DESCRIPTION Sunline 2000 units are highly efficient, convertible rooftops. All models ha ve dual re frigeran t circui ts for e fficie nt part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
FIELD-INST ALLED ACCESSORIES SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS Includes a slide-in / plug-in damper assembly with fu lly modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
RA TINGS ® SUNLINE 2000 MODEL DCG (Gas Heating) (OPTION / A CCE SS. ) DCE UNITS D*CG UNI TS (OPTION / ACCESSO RY ) THROW A W A Y ALUMINIZED STEEL FEMALE Model Rating 1 Point T o tal Output, Mbh / kW T otal Input, kW COP 2 EER 3 Sensib le Output, Mbh / kW Latent Out put , Mbh / kW Electric H eat4 Nominal Capac ity , kW D3CE180 T1 159 / 46.
COOLING CAP ACITIES (m 3 /s Air Flow) - 180 UNITS Air On Evapor at or Coil To t a l Cap. 1 kW Power Input 2 kW Sensible C apac ity 1 , k W Entering Dry Bulb T emp ., ° C m 3 /s WB ° C 32 30 28 26 24 22 @27 ° C A ir T emperature on Condens er C oil 3.
COOLING CAP ACITIES (CFM Air Flow) - 180 UNITS Air On Evaporator Coil To t a l Cap. 1 MBH Power Input 2 kW Sensible C apac ity 1 , MBH Enter i ng Dr y Bulb T emp., ° F CFM WB ° F 90 86 82 79 75 72 @80 ° F Air T emperature on Condens er Coil 1 7200 73 227 14.
COOLING CAP ACITIES (m 3 /s Air Flow) - 240 UNITS Air On Evapor at or Coil To t a l Cap. 1 kW Power Input 2 kW Sensible C apac ity 1 , k W Entering Dry Bulb T emp ., ° C m 3 /s WB ° C 32 30 28 26 24 22 @27 ° C A ir T emperature on Condens er C oil 4.
COOLING CAP ACITIES (CFM Air Flow) - 2 40 UNITS Air On Eva porat or Coil To t a l Cap. 1 MBH Power Input 2 kW Sensibl e C apacity 1 , MBH Entering Dry Bu lb T emp., ° F CFM WB ° F 90 86 82 79 75 72 @80 ° F Air T emperature on Condens er Coil 9320 73 274 19.
BLOWER SPEED, RPM MOT OR PULLEY (TURNS OPEN)* AIRFLOW 2.10 m 3 /s 2.45 m 3 /s 2.80 m 3 /s 3. 10 m 3 /s 3. 40 m 3 /s ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) 845 6.
BLOWER SPEED, RPM MOTOR PULLEY (TURNS OPEN)* AIRFLOW 2.80 m 3 /s 3.30 m 3 /s 3.80 m 3 /s 4.10 m 3 /s 4. 40 m 3 /s ESP (Pa) Output (kW) Input (kW ) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) Input (kW) ESP (Pa) Output (kW) I nput (kW) 7 6 5 6 .
BLOWER SPEED, RPM MOTOR PULLEY (TURNS OPEN)* AIRFLOW 4450 CFM 5190 CFM 5930 CFM 6565 C FM 7200 CFM ESP (iwg) Output (bhp) Input (kW) ESP (iwg) Output (bhp) Input (kW) ESP (iwg) Output (bhp) Input (kW) ESP (iwg) Output (bhp) Input (kW ) ESP (iwg) Output (bhp) Input (kW ) 845 6.
BLOWER SPEED, RPM MOT OR PULLEY (TURNS OPEN)* AIRFLOW 5930 CFM 6990 CFM 8050 CFM 8685 CFM 9320 CFM ESP (iw g) Output (bhp) Input (kW) ESP (iwg) Output (bhp) Input (kW ) ESP (iwg) Output (bhp) Input (kW ) ESP (iwg) Output (bhp) Input (kW) ESP (iwg) Output (bhp) Input (kW) 7 6 5 6 .
UNIT SIZE BLOWER RANGE (RPM) MOTOR 1 ADJUST ABLE MOTOR P ULLEY 2 FI XED BLOWER PULLEY BEL T (NOTCHED) kW/HP FRAME SIZE EFF . (%) PITCH DIA. (mm/in.) BORE (mm/in.) DESIG- NA TI ON PITCH DIA. (mm / in.) BORE (mm/in.) DESIG- NA TI ON PITCH LENGTH (mm/in.
UNIT SIZE POWER SUPPL Y COMPRESSOR OUTDOOR FA N MOT OR, (#1 & #2) FLA, EA C H SUPPL Y AIR BLOWER MOTOR , (FLA) TOT AL UNIT AMP AC ITY , (AMPS) MAX. FUSE SIZE 1 MIN. WIRE SIZE 2 , (mm 2 /A WG) RLA LRA 3 kW 4 HP 5. 6 kW 7.5 HP 3 kW 4 HP 5.6 kW 7.5 HP #1 #2 #1 #2 180 380/400/415-3+N-50 19.
UNIT SIZE POWER SUPPL Y (VOL TS) HEA TER OPTION MINIMUM CIRCU IT AMP ACITY (AMPS) MAXIMUM FUSE SIZE 1 MINIMUM WIRE SIZE 2 (mm 2 /A W G) MODEL OUTPU T kW ST AGES AM PS 180 380-3+N-50 E018 E036 E054 E072 11 . 3 22.6 33.8 45.1 1 2 2 2 17.1 34.3 51.4 68.6 47.
All dimens ions are in mi llimeters and inches, unless other wise specified. They are subj ect to change without no tice. Certified dimensions wi ll be pr ov ided u p on reques t.
UNIT DIMENSIONS - D*CG180 & 240 UNITS 1235 (48-5/8 " ) (1 8 0 ) 1337 (52-5/8 " ) (2 4 0 ) 3181 (125 -1/4") (180 ) 3561 (136 -1/4") (240 ) 616 (24-1 /4") (180 ) 895 (35-1 /4") (240 ) HOLE OPENING DIAMETER * (in. / mm) USED FOR A 1-1/8 / 29 K O Control Wirin g Front 3/4 NPS / 19 (Fem.
UNIT DIMENSIONS - D* CE / D*CG180 & 240 UNITS (Cont’ d.) DUCT C O V E R S - Uni ts ar e shi pped w i th the bot tom duct opening s covered. An acce ssory flange kit is available for c onnec ting s ide ducts . For do wnf l o w duct appli c ations : 1.
ROOF CURB DIMENSIONS - D* CE / D*CG180 & 240 UNITS ROOF CURB BENEFITS 2927 (115-1/4") ( 180) 3207 (126 -1/4") (240) UNIT AND CURB APPLICA TION TYPICAL APPLICA T IONS 362 (14-1/4") (.
TYPICAL APPLICA TIONS - Cont’d. ROOF-TOP INST A LLA TION (GAS/E LECTRIC UNIT SHO WN) 530.26-TG3YI Unitary P roducts Group 19.
P . O. Box 1592, Y or k, Pennsylvani a USA 17405-1592 Subject to cha ng e without notice. P rinted in U.S.A Copyright by Y ork International Corp oration 1994 .
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il York D3CG è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del York D3CG - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso York D3CG imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul York D3CG ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il York D3CG, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del York D3CG.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il York D3CG. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo York D3CG insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.