TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 13 SEER – R-410A MODELS: YZB018 THRU 060 (1.5 THRU 5 NOMINAL T ONS) Due to continuou s prod uc t im prov e m en t, specification s are subjec t to ch an ge without notice. Visit us on the web at www .
271457-YTG-B-0908 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge with- out notice. Certified dimensions will be provi ded upon request.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 3 * Does not achieve 13 SEER with PSC furnaces. For ratings, see technical guide or visit www .aridirectory .
271457-YTG-B-0908 4 Johnson Controls Unitary Products — = Not applicable. Go to www.ari.org/aridirectory for the latest additional match es. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - Upflow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL S EN S. YZB0181 1 450 750 14,17 FC/MC/PC/UC18 600 18.
271457-YTG-B-0908 6 Johnson Controls Unitary Products COOLING CAP ACITY - YZB0181 1 With V ariable Speed Furnace s V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC18A 14 600 18.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - YZB0241 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER TO T A L S E N S . 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC24A 14 750 23.
271457-YTG-B-0908 8 Johnson Controls Unitary Products COOLING CAP ACITY - YZB0301 1Wit h V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC36A 14 1050 30.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 9 G*9V*B12 HD36 17 985 29.2 20.8 13.70 1 1.70 G*9V*C16 HD36 21 1005 29.2 20.8 13.90 1 1.90 G*9V*C20 HD36 21 1045 29.2 20.8 13.80 1 1.70 G*9V*A12 UC30A 14 1000 29.4 21.0 13.80 1 1.60 G*9V*A12 UC36A 14 1000 29.
271457-YTG-B-0908 10 Johnson Controls Unitary Products Y*(8,L)C*B12 HD48 17 1210 34.0 25.4 13.60 1 1.30 Y*(8,L)C*C16 HD48 21 1210 34.2 25 .6 14.10 1 1.70 Y*(8,L)C*C20 HD48 21 1 155 34 .4 25.8 14.30 1 1.80 Y*9C*B12 HD48 17 1 150 34.0 25.4 13.50 1 1.20 Y*9C*C16 HD48 21 1 195 34.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 11 COOLING CAP ACITY - YZB0421 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER TO T A L S E N S . 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 PV8*C16 FC/MC/PC48C 21 1400 41.
271457-YTG-B-0908 12 Johnson Controls Unitary Products COOLING CAP ACITY - YZB0481 1Wit h V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 P(C,V)9*D20 FC/MC/PC60D 24 1600 46.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 13 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 14 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 15 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 16 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 17 HEA TING CAP ACITY - YZB0301 1Wi th V ariable Speed Furnaces V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA TING 2 47 ° F1 7 ° F HSPF MBH COP KW MBH COP KW STD 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES PV8*A12 FC/MC/PC36A 29.
271457-YTG-B-0908 18 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 19 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 20 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 21 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for heating divided by the total electric power input during the same period.
271457-YTG-B-0908 22 Johnson Controls Unitary Products ACCESSORIES* Hard St art Kit (024-31994-000, 024-31995-000) - Provides increased starting torque for areas with low voltage. TXV Kits - 1 TV09 series the rmal expansion valves precisely meter refrigerant for optimum performan ce.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween.
271457-YTG-B-0908 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween .
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
271457-YTG-B-0908 26 Johnson Controls Unitary Products V ariable Speed Furnace Coil T .C. S.C. KW PV8*A12 FC/MC/PC36A 1.02 0.98 1.0 1 PV9*A12 FC/MC/PC36A 1.01 0.97 1.0 1 PV8*B16 FC/MC/PC36B 1.02 0.98 1.0 3 P(C,V)9*B12 FC/MC/PC36B 1.01 0.97 1.01 PV8*C16 FC/M C/PC36C 1.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 27 Multipliers for determining the pe rformance with other indoor sect ions NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween.
271457-YTG-B-0908 28 Johnson Controls Unitary Products V ariable Speed Furnace Coil T .C. S.C. KW PV8*A12 FC/MC/PC36A 0.99 0.92 1.0 2 PV9*A12 FC/MC/PC36A 0.98 0.92 1.0 2 PV8*B16 FC/MC/PC36B 0.99 0.92 1.0 3 P(C,V)9*B12 FC/MC/PC36B 0.98 0.92 1.02 PV8*C16 FC/M C/PC36C 0.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 29 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
271457-YTG-B-0908 30 Johnson Controls Unitary Products Multipliers for determining th e performance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 7.
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 31 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
271457-YTG-B-0908 32 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA T ING PERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YZB0181 1 INDOOR COIL MODEL NO . FC/MC/PC/UC18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 33 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YZB0241 1 INDOOR COIL MODEL NO. AHP24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
271457-YTG-B-0908 34 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. Continued on Pa ge 35. HEA T ING PERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YZB0301 1 INDOOR COIL MODEL NO . FC/MC/PC/UC36 AIR TEMP .
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 35 V ariable Speed Furnace Coil MBH KW COP PV8*A12 F C/MC/PC36A 0.98 0.98 1.00 PV8*A12 H D36 0.98 0.98 1.00 PV8*B16 F C/MC/PC36B 0.98 0.98 1.00 PV8*B16 H C36 0.98 0.98 1.00 PV8*C16 FC/MC/PC36 C 0.98 0.
271457-YTG-B-0908 36 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. Continued on Pa ge 37. HEA T ING PERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YZB0361 1 INDOOR COIL MODEL NO . FC/MC/PC/UC36 AIR TEMP .
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 37 V ariable Speed Furnace Coil MBH KW COP PV8*A12 F C/MC/PC36A 1.00 0.97 1.00 PV8*B16 F C/MC/PC36B 1.00 0.97 1.00 PV8*B16 H C36 1.00 0.97 1.00 PV8*B16 H D36 1.00 0.97 1.00 PV8*C16 FC/MC/PC36 C 1.00 0.
271457-YTG-B-0908 38 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA T ING PERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YZB0421 1 INDOOR COIL MODEL NO . FC/MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
271457-YTG-B-0908 Johnson Controls Unitary Pro ducts 39 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A OUTDOOR UNIT MODEL NO. YZB0481 1 INDOOR COIL MODE L NO. FC/MC/PC/UC60 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP .
Subject to change without notice. Printe d in U.S.A. 271457-YTG-B-0908 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 271457-YTG-A-0907 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York YZB018 THRU 060 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York YZB018 THRU 060 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York YZB018 THRU 060 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York YZB018 THRU 060 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York YZB018 THRU 060, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York YZB018 THRU 060.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York YZB018 THRU 060. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York YZB018 THRU 060 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.