Inst allation and Maintenance Series EHU-700 Humidifiers Please Read And Save These Instructions The Armstrong Series EHU-700 humidifier is an electronically controlled, non-pressurized steam-generating humidifier , with its vapor discharged into a duct of an air-handling system or through a fan package.
DANGER ELECTRICAL SHOCK HAZARD HIGH VOL T AGES EXIST INSIDE THE HUMIDIFIER T o protect yourself and others from accidental shocks: 1. Keep the humidifier locked during normal operation and store the key in a safe location away from the humidifier . 2.
T ABLE OF CONTENTS 3 SECTION 1: PREP ARA TION AND INST ALLA TION W ARNINGS.................................................................................................................. 2 PRE-INST ALLA TION..........................................
PRE-INST ALLA TION 1) CHECK SHIPMENT A claim should be filed with the transportation comp any (and reported to Armstrong) if any items are missing or damaged.
The mounting surface should be a wall capable of supporting the maximum humidifier weight. The maximum operating weight is: The location chosen should be inside with a minimum ambient temperature of 40°F . and a maximum of 100°F . The humidifier should not be mounted on hot surfaces.
INST ALLA TION 4) MOUNTING THE HUMIDIFIER MODEL EHU-701: Making sure the unit is level, hold it against the mounting surface and mark the hole pattern. Attach the unit s to studs or other sturdy structure with the two 3/8"× 1½" lag screws provided.
6) W A TER FILL SUPPL Y Connect the unit to the building water supply (25 to 125 psig pressure). Inst all a shut-off valve near the humidifier . Connect the water supply to the 3/8" tube compression fitting on the fill valve adaptor . NOTE: ORDINARY (POT ABLE) T AP W A TER IS RECOMMENDED.
c. Use the template provided to cut installation holes in the duct for the dispersion tube as in Figure 7-2 (and optional drain tube, Figure 7-3). d. Insert the dispersion tube into the duct so the holes face upward. Fasten the mounting plate to the outside of the duct with sheet metal screws.
CONTROL WIRING NOTE: Wiring to the low-voltage controls should not run in the same conduit s as the power supply wiring because faulty signals could result. The use of either a metal conduit or shielded wire is required for all the control and / or safety wiring.
W all Mounted Control Humidist at: W all-mounted humidistat s are usually installed 4 f t. to 5 ft. above floor level. Of ten, the best location is beside a thermostat that controls temperature in the.
Duct Mounted Control Humidist at: Duct-mounted control humidistat s are also available for installation where sensing and control of return air or exhaust air ducts is preferable. (Figure 10-1) Please refer to manufacturer's recommendations for further information on the location, mounting, and operation of the various control humidistat s.
12) AUDIBLE ALARM There is an external alarm circuit provided. When an alarm condition is detected in the diagnostic routines, a relay contact closes allowing activation of an external Class II device connected between terminals 27 & 28. This circuit is rated to 1 amp.
INSTRUMENT P ANEL The Mode select button is depressed for approximately ½ second to switch both the "display mode selected" indicator and the 3 MODE BUTTON, digit display between: INDICA TOR, -DEMAND- % of humidistat control range. and DISPLA Y -CURRENT - actual current in amps.
ST ART -UP PROCEDURE FOR ARMSTRONG SERIES EHU-700 HUMIDIFIERS The following steps should be performed on all newly inst alled Series EHU-700 Humidifiers to ensure that the humidifier and the entire humidification system functions correctly .
If the stat demand display is greater than 35% and the unit does not begin filling, press the mode select button three times and the diagnostic mode indicator will light. Note the diagnostic message and refer to the diagnostics information in the troubleshooting section of this manual (page 20).
15) V erify that all of the input/output circuits are functioning properly by entering the input/output diagnostics mode. Press the mode button until the diagnostics indicator lights and wait ten seconds. The unit will do a complete self-diagnostic check.
TROUBLESHOOTING GUIDE CAUTION!: Disconnect the electric power supply at the circuit breaker or switch whenever the unit is to be inspected or serviced. DO NOT USE THE T ANK ON/OFF SWITCH ON THE HUMIDI- FIER BECAUSE THIS SWITCH DISCONNECTS THE STEAM GENERA TOR T ANK ONL Y .
A high-water float switch prevents water carry-over into the duct due to an excessive water level in the tank. When the high water limit is reached the HIGH W A TER light comes on and the fill valve is blocked until some water is boiled away and the water level drops.
Monitoring Current: While the unit is filling, the current should increase. As the current approaches the maximum rating of the unit, it increases more slowly , especially in higher capacity units. With the t ank on, and the fill and drain circuits idle, the current should fall slowly .
EHU-700 DIAGNOSTICS THE Series EHU-700 has built in diagnostics to detect system problems early , before they become severe. If possible, the diagnostic routine performs corrective measures. If necessary , the unit is shut- down and a dry contact is closed to enable a remote alarm.
C04: HIGH LIMIT CIRCUIT : When the humidity in the duct reaches the high limit stat set-point, the circuit will open and the microcontroller will de-energize the contactor . The diagnostic mode will display the message C04 and the fill solenoid is blocked.
C09: I/O DIAGNOSTICS If the display mode selection is left in the diagnostic mode for 10 seconds, the Input/Output circuit diagnostic check will begin. The display will show the message C09, the t ank will be off, and the diagnostics mode light will remain on.
W A TER QUALITY AND TREA TMENT FOR EHU SERIES HUMIDIFIERS GENERAL Series EHU 700 electronic humidifiers use ordinary tap water in their operation. The quality of this water affect s both the operation and the maintenance of the humidifier . How the EHU works: The EHU is an electrode boiler .
Result s: -Excessive time needed to reach set point during star-up. -Poor humidity control. Remedy: -Add 1/2 teaspoon of Epsom salt s to the fill cup. After start-up the automatic drain program should maintain the unit at full cap acity . -If problem persists, cont act the factory .
25 See Drawings on Page 28 EHU-701, -703, -704 Series Electronic Steam Hu midifier Repa ir Parts Item Part N o. Descr iption Used On *1A D4417 1 Ph Low Voltage 120,208,240,277 Volts 701 *1B D4418 1 Ph.
26 Item Part No. Description Use d On 15 B2717 Drain Valv e Assembly w/ H ose & (2) Clamps 701,703,704 16A B2582A-1 Float Switch Assembly 701,703,704 16B B2582A-2 Float Switch Assembly (Far Tank) .
27 Electrical Parts Item Part No. Description Used On 46 C2059 Display PC Board 701,703,704 47A A22925 Control PC Board Less Current M odule 701 47B A22926 Control PC Board Less Current M odule 703,70.
Figure 28-1. EHU-700 Parts List Figure 28-2. EHU-700 Steam Generator Repair Parts List 28 23 40 29 47 48 46 55 52 51 61 21 34 20 22 57 50 62 53 54 49 19 33 15 56 42 17 16 25 30 31 32 18 6 8 14 12 6 11.
MAINTENANCE RECOMMENDED MAINTENANCE SCHEDULE 1 TO 2 DA YS AFTER 1) Check unit operation. ST ART UP 2) Look in drain pan for leaks. 3) Check steam piping for leaks.
If the electrodes begin to disintegrate, the tank may turn black or red, and arcing or flashing may be visible inside the tank while it is operating. IF YOU NOTICE EXCESSIVE ARCING , SHUT THE UNIT OFF AND CALL THE F ACTORY BEFORE RE-ST ARTING UNIT .
STEAM GENERA T OR CHEMICAL CLEANING PROCEDURE This procedure is intended as a guide only for the chemical cleaning of the generator in all EHU mod- els. Read and follow label directions on any cleaning product. Check local codes before disposing of chemicals.
12) Reassemble tank. Make sure o-rings are still on electrode terminals. Also check condition of steam generator o-ring. After a couple cleanings, it will need to be replaced. Make sure o-ring is sealed in its groove and not pinched when halves are put together .
T ANK DISASSEMBL Y , CLEANING , AND ELECTRODE REPLACEMENT MODELS EHU-703 AND 704, SINGLE AND THREE PHASE 1) Using a 7/16" wrench, disconnect the jumper wires from the steam generator . 2) Remove 24 metal clip s by pushing gently on top of each clip with a screwdriver while cupping the clip with the other hand.
MODEL EHU-701, SINGLE AND THREE PHASE Figure 35-1 1) Remove 24 metal clip s by pushing gently on top of each clip with a screwdriver while cupping the clip with the other hand. 2) Clean the inside of the steam generator thoroughly unsing a scraper , stiff bristle brush and/or water spray and rinse with clear water .
b) While the tank is out, look into the lower end of the t ank. Make sure the drain screen is in place. Also check for accumulations of lime at the bottom of the tank. Refer to "S team Generator Disassembly" and "Cleaning Procedure" sections to rectify these problems.
HUMIDIST A T DA T A AUTOCAL PROCEDURE 1. Measure the room humidity near the humidistat with an accurate hygrometer . 2. T urn the humidistat set point dial to match the reading of the hygrometer . 3. Push and hold the Autocal button for more than 3 seconds or until the internal red light turns On and Off.
DIMENSIONS Figure 37-1. Dimension drawing. Duct Humidistat Note: S pecifications and equipment are subject to change without prior notice. T ABLE 5: SENSOR CHARACTERISTICS V oltage between black and w.
AIR SUPPL Y HIGH LIMIT HUMIDITY SENSOR The A 17898 (H270) includes a high limit circuit. This allows the use of a second humidity in the supply air . Input signal goes to terminals #8 on the humidistat. High limit set point is preprogrammed at 85%. It can be readjusted using the A19517 service tool.
APPLICA TION EXAMPLE S team humidification system controlled by a 0 to 10 Vdc valve wired to output #1. Remote humidity display using 0 to 5 Vdc signal is wired to output #2. The humidity sensor is located in the return air duct. A proportional high limit humidity sensor is installed in the supply duct.
Dimensional Information Limited Warranty and Remedy A H Q A H I S B B M K E G EHU-704 R K K E E M M EHU-703 EHU-701 S J J D D L L C Side Side P Conn. for Dispersion 2" ID Hose Conn.
Un punto importante, dopo l’acquisto del dispositivo (o anche prima di acquisto) è quello di leggere il manuale. Dobbiamo farlo per diversi motivi semplici:
Se non hai ancora comprato il Armstrong World Industries EHU-701 è un buon momento per familiarizzare con i dati di base del prodotto. Prime consultare le pagine iniziali del manuale d’uso, che si trova al di sopra. Dovresti trovare lì i dati tecnici più importanti del Armstrong World Industries EHU-701 - in questo modo è possibile verificare se l’apparecchio soddisfa le tue esigenze. Esplorando le pagine segenti del manuali d’uso Armstrong World Industries EHU-701 imparerai tutte le caratteristiche del prodotto e le informazioni sul suo funzionamento. Le informazioni sul Armstrong World Industries EHU-701 ti aiuteranno sicuramente a prendere una decisione relativa all’acquisto.
In una situazione in cui hai già il Armstrong World Industries EHU-701, ma non hai ancora letto il manuale d’uso, dovresti farlo per le ragioni sopra descritte. Saprai quindi se hai correttamente usato le funzioni disponibili, e se hai commesso errori che possono ridurre la durata di vita del Armstrong World Industries EHU-701.
Tuttavia, uno dei ruoli più importanti per l’utente svolti dal manuale d’uso è quello di aiutare a risolvere i problemi con il Armstrong World Industries EHU-701. Quasi sempre, ci troverai Troubleshooting, cioè i guasti più frequenti e malfunzionamenti del dispositivo Armstrong World Industries EHU-701 insieme con le istruzioni su come risolverli. Anche se non si riesci a risolvere il problema, il manuale d’uso ti mostrerà il percorso di ulteriori procedimenti – il contatto con il centro servizio clienti o il servizio più vicino.