Inst allation, S t art-Up and Service Instructions T ABLE OF CONTENTS SA FE TY C ON SI DE RA TI ON S . . . . . . . . . . . . . . . . . . . . . . . 1 PR E- IN ST AL LA T IO N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Mo vi ng a nd St or ag e .
2 PRE-INST ALLA TION 1. The power supply (v , ph, and Hz) must correspond to that specified on unit rating plate. 2. The electrical supply provided by the utility must be suf- ficient to handle load imposed by this unit. 3. Refer to Installation, General section (page 2) and Fig.
3 Fig. 2A — Dimensions – Size 25 LEGEND TXV — Thermostatic Expansion V alve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow . 3. Recommended clearance: • Rear: 3 in. (76 mm) • Front: 2 ft, 6 in. (762 mm) • Right Side: 2 ft, 6 in.
4 Fig. 2B — Dimensions – Sizes 28 and 30 UNIT UNIT WEIGHT lb (kg) 40RUA*28 1050 (477) 40RUA*30 1062 (482) 40RUS*28 1035 (469) 40RUS*30 1042 (473) LEGEND TXV — Thermostatic Expansion V alve NOTES: 1. Dimensions in [ ] are in millimeters. 2. Direction of airflow .
5 Table 1A — 4 0RUA Physical Data, En glish — Cooling Unit s LEGEND UNIT 40RUA* 25 28 30 NOMINAL CAP ACIT Y (T o ns) 20 25 30 OPERA TING WEIGHT (lb) Base Unit with TXV 730 1050 1062 Plenum 225 325 3 25 FA N S Qty .
6 Table 1B — 40RUA Physical Data, SI — Cooling Units LEGEND U N I T 4 0 R U A * 2 52 83 0 NOMINAL CAP ACITY (kW) 70 87 105 OPERA TING WEIGHT (kg) Base Unit with TXV 331 477 482 Plenum 102 148 148 FA N S Qty .
7 Table 1C — 40RUS Physical Data, Eng lish — Chilled Water Units LEGEND U N I T 4 0 R U S * 2 52 83 0 NOMINAL CAP ACITY (T ons) 20 25 30 OPERA TING WEIGHT (lb) Base Unit 683 1035 1042 Plenum 225 325 325 FA N S Qty ...Diam. (in.) 2...15 2...18 2...
8 Table 1D — 40RUS Physical Data, SI — Chilled Water Units LEGEND U N I T 4 0 R U S * 2 52 83 0 NOMINAL CAP ACITY (kW) 70 87 105 OPERA TING WEIGHT (kg) Base Unit 310 469 473 Plenum 102 148 148 F ANS Qty .
9 Fig. 3 — Model Number Nomenclature Fig. 4 — Serial Number Nomenclature Unit Positioning — The unit can be mounted on the floor for vertical application with return air entering the face of the unit and supply air dischar ging vertically through the to p of the unit.
10 Fig. 6 — Preferred Suspension Techn i que OVERHEAD SUSPENSION ACCESSORY UNIT SIZE 25 UNIT SIZES 28, 30 NOTE: Dimensions in [ ] are millimeters.
11 Unit Isolation — Where extremely quiet operation is essential, install isolators betw een floor and base of unit, or between ceiling and top section of unit. Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.
12 Fig. 8 — Face-Split Coi l Suction and Liquid Line Pi ping (Typical) Fig. 9 — Typical Evaporator Co il Connections (40RU) Fig. 10 — TXV Sensing Bulb Location LEGEND: TXV – Thermo static Expa.
13 Table 2 — Factory-Installed Nozzle and Distribu tor Data Table 3 — Fitt ing Requirements UNIT COIL TYPE STD TXV Qty ...Part No. DISTRIBUTOR Qty ...Part No. FEEDER TUBES PER DISTRIBUTOR † Qty ...Size (in.) NOZZLE Qty ...Part No. 40RU*25 4 Row 2.
14 Table 3 — Fit ting Requirement (cont) ‡ See Fig. 7 for acc es s hole location by numbe r . † Fittin gs are listed in order fr om header or tee stub con nection out to access hole in corner support post. UNIT ACCESS HOLE NO. ‡ CONNECT ION TYPE CIRCUIT FITTINGS REQUIRED † (in.
15 Chillled W ater Piping — See T ables 1C and 1D for chilled water connecton sizes. Fo r ease in bazing, it it recom- mended that all internal solder joints be made before unit is placed in final position. Knockouts are provided in the unit corner posts for 40RUS re- frigerant piping.
16 Condensate Drain — Install a trapped condensate drain line to unit connection as shown in Fig. 12. The unit drain con- nection is a PVC stub. See Fig. 13. Some areas may require an adapter to connect to either galvanized steel or copper pipe. For these applications, install a field-supplied threaded PVC adapter .
17 Power Supply and Wiring — Check the unit data plate to ensure that available power supply matches electrical characteristics of the unit. Provide a disconnect switch with an integrated lock-out feature of size required to provide adequate fan motor starting current.
18 Table 4 — Electrical Data , Sta nda rd Mot ors See Legend and Notes below . Table 5 — Electrica l Da ta, Alternate Motor s See Legend and Notes below . Legend and Notes For T ables 4 and 5 UNIT V -PH-Hz † V O LTA G E LIMITS F AN MOTOR POWER SUPPL Y Hp (kW) FLA Minimum Circuit Amps MOCP 40RUA*25 40RUS*25 208/230-3-60 187-253 5.
19 Fig. 17 — Unit Wiring LEGEND NOTE: Use copper conductors only . EQUIP — Equipment GND — Ground HC — Heating Con tactor HTR — Electric Hea ter IFC — Indoor-Fan C ontactor IFM — Indoor-.
20 Table 6 — Fan Contac to r Coil Data Connecting Ductwork — Refer to the Carrier System Design Manual for the recommended design and layout of ductwork.
21 Fig. 19 — Duct Flange Ins t a lla tio n ST AR T -UP Before starting unit, check the following and correct as necessary: • Is unit solidly supported? • Is fan adjusted for speed and pulley ali.
22 Centering Fan Wheel — If fan and fan shaft assembly are not properly centered, blades may scrape against the blower side scroll plate or may create an objectionable whistling noise. It may be necessary to adjust individual fan wheels or move en- tire fan shaft.
23 Fig. 23 — Fa n Rotation Fan Pulley Alignment — Align as follows: 1. Loosen setscrews on pulleys. 2. Align pulleys visually and tighten setscrews on fan pulley to lock it in place. 3. Use the methods shown in Fig. 24 to check proper pulley alignment.
24 Replacing Filters — Filters can be removed and in- stalled from either side of the unit. Install new filters in units that have one fan as follows: 1. Remove the side access panel (retain screws). 2. Remove the filter retainer clip (see Fig. 25).
25 Table 8A — Fan Motor Data, Standard Motor — English Table 8B — Fan Motor Data, Alternate Motor — English UNIT 40RUA*25 40RUS*25 40RUA*28 40RUS*28 40RUA*30 40RUS*30 208/230-3-60 and 460-3-60 Speed (rpm) 1745 1745 1745 Hp 5.0 7.5 10.0 Frame (NEMA) S184T S213T S215T Shaft Dia (in.
26 Table 8C — Fan Motor Da ta, Standard Motor — SI Table 8D — Fan Motor Da ta, Alternate Motor — SI UNIT 40RUA*25 40RUS*25 40RUA*28 40RUS*28 40RUA*30 40RUS*30 208/230-3-60 and 460-3-60 Speed (r/s) 29.08 29.08 29.08 Shaft kW 3.73 5.60 7.46 Frame (NEMA) S184T S213T S215T Shaft Dia (mm) 2 8 .
27 Table 9A — Standard Drive Data, 60 Hz — English Table 9B — Medium-Static Drive Data, 60 Hz — English UNIT 40RUA*25 40RUS*25 40RUA*28 40RUS*28 40RUA*30 40RUS*30 MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 3.7-4.7 4.3-5.3 4.3-5.3 Pulley Factory Setting Full T urns Open 3.
28 Table 9C — High-Stat ic Drive Data, 6 0 Hz — English Table 9D — Standa rd Drive Data, 60 Hz — SI UNIT 40RUA*25 40RUS*25 40RUA*28 40RUS*28 40RUA*30 40RUS*30 MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 4.3-5.3 4.3-5.3 4.3-5.3 Pulley Factory Setting Full T urns Open 3.
29 Table 9E — Medium-Static Drive Data, 60 Hz — SI Table 9F — High-Static Drive Data, 60 Hz — SI UNIT 40RUA*25 40RUS*25 40RUA*28 40RUS*28 40RUA*30 40RUS830 MOTOR DRIVE Motor Pulley Pitch Diameter (mm ) 109.2- 134.6 109.2- 134.6 109.2- 134.6 Pulley Factory Setting Full T urns Open 3.
30 Table 10A — 40RU Standard Fan Performa n ce Data — 0.0-2.4 in. wg External Static Pressure — English See Legend and Notes on page 34. Table 10A — 40RU Standard Fan Performa n ce Data — 0.0-2.4 in. wg Extern al Static Pressure — English (cont) See Legend and Notes on page 34.
31 Table 10B — 40RU Standard Fan Performance Data — 0-600 kPa External Static Pressure — SI See Legend and Notes on page 34. Table 10B — 40RU Standard Fan Performance Data — 0-600 kPa External Static Pressure — SI (cont) See Legend and Notes on page 34.
32 Table 10C — 4 0RU High-Capacity Fan Performance Data — 0.0-2.4 in. wg External Static Pressure — English See Legend and Notes on page 34. Table 10C — 4 0RU High-Capacity Fan Performance Data — 0.0-2.4 in. wg Extern al Static Pressure — English (cont) See Legend and Notes on page 34.
33 Table 10D — 4 0RU High-Capacity Fan Performance Data — 0-600 kPa External Static Pressure — SI See Legend and Notes on page 34. Table 10D — 4 0RU High-Capacity Fan Performance Data — 0-600 kPa External Static Pressure — SI (cont) See Legend and Notes on page 34.
Copyright 2009 Ca rrier Corp • 7310 W . Morris S t. • Indianapolis, IN 46231 Printed in Mexico Edition Date: 09/09 Catalog No: 40RU-03SI Manufacturer reserves the right to change, at any time, spec ifica tions and designs without notice and without obligations.
CL-1 ST A RT -UP CHECKLIST (SPLIT SYSTEMS WITH 40RU UNITS) I. PRELIMINAR Y INFORMA TION OUTDOOR: MODEL NO. _______________ __________ SERIAL NO. __________________ _________________ INDOOR: MODEL NO.
Copyright 2009 Carr ier Corp • 7310 W . Morris S t. • Indianapolis, IN 46231 Printed in Mexico Edition Date: 09/09 Catalog No: 40RU-03SI Manufacturer reserves the right to change, at any time, spec ifications and designs without notice and without obligations.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Carrier REFRIGERANT R-410A è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Carrier REFRIGERANT R-410A - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Carrier REFRIGERANT R-410A imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Carrier REFRIGERANT R-410A ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Carrier REFRIGERANT R-410A, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Carrier REFRIGERANT R-410A.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Carrier REFRIGERANT R-410A. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Carrier REFRIGERANT R-410A insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.