12.
78-81 17-0985-2 Rev C 15 13.0 Install Ground Braid 13.1 Select a Scotch® Mastic Strip 2230 from kit and remove white release liners. Using light tension, apply a single wrap of mastic around the cable semi-conductive jacket 1/4" (6 mm) from shield wires ( Figur e 19 ).
16 78-81 17-0985-2 Rev C 13.3 W rap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with constant force spring. W rap spring in same direction as ground braid (Figure 21). Cinch (tighten) the spring after wrapping the final winding.
78-81 17-0985-2 Rev C 17 14.0 Install Lug or Connector 14.1 Check to insure 3M™ Cold Shrink QT -III Silicone Rubber T ermination assembly fits over the selected lug or connector . If lug or connector (Figure 23) will not fit through the termination core, clean the insulation (per Step 15.
18 78-81 17-0985-2 Rev C 16.0 Install T er mination 16.1 Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with the loose end (Figure 24). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape marker previously applied (Figure 24).
78-81 17-0985-2 Rev C 19 T ooling Index Lug and Crimping Information for 3M™ Scotchlok™ Copper Lugs 30014 thru 30045 One hole 31036 thru 31068 One hole-long barrel Cable Size AWG/ kcmil Stud Size (in.
20 78-81 17-0985-2 Rev C T ooling Index Lug and Crimping Information for 3M™ Scotchlok™ Copper/Aluminum Lugs 40016 thru 40079 One hole 40132 thru 40178 T wo hole Cable Size AWG/ kcmil Stud Size (in.) 3M™ Scotchlok ™ Lug Number Crimping T ool-Die Sets (Minimum Number Of Crimps) Burndy Corporation Thomas & Betts Corporation Square D Co.
78-81 17-0985-2 Rev C 21 T ooling Index Crimping Information for 3M™ Stem Connectors Copper/Aluminum Conductor Size AWG & kcmil 3M™ Connec - tor Number Crimping T able For 3M™ Stem T ype Connector Recommended Crimping T ools Stranded Solid Manufacturer Mech.
3M, Scotch and Scotchlok are trademarks of 3M Company . UniShield is a registered trademark of General Cable T echnologies Corporation. Important Notice All statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il 3M 7684-S-8 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del 3M 7684-S-8 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso 3M 7684-S-8 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul 3M 7684-S-8 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il 3M 7684-S-8, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del 3M 7684-S-8.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il 3M 7684-S-8. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo 3M 7684-S-8 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.