Manuale d’uso / di manutenzione del prodotto PROTECT C. 1000 (S) del fabbricante AEG
Vai alla pagina of 43
OPERATING IN STRUCTIONS U PS PROTECT C. 1000 (S) PROTECT C. 2000 (S) PROTECT C. 3000 (S) PROTECT C ..
2 Thank you for p urchasin g the AEG U PS PROT ECT C. from AEG Power Solution s. Safety information an d operating inst ructions are included in this manual. To ensure correct use of the UPS, please read thi s manual thoroughly before operating it. Save t his ma nual properl y.
3 1 Notes on these Operating Instructions Duty to Provide Information These operating instructions will help you to ins tall and operate the U ninterruptible P ower S uppl y (U PS) P R O T E C T C . 1 0 0 0 ( S ) , P RO TEC T C. 200 0 (S ) or PROTECT C.
4 The warrant y do es not appl y to dam age caused b y no n- compliance with these instructions (su ch da mage al so in clud es damagi ng the warranty seal). AEG will acc ept no liability for consequential d amage. AEG reserves the right to rescind all obligations suc h as warranty agreem ents, service contracts, etc.
5 Table of Contents 1 Notes on these Opera ting Instr uctions ............................. 3 2 General Inform ation.............................................. ............ 7 2.1 Technolog y................................................ .........
6 6 Signalling and Error C orrection ...................................... 35 6.1 Signalling ................................................... .............. 35 6.2 Fault Diagnosis / Fau lt Rectification ........................ 37 6.2.1 Error Messages .
7 2 General Informa tion 2.1 Technology i PROTECT C. is an U ninter ruptible P o wer S upply (UPS) for ess ential loads s uch as PCs, works tations, servers, n etwork c omponents, telecomm unication equipm ent and sim ilar de vices.
8 2.2 System Description The UPS is connect ed to a shock proof s ocket bet ween the public utilit y's mains and th e loads to be protect ed. The power section of the r ectifier conver ts the mains vo ltage to DC voltage for supplying the inverter.
9 3 Safety 3.1 General Safety Instructions Read these operatin g instr uctions pr ior to s tart-up of the PROTECT C. UPS an d its external batter y m odules (s pecial accessories), and observe the saf.
10 The UPS car ries high voltage. Danger! The u nit may only be op ened b y t rained and qualified personnel. R epairs m ay onl y be c arried out by qualified custom er service staff! The output m ay .
11 ♦ The unit is des igned to be instal led inside in hea ted rooms . Never install the housing in the vicinit y of water or in an excessivel y damp environm ent! ♦ Condensation m ay occur if the U PS is brough t from a cold environm ent into the room where it is to be installed.
12 W hen replacing the batteri es, the f ollowing m ust be obs erved: Only ever use identical m aintenance-f ree sealed lead batteries with the sam e data as th e original batteri es. Danger! Explosive ! Never throw batteries into open fire. Never open or dam age batteries.
13 3.3 CE-Certificate.
14 3.4 Technical Data Type pow er PROTECT C. 1000 (S) 1000 VA (cos ϕ = 0.7 lag.) 700 W PROTECT C. 2000 (S) 2000 VA (cos ϕ = 0.7 lag.) 1400 W PROTECT C.
15 Connection Non-heating app liance connectors Current Crest Rat io 3:1 Overload behavio ur up to 105 % ± 5 % continuous; in battery m ode > 105 % ± 5 % – < 150 % ± 5 % fo r 25 s; 150 % ±.
16 Battery charging cur rent (m ax.) PROTECT C. 1000 1 A PROTECT C. 1000 S 7 A PROTECT C. 2000 1 A PROTECT C. 2000 S 9. 6 A PROTECT C. 3000 1 A PROTECT C.
17 General data Classification V FI S S 2 11 a cc . to IE C 6 2 04 0 –3 Do ubl e c onve rsi on tec hnol ogy Overall efficienc y AC-AC (full lo ad) PROTECT C. 1000 (S) 85 % PROTECT C. 2000 (S) 85 % PROTECT C. 3000 (S) 88 % Noise level (1m distance) PROTECT C.
18 W eight s: PROTECT C. 1000 15 kg PROTECT C. 1000 S 8 kg PROTECT C. 1000 BP 19 kg PROTECT C. 2000 34 kg PROTECT C. 2000 S 15 kg PROTECT C. 3000 35 kg PROTECT C. 3000 S 16 kg PROTECT C. 2030 BP 52 kg Dimensions W x H x D: PROTECT C. 1000 (S) 145 mm x 220 mm x 400 mm PROTECT C.
19 4 Set-Up and Ope ration 4.1 Unpacking and Inspection The device has been fully tested and inspected. Although the device has been packed and shipp ed with t he usu al de gree of care, dam age during trans port cannot be ru led out completely.
20 Handle the com ponents with care. Please t ak e into accoun t the weight. It ma y be necessar y to engage th e he lp of a second person, particularl y in the case of the 2 and 3 kVA m odels and if there are external battery u nits. 4.2 Point of Installation PROTECT C.
21 4.3 Overview: Connections, Operating / Display Elements 4.3.1 Front view PROTECT C.1000 ( S) PROTECT C. 2000 (S) PROTECT C. 3000 (S) PROTECT C.1000 BP PROTECT C.
22 4.3.2 Display Explanations: 1. OFF-Pushbutton (O FF) 2. ON-Pushbutton (ON) / Alarm off 3. Orange LED bypass (B ypass) 4. Green LED inverter (Invert er) 5.
23 4.3.3 Rear view (conn ections): PROTECT C. 100 0 (S) P ROTECT C. 20 00 (S) PROTECT C. 300 0 (S).
24 Comments: 1. Mains connection (UPS input) 2. Mains input circuit break er 3. Load connections (UP S outputs) PROTECT C. 3000 (S) with additional load connection (IEC 3 20-16A) 4. Connection for externa l batter y module 5. Data interface for telephone, m odem fax (RJ 11) or 10/100 MBit/s n etwork (R J 45) 6.
25 5 Commissioning 5.1 Mechanical Set-Up Note the following points when setting u p the UPS system and its external batt ery units (special acc essories): ♦ The c ontact surf ace must be sm ooth and leve l. It mus t also be suff iciently strong and sturd y t o avoid v ibration and shock loads.
26 5.2 External Battery Expansions To achieve longer backup tim e, it is possible to connec t multi- battery pack s. Connect exclusively t he fol lowing products together: PROTECT C. 1000 with PROTECT C. 1000 BP PROTECT C. 2000 with PROTECT C. 2030 BP PROTECT C.
27 PROTECT C. with 2 batter y expansions Fig.: PROTECT C. 1000 and two C. 1000BP 1. Check the correct fit of th e UP S and the batter y unit (t he casings e.g. have to have the sam e dimension). 2. No w connect the corresponding battery connectors us ing the su pplied battery conn ection cables as shown in the figure above.
28 i Default s etting: No automatic supply for load over integrated b ypass af ter executing step 1 and 2 ( Modification of the c onfigurat ion wi th th e provided Software ” CompuW a tch“). 3. Then connect the outputs of your UPS to your loads. Use the l oad c onnection cables pr ovided f or this.
29 5.3 Operating Statuses 5.3.1 Normal Operation Once you have connect ed the U PS to a suitabl e m ains connection, you can start operation using the UPS main switch (see also "Electrical Start-Up" on page 27). Nor mally, the U PS operates cont inuousl y.
30 5.3.2 Battery Operation / Autonom y Operation The mains is not wi thin the requi red tole ranc e r ang e or has fai led. In this case powe r is suppl ied to the invert er from the cha rged batte r y with out inte rru ptio n. The powe r suppl y to the loa ds is there fore als o ensure d in the event of a main s fail ure.
31 W hen the v oltage and f requenc y ar e within th e tolera nce range once m ore, the rectifier and t he battery c harger s witch back on autom aticall y. The rectifier then co ntinues s uppl ying the inverter and th e batter y charger takes over c harging th e battery.
32 i The LED bar graph f unctions as displa y f or UPS utilisation. T he s ignal goes off during this operations status e very 2 seconds. 5.3.4 Unit Overload The load on the U PS shoul d ne ver exceed the specified rate d load of the unit.
33 5.4 Interfaces and communication 5.4.1 Data line protection R J11 and RJ4 5 The incom ing data lines are connected to the “IN” li ne at the rear of the UPS. T he “OUT” line is connected via data line with your term inal. i The data line protection s upports networ ks with transfer rates bet ween 10 a nd 100 MBit/s.
34 5.4.4 Shutdow n and UPS management sof tware The "Com puW atch" sof tware speciall y developed for these purposes by AEG continu ously check s the mains supply a nd the UPS status. In conjunction with the "intelligent" UPS, this ensures that the availability of IT components and data securit y is guarantee d.
35 6 Signalling and E rror Correctio n 6.1 Signalling 1. OFF push button ( OFF): Press the OFF switch for about 2 seconds t o switch on the U PS 2. ON push butto n (ON): Press the ON s witch for about 2 seconds to s witch of f the UPS.
36 6. LED Line (M ains status): The green LED li ghts up if mains volta ge is in a s pecified range of tolerance. The L ED Line flas hes when the ph ase and neutral conductor have bee n reversed at the input of the UPS s ystem . In this case turn the mains connector 18 0° in the shock proof socket.
37 6.2 Fault Diagnosis / Fault Rectification The PROTECT C. generates detailed err or m essages. Support personal c an loca lise and interpret faults quic k ly an d precisely. 6.2.1 Error Messages Problem Cause Solution UPS does not start . No indication, no au dible signal even thoug h system is connected to mains power supply.
38 Emergency supply period shorter than no minal value B atteries not fully charged / batteries old re sp. defect Char ge the batteries for at least for the charging time acc. Chapter 3.4 , page 16 and then check capacity. I f the problem still persi sts, consult your dealer .
39 7 Maintenance The PROTECT C. consists of advanced and resistan t components. To guarantee a continuous and high availab ility it is r ecom mended to chec k the unit (especiall y the batteries and the fans) in regu lar inte rvals (at least e very 6 months).
40 CAUTION: PROTECT C. m ust be disc onnected from the power su pply prior to carr ying out the following work . If large quantit ies of dust h ave accum ulated, the un it should, as a precaution, be c leaned with dr y com pressed air, in order to ensure adequate heat dis sipation.
41 8 Sto rage, Dism antling a nd Disposal 8.1 Storage Long stora ge tim es without char ging or discharging the batter y at regular intervals m ay lead to perm anent damage of the battery. If the ba ttery is stored a t room te m perature (20° C to 30° C) it will autom atically disc harge at a rate of 3 - 6 % per month due to internal r eactions.
42 9 Glossar y 9.1 Technical terms Class D, Class III see equip ment protection DC/DC Booster Circuit technology to boost the dir ect voltage on a higher voltage leve l Equipment protection Techno log.
43 Guarantee certificate T y pe: …….…… ………… ….......................... ....................... ..... Serial-no.: ………… ……… …..…………… ............................... Date of purchase: … ………….. ......
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il AEG PROTECT C. 1000 (S) è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del AEG PROTECT C. 1000 (S) - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso AEG PROTECT C. 1000 (S) imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul AEG PROTECT C. 1000 (S) ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il AEG PROTECT C. 1000 (S), ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del AEG PROTECT C. 1000 (S).
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il AEG PROTECT C. 1000 (S). Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo AEG PROTECT C. 1000 (S) insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.